<?xml version="1.0" encoding="iso-8859-1"?>
<?xml-stylesheet href="http://types.lonmark.org/templates/index.xsl" type="text/xsl"?>
<!-- created by Report Generator 4.01.07 at Sun May 26 11:30:07 2013 -->
<ldrf>
	<control>
		<xsl>index.xsl</xsl>
		<self>cps.xml</self>
		<base>http://types.lonmark.org</base>
		<folder>0000000000000000-0</folder>
		<standard>http://types.lonmark.org</standard>
		<tools>http://types.lonmark.org/templates</tools>
		<set>Standard 00:00:00:00:00:00:00:00-0</set>
		<html>index.html</html>
		<generator>Report Generator 4.01.07</generator>
		<group>Configuration Properties</group>
		<selector>0</selector>
		<data-version>14.00</data-version>
		<format-version>6.00</format-version>
		<timestamp>12/13/2012 18:20:12</timestamp>
		<url>tech@lonmark.org</url>
		<description id="0-1"/>
		<creator id="0-2"/>
	</control>
	<items>
		<cpt id="SCPTOLCLimits" idx="345" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0 0 0 0,00000 0,0 0,0</default>
			<size>22</size>
			<aggregate cat="struct">
				<members>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_amp_ac_mil</ref>
						<name id="0-5022"/>
						<p-name>lamp_current_high</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_amp_ac_mil</ref>
						<name id="0-5023"/>
						<p-name>lamp_current_low</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_amp_ac_mil</ref>
						<name id="0-5024"/>
						<p-name>main_current_high</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_amp_ac_mil</ref>
						<name id="0-5025"/>
						<p-name>main_current_low</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_volt_ac</ref>
						<name id="0-5026"/>
						<p-name>lamp_voltage_high</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_volt_ac</ref>
						<name id="0-5027"/>
						<p-name>lamp_voltage_low</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_volt_ac</ref>
						<name id="0-5028"/>
						<p-name>main_voltage_high</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_volt_ac</ref>
						<name id="0-5029"/>
						<p-name>main_voltage_low</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_pwr_fact</ref>
						<name id="0-5030"/>
						<p-name>power_factor_low</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_power</ref>
						<name id="0-5031"/>
						<p-name>power_high</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_power</ref>
						<name id="0-5032"/>
						<p-name>power_low</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5020"/>
			<comment id="0-5021"/>
			<p-name>SCPTOLCLimits</p-name>
			<formats>
				<format id="SCPTOLCLimits">
					text(&quot;%d %d %d %d %d %d %d %d %f %f %f&quot;,  lamp_current_high, lamp_current_low, main_current_high, main_current_low, lamp_voltage_high, lamp_voltage_low, main_voltage_high, main_voltage_low, power_factor_low, power_high, power_low)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPToutdoorLuminairController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTactFbDly" idx="1" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>0 0:0:59:999</max>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-408"/>
			<comment id="0-409"/>
			<p-name>SCPTactFbDly</p-name>
			<formats>
				<format id="SCPTactFbDly">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTactFbDly#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTactuatorCharacteristic" idx="284" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>DCM_SPEED_CONST</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_dev_c_mode</ref>
			<name id="0-3211"/>
			<comment id="0-3212"/>
			<p-name>SCPTactuatorCharacteristic</p-name>
			<formats>
				<format id="SCPTactuatorCharacteristic">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTactuatorType" idx="41" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*31</default>
			<size>31</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_str_asc</ref>
			<name id="0-663"/>
			<comment id="0-975"/>
			<p-name>SCPTactuatorType</p-name>
			<formats>
				<format id="SCPTactuatorType">text(&quot;%s&quot;, ascii)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfireSmokeDamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTahamApplianceModel" idx="304" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>AHAM_CLOTHES_WASHER</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>6</max>
				<idx>67</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">aham_appl_t</ref>
			</enum>
			<name id="0-3387"/>
			<comment id="0-3388"/>
			<p-name>SCPTahamApplianceModel</p-name>
			<formats>
				<format id="SCPTahamApplianceModel">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclothesWasherDomestic</ref>
			</refs>
		</cpt>
		<cpt id="SCPTairTemp1Alrm" idx="132" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,000</min>
			<max>100,000</max>
			<default>100,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-790"/>
			<comment id="0-791"/>
			<p-name>SCPTairTemp1Alrm</p-name>
			<formats>
				<format id="SCPTairTemp1Alrm">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTairTemp1Day" idx="126" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,000</min>
			<max>100,000</max>
			<default>100,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-778"/>
			<comment id="0-779"/>
			<p-name>SCPTairTemp1Day</p-name>
			<formats>
				<format id="SCPTairTemp1Day">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTairTemp1Night" idx="131" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,000</min>
			<max>100,000</max>
			<default>100,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-788"/>
			<comment id="0-789"/>
			<p-name>SCPTairTemp1Night</p-name>
			<formats>
				<format id="SCPTairTemp1Night">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTalrmClrT1" idx="2" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>0 0:0:59:999</max>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-410"/>
			<comment id="0-411"/>
			<p-name>SCPTalrmClrT1</p-name>
			<formats>
				<format id="SCPTalrmClrT1">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTalrmClrT1#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTalrmClrT2" idx="3" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>0 0:0:59:999</max>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-412"/>
			<comment id="0-508"/>
			<p-name>SCPTalrmClrT2</p-name>
			<formats>
				<format id="SCPTalrmClrT2">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTalrmClrT2#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTalrmIhbT" idx="4" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>0 0:0:59:999</max>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-413"/>
			<comment id="0-414"/>
			<p-name>SCPTalrmIhbT</p-name>
			<formats>
				<format id="SCPTalrmIhbT">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTalrmIhbT#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTalrmSetT1" idx="5" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>0 0:0:59:999</max>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-415"/>
			<comment id="0-416"/>
			<p-name>SCPTalrmSetT1</p-name>
			<formats>
				<format id="SCPTalrmSetT1">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTalrmSetT1#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTalrmSetT2" idx="6" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>0 0:0:59:999</max>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-417"/>
			<comment id="0-418"/>
			<p-name>SCPTalrmSetT2</p-name>
			<formats>
				<format id="SCPTalrmSetT2">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTalrmSetT2#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTareaDuctHeat" idx="266" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>13,1070</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_area</ref>
			<name id="0-2233"/>
			<comment id="0-2234"/>
			<p-name>SCPTareaDuctHeat</p-name>
			<formats>
				<format id="SCPTareaDuctHeat#SI">text(&quot;%f&quot;)</format>
				<format id="SCPTareaDuctHeat#US">text(&quot;%f&quot;, *10.7639+0(0:884))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTaudOutput" idx="144" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_sound_db</ref>
			<name id="0-816"/>
			<comment id="0-817"/>
			<p-name>SCPTaudOutput</p-name>
			<formats>
				<format id="SCPTaudOutput">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTaudibleFireIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTaudibleLevel" idx="228" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0 0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_switch</ref>
			<name id="0-1341"/>
			<comment id="0-1342"/>
			<p-name>SCPTaudibleLevel</p-name>
			<formats>
				<format id="SCPTaudibleLevel">text(&quot;%f %d&quot;, value, state)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorVoiceAnnouncer</ref>
			</refs>
		</cpt>
		<cpt id="SCPTautoAnswer" idx="177" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>BOOL_FALSE</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>1</max>
				<idx>41</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">boolean_t</ref>
			</enum>
			<name id="0-1241"/>
			<comment id="0-1242"/>
			<unit id="0-153"/>
			<p-name>SCPTautoAnswer</p-name>
			<formats>
				<format id="SCPTautoAnswer">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTmodemController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTbaseValue" idx="164" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 RVU_NONE 0</default>
			<size>6</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_reg_val</ref>
			<name id="0-1030"/>
			<comment id="0-1031"/>
			<p-name>SCPTbaseValue</p-name>
			<formats>
				<format id="SCPTbaseValue">text(&quot;%d %m %d&quot;, raw, unit, nr_decimals)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTutilityDataLoggerRegister</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTutilityMeter</ref>
			</refs>
		</cpt>
		<cpt id="SCPTbkupSchedule" idx="344" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0</default>
			<size>4</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>23</max>
							<invalid>255</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-5012"/>
						<comment id="0-5013"/>
						<unit id="0-96"/>
						<p-name>hour_on</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>59</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-5014"/>
						<comment id="0-5015"/>
						<unit id="0-97"/>
						<p-name>minute_on</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>23</max>
							<invalid>255</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-5016"/>
						<comment id="0-5017"/>
						<unit id="0-96"/>
						<p-name>hour_off</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>59</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-5018"/>
						<comment id="0-5019"/>
						<unit id="0-40"/>
						<p-name>minute_off</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5011"/>
			<p-name>SCPTbkupSchedule</p-name>
			<formats>
				<format id="SCPTbkupSchedule">text(&quot;%d %d %d %d&quot;,  hour_on, minute_on, hour_off, minute_off)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPToutdoorLuminairController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTblockProtectionTime" idx="251" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_hour</ref>
			<name id="0-1394"/>
			<comment id="0-1395"/>
			<p-name>SCPTblockProtectionTime</p-name>
			<formats>
				<format id="SCPTblockProtectionTime">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTbrightness" idx="230" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0 0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_switch</ref>
			<name id="0-1345"/>
			<comment id="0-1346"/>
			<p-name>SCPTbrightness</p-name>
			<formats>
				<format id="SCPTbrightness">text(&quot;%f %d&quot;, value, state)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorDirectionLantern</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorHallLantern</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorPositionIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTbuildingStaticPressureSetpoint" idx="193" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>25</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_press_p</ref>
			<name id="0-1273"/>
			<comment id="0-1274"/>
			<p-name>SCPTbuildingStaticPressureSetpoint</p-name>
			<formats>
				<format id="SCPTbuildingStaticPressureSetpoint#SI">text(&quot;%f&quot;)</format>
				<format id="SCPTbuildingStaticPressureSetpoint#US">text(&quot;%f&quot;, *0.0040217+0(0:954))</format>
				<format id="SCPTbuildingStaticPressureSetpoint#US_psi">text(&quot;%f&quot;, *1.4504e-4+0(0:875))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTbuttonColor" idx="312" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0</default>
			<size>6</size>
			<aggregate cat="struct">
				<members>
					<member>
						<aggregate cat="struct">
							<members>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>255</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-3693"/>
									<comment id="0-3694"/>
									<p-name>red</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>255</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-3695"/>
									<comment id="0-3696"/>
									<p-name>green</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>255</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-3697"/>
									<comment id="0-3698"/>
									<p-name>blue</p-name>
								</member>
							</members>
						</aggregate>
						<name id="0-3691"/>
						<comment id="0-3692"/>
						<p-name>on_color</p-name>
					</member>
					<member>
						<aggregate cat="struct">
							<members>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>255</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-3693"/>
									<comment id="0-3701"/>
									<p-name>red</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>255</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-3695"/>
									<comment id="0-3702"/>
									<p-name>green</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>255</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-3697"/>
									<comment id="0-3703"/>
									<p-name>blue</p-name>
								</member>
							</members>
						</aggregate>
						<name id="0-3699"/>
						<comment id="0-3700"/>
						<p-name>off_color</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-3689"/>
			<comment id="0-3690"/>
			<p-name>SCPTbuttonColor</p-name>
			<formats>
				<format id="SCPTbuttonColor">text(&quot;%d %d %d %d %d %d&quot;,  on_color.red, on_color.green, on_color.blue, off_color.red, off_color.green, off_color.blue)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
			</refs>
		</cpt>
		<cpt id="SCPTbuttonHoldAction" idx="314" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>BTA_TOGGLE_STATE 0,0 </default>
			<size>2</size>
			<aggregate cat="struct">
				<members>
					<member>
						<enum>
							<min>-1</min>
							<max>41</max>
							<idx>68</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">button_action_t</ref>
						</enum>
						<name id="0-3679"/>
						<comment id="0-3680"/>
						<p-name>action</p-name>
					</member>
					<member>
						<aggregate cat="union">
							<members>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>1</min>
										<max>255</max>
										<invalid>0</invalid>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-3683"/>
									<comment id="0-3684"/>
									<p-name>scene_number</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>64</max>
										<invalid>255</invalid>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-4138"/>
									<comment id="0-4139"/>
									<p-name>group_number</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>200</max>
										<invalid>255</invalid>
										<scaling>
											<a>5</a>
											<b>-1</b>
											<c>0</c>
											<s>0.5</s>
										</scaling>
									</scalar>
									<name id="0-3685"/>
									<comment id="0-3686"/>
									<p-name>value</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>180</max>
										<invalid>255</invalid>
										<scaling>
											<a>2</a>
											<b>0</b>
											<c>0</c>
											<s>2</s>
										</scaling>
									</scalar>
									<unit id="0-375"/>
									<p-name>angle</p-name>
								</member>
							</members>
						</aggregate>
						<name id="0-3681"/>
						<comment id="0-3682"/>
						<p-name>setting</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-3677"/>
			<comment id="0-3678"/>
			<p-name>SCPTbuttonHoldAction</p-name>
			<formats>
				<format id="SCPTbuttonHoldAction">
					text((&quot;%m &quot;, action),((action == 1) ? (&quot;%d &quot;, setting.scene_number) :((action == 3) ? (&quot;%d &quot;, setting.scene_number) :((action == 15) ? (&quot;d &quot;, setting.angle) :((action == 16) ? (&quot;%d &quot;, setting.angle) :((action == 17) ? (&quot;%d &quot;, setting.angle) :((action == 20) ? (&quot;%d &quot;, setting.scene_number) :((action == 34) ? (&quot;%d &quot;, setting.group_number) :((action == 35) ? (&quot;%d &quot;, setting.group_number) :((action == 36) ? (&quot;%d &quot;, setting.group_number) :((action == 255) ? (&quot;UNKNOWN &quot;) :(&quot;%f &quot;,  setting.value))))))))))))
				</format>
			</formats>
		</cpt>
		<cpt id="SCPTbuttonPressAction" idx="311" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>BTA_TOGGLE_STATE 0,0 </default>
			<size>2</size>
			<aggregate cat="struct">
				<members>
					<member>
						<enum>
							<min>-1</min>
							<max>41</max>
							<idx>68</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">button_action_t</ref>
						</enum>
						<name id="0-3679"/>
						<comment id="0-3680"/>
						<p-name>action</p-name>
					</member>
					<member>
						<aggregate cat="union">
							<members>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>1</min>
										<max>255</max>
										<invalid>0</invalid>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-3683"/>
									<comment id="0-3684"/>
									<p-name>scene_number</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>64</max>
										<invalid>255</invalid>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-4138"/>
									<comment id="0-4139"/>
									<p-name>group_number</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>200</max>
										<invalid>255</invalid>
										<scaling>
											<a>5</a>
											<b>-1</b>
											<c>0</c>
											<s>0.5</s>
										</scaling>
									</scalar>
									<name id="0-3685"/>
									<comment id="0-3686"/>
									<p-name>value</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>signed short</nc-type>
										<min>-90</min>
										<max>90</max>
										<invalid>127</invalid>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<unit id="0-375"/>
									<p-name>angle</p-name>
								</member>
							</members>
						</aggregate>
						<name id="0-3681"/>
						<comment id="0-3682"/>
						<p-name>setting</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-3704"/>
			<comment id="0-3705"/>
			<p-name>SCPTbuttonPressAction</p-name>
			<formats>
				<format id="SCPTbuttonPressAction">
					text((&quot;%m &quot;, action),((action == 1) ? (&quot;%d &quot;, setting.scene_number) :((action == 3) ? (&quot;%d &quot;, setting.scene_number) :((action == 15) ? (&quot;d &quot;, setting.angle) :((action == 16) ? (&quot;%d &quot;, setting.angle) :((action == 17) ? (&quot;%d &quot;, setting.angle) :((action == 20) ? (&quot;%d &quot;, setting.scene_number) :((action == 34) ? (&quot;%d &quot;, setting.group_number) :((action == 35) ? (&quot;%d &quot;, setting.group_number) :((action == 36) ? (&quot;%d &quot;, setting.group_number) :((action == 255) ? (&quot;UNKNOWN &quot;) :(&quot;%f &quot;,  setting.value))))))))))))
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
			</refs>
		</cpt>
		<cpt id="SCPTbuttonRepeatInterval" idx="313" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<scalar>
				<nc-type>unsigned long</nc-type>
				<min>0</min>
				<max>65534</max>
				<invalid>65535</invalid>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-3687"/>
			<comment id="0-3688"/>
			<unit id="0-100"/>
			<p-name>SCPTbuttonRepeatInterval</p-name>
			<formats>
				<format id="SCPTbuttonRepeatInterval">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
			</refs>
		</cpt>
		<cpt id="SCPTbypassTime" idx="34" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_min</ref>
			<name id="0-650"/>
			<comment id="0-651"/>
			<p-name>SCPTbypassTime</p-name>
			<formats>
				<format id="SCPTbypassTime">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchilledCeilingController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsunblindController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTunitVentilatorController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTclOffDelay" idx="85" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>300,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-702"/>
			<comment id="0-703"/>
			<p-name>SCPTclOffDelay</p-name>
			<formats>
				<format id="SCPTclOffDelay">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTconstantLightController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTclOnDelay" idx="86" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-704"/>
			<comment id="0-705"/>
			<p-name>SCPTclOnDelay</p-name>
			<formats>
				<format id="SCPTclOnDelay">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTconstantLightController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTclockCalibration" idx="300" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<scalar>
				<nc-type>signed long</nc-type>
				<min>-32768</min>
				<max>32767</max>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-3385"/>
			<comment id="0-3332"/>
			<unit id="0-3333"/>
			<p-name>SCPTclockCalibration</p-name>
			<formats>
				<format id="SCPTclockCalibration">text(&quot;%d&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTcombFlowCharacteristic" idx="287" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>DCM_SPEED_CONST</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_dev_c_mode</ref>
			<name id="0-3217"/>
			<comment id="0-3218"/>
			<p-name>SCPTcombFlowCharacteristic</p-name>
			<formats>
				<format id="SCPTcombFlowCharacteristic">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTcontrolPriority" idx="171" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>200</max>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-1229"/>
			<comment id="0-1230"/>
			<unit id="0-890"/>
			<p-name>SCPTcontrolPriority</p-name>
			<formats>
				<format id="SCPTcontrolPriority">text(&quot;%d&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTcontrolSignal" idx="245" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,000 0,000 0,000 0,000</min>
			<default>0,000 0,000 0,000 0,000</default>
			<size>8</size>
			<aggregate cat="struct">
				<members>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
						<name id="0-1380"/>
						<p-name>x1Value</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
						<name id="0-1381"/>
						<p-name>y1Value</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
						<name id="0-1382"/>
						<p-name>x2Value</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
						<name id="0-1383"/>
						<p-name>y2Value</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-1377"/>
			<comment id="0-1378"/>
			<unit id="0-1379"/>
			<p-name>SCPTcontrolSignal</p-name>
			<formats>
				<format id="SCPTcontrolSignal">text(&quot;%f %f %f %f&quot;,  x1Value,  y1Value,  x2Value,  y2Value)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTcontrolTemperatureWeighting" idx="215" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,000</min>
			<default>100,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-1317"/>
			<comment id="0-1318"/>
			<p-name>SCPTcontrolTemperatureWeighting</p-name>
			<formats>
				<format id="SCPTcontrolTemperatureWeighting">text(&quot;%f&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTcoolLowerSP" idx="76" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>10,00</min>
			<max>35,00</max>
			<default>10,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-690"/>
			<comment id="0-993"/>
			<p-name>SCPTcoolLowerSP</p-name>
			<formats>
				<format id="SCPTcoolLowerSP#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTcoolLowerSP#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTthermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTcoolSetpt" idx="75" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>-40,00</min>
			<max>48,80</max>
			<default>7,20</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-689"/>
			<comment id="0-992"/>
			<p-name>SCPTcoolSetpt</p-name>
			<formats>
				<format id="SCPTcoolSetpt#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTcoolSetpt#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchiller</ref>
			</refs>
		</cpt>
		<cpt id="SCPTcoolUpperSP" idx="77" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>10,00</min>
			<max>35,00</max>
			<default>10,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-691"/>
			<comment id="0-994"/>
			<p-name>SCPTcoolUpperSP</p-name>
			<formats>
				<format id="SCPTcoolUpperSP#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTcoolUpperSP#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTthermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTcoolingLockout" idx="209" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>10,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-1305"/>
			<comment id="0-1306"/>
			<p-name>SCPTcoolingLockout</p-name>
			<formats>
				<format id="SCPTcoolingLockout#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTcoolingLockout#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTcoolingResetEnable" idx="211" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>BOOL_FALSE</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>1</max>
				<idx>41</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">boolean_t</ref>
			</enum>
			<name id="0-1309"/>
			<comment id="0-1310"/>
			<unit id="0-153"/>
			<p-name>SCPTcoolingResetEnable</p-name>
			<formats>
				<format id="SCPTcoolingResetEnable">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTcurrentSenseEnable" idx="359" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>BOOL_FALSE</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>1</max>
				<idx>41</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">boolean_t</ref>
			</enum>
			<name id="0-5181"/>
			<comment id="0-5182"/>
			<p-name>SCPTcurrentSenseEnable</p-name>
			<formats>
				<format id="SCPTcurrentSenseEnable">text(&quot;%m&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTcutOutValue" idx="125" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>10,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-776"/>
			<comment id="0-777"/>
			<p-name>SCPTcutOutValue</p-name>
			<formats>
				<format id="SCPTcutOutValue#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTcutOutValue#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdayDateIndex" idx="103" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0/0,0/0,0</default>
			<size>6</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>1</min>
							<max>31</max>
							<invalid>0</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-937"/>
						<comment id="0-955"/>
						<unit id="0-32"/>
						<p-name>day_1</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>1</min>
							<max>12</max>
							<invalid>0</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-939"/>
						<comment id="0-956"/>
						<unit id="0-30"/>
						<p-name>month_1</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>31</max>
							<invalid>0</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-941"/>
						<comment id="0-938"/>
						<unit id="0-32"/>
						<p-name>day_2</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>12</max>
							<invalid>0</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-942"/>
						<comment id="0-940"/>
						<unit id="0-30"/>
						<p-name>month_2</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned long</nc-type>
							<min>0</min>
							<max>65535</max>
							<invalid>0</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-943"/>
						<comment id="0-944"/>
						<unit id="0-933"/>
						<p-name>event_mode_index</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-934"/>
			<comment id="0-935"/>
			<unit id="0-936"/>
			<p-name>SCPTdayDateIndex</p-name>
			<formats>
				<format id="SCPTdayDateIndex">text(&quot;%d/%d,%d/%d,%d&quot;, day_1,  month_1,  day_2,  month_2,  event_mode_index)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrealTimeBasedScheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdayNightCntrl" idx="121" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_state</ref>
			<name id="0-768"/>
			<comment id="0-769"/>
			<p-name>SCPTdayNightCntrl</p-name>
			<formats>
				<format id="SCPTdayNightCntrl">
					text(&quot;%d,%d,%d,%d,%d,%d,%d,%d,%d,%d,%d,%d,%d,%d,%d,%d&quot;, bit0,  bit1,  bit2,  bit3,  bit4,  bit5,  bit6,  bit7,  bit8, bit9,  bit10,  bit11,  bit12,  bit13,  bit14,  bit15)
				</format>
				<format id="SCPTdayNightCntrl#LO">
					text(&quot;%d|%d|%d|%d|%d|%d|%d|%d|%d|%d|%d|%d|%d|%d|%d|%d&quot;, bit0,  bit1,  bit2,  bit3,  bit4,  bit5,  bit6,  bit7,  bit8, bit9,  bit10,  bit11,  bit12,  bit13,  bit14,  bit15)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdebounce" idx="139" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-804"/>
			<comment id="0-805"/>
			<p-name>SCPTdebounce</p-name>
			<formats>
				<format id="SCPTdebounce">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiOccupancySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPToccupancySensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdefInput" idx="305" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTdefInput">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdefOutput" idx="7" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTdefOutput">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTentryExit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTlampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdefScale" idx="162" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-1052"/>
			<comment id="0-1053"/>
			<p-name>SCPTdefScale</p-name>
			<formats>
				<format id="SCPTdefScale">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableSpeedMotorDrive</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdefWeekMask" idx="102" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0,0,0,0,0,0</default>
			<size>14</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned long</nc-type>
							<min>0</min>
							<max>65535</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
							<array-size>7</array-size>
						</scalar>
						<name id="0-929"/>
						<unit id="0-930"/>
						<p-name>time_event_index</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-927"/>
			<comment id="0-928"/>
			<p-name>SCPTdefWeekMask</p-name>
			<formats>
				<format id="SCPTdefWeekMask">
					text(&quot;%d,%d,%d,%d,%d,%d,%d&quot;, time_event_index[0],  time_event_index[1], time_event_index[2],  time_event_index[3], time_event_index[4],  time_event_index[5], time_event_index[6])
				</format>
				<format id="SCPTdefWeekMask#LO">
					text(&quot;%d|%d|%d|%d|%d|%d|%d&quot;, time_event_index[0],  time_event_index[1], time_event_index[2],  time_event_index[3], time_event_index[4],  time_event_index[5], time_event_index[6])
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrealTimeBasedScheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdefaultAutoPanSpeed" idx="176" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>25,2</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>250</max>
				<invalid>255</invalid>
				<scaling>
					<a>4</a>
					<b>-1</b>
					<c>0</c>
					<s>0.40000000596046</s>
				</scaling>
			</scalar>
			<name id="0-1239"/>
			<comment id="0-1240"/>
			<unit id="0-56"/>
			<p-name>SCPTdefaultAutoPanSpeed</p-name>
			<formats>
				<format id="SCPTdefaultAutoPanSpeed">text(&quot;%f&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTdefaultPanTiltZoomSpeeds" idx="175" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>PAN_STOP 100,0 TILT_STOP 100,0 ZOOM_STOP 100,0</default>
			<size>6</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_ptz</ref>
			<name id="0-1237"/>
			<comment id="0-1238"/>
			<p-name>SCPTdefaultPanTiltZoomSpeeds</p-name>
			<formats>
				<format id="SCPTdefaultPanTiltZoomSpeeds">text(&quot;%m %f %m %f %m %f&quot;,  pan_dir,  pan_speed, tilt_dir,  tilt_speed,  zoom,  zoom_speed)</format>
			</formats>
		</cpt>
		<cpt id="SCPTdefaultSetting" idx="297" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>SET_OFF 0,0 0,00</default>
			<size>4</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_setting</ref>
			<name id="0-3355"/>
			<p-name>SCPTdefaultSetting</p-name>
			<formats>
				<format id="SCPTdefaultSetting">text(&quot;%m %f %f&quot;, function,setting,rotation)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsunblindController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdefaultState" idx="295" stlp_std="yes">
			<obsolete>yes</obsolete>
			<default>SSE_OFF 0</default>
			<size>3</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_sec_state</ref>
			<name id="0-3372"/>
			<comment id="0-3373"/>
			<p-name>SCPTdefaultState</p-name>
			<formats>
				<format id="SCPTdefaultState">text(&quot;%m %d&quot;, state,identity)</format>
			</formats>
		</cpt>
		<cpt id="SCPTdefltBehave" idx="71" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0 0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_switch</ref>
			<name id="0-686"/>
			<comment id="0-988"/>
			<p-name>SCPTdefltBehave</p-name>
			<formats>
				<format id="SCPTdefltBehave">text(&quot;%f %d&quot;, value, state)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchiller</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdefrostCycles" idx="219" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>255</max>
				<invalid>255</invalid>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-1325"/>
			<comment id="0-1326"/>
			<unit id="0-20"/>
			<p-name>SCPTdefrostCycles</p-name>
			<formats>
				<format id="SCPTdefrostCycles">text(&quot;%d&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTdefrostDetect" idx="225" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,00</min>
			<max>50,00</max>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_diff_p</ref>
			<name id="0-1336"/>
			<comment id="0-1337"/>
			<p-name>SCPTdefrostDetect</p-name>
			<formats>
				<format id="SCPTdefrostDetect#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTdefrostDetect#US">text(&quot;%f&quot;, *1.8+0(0:855))</format>
			</formats>
		</cpt>
		<cpt id="SCPTdefrostFanDelay" idx="222" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_min</ref>
			<name id="0-1330"/>
			<comment id="0-1331"/>
			<p-name>SCPTdefrostFanDelay</p-name>
			<formats>
				<format id="SCPTdefrostFanDelay">text(&quot;%d&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTdefrostHold" idx="224" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>BOOL_FALSE</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>1</max>
				<idx>41</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">boolean_t</ref>
			</enum>
			<name id="0-1334"/>
			<comment id="0-1335"/>
			<unit id="0-153"/>
			<p-name>SCPTdefrostHold</p-name>
			<formats>
				<format id="SCPTdefrostHold">text(&quot;%m&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTdefrostInternalSchedule" idx="217" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>BOOL_FALSE</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>1</max>
				<idx>41</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">boolean_t</ref>
			</enum>
			<name id="0-1321"/>
			<comment id="0-1322"/>
			<p-name>SCPTdefrostInternalSchedule</p-name>
			<formats>
				<format id="SCPTdefrostInternalSchedule">text(&quot;%m&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTdefrostMode" idx="106" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>DFM_MODE_FORCED</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_defr_mode</ref>
			<name id="0-604"/>
			<comment id="0-736"/>
			<p-name>SCPTdefrostMode</p-name>
			<formats>
				<format id="SCPTdefrostMode">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerDefrost</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdefrostRecoveryTime" idx="223" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_min</ref>
			<name id="0-1332"/>
			<comment id="0-1333"/>
			<p-name>SCPTdefrostRecoveryTime</p-name>
			<formats>
				<format id="SCPTdefrostRecoveryTime">text(&quot;%d&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTdefrostStart" idx="218" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0:0</min>
			<max>23:59</max>
			<default>0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp</ref>
			<name id="0-1323"/>
			<comment id="0-1324"/>
			<p-name>SCPTdefrostStart</p-name>
			<formats>
				<format id="SCPTdefrostStart">text(&quot;%d:%d&quot;, hour, minute)</format>
				<format id="SCPTdefrostStart#LO">text(time(hour, minute))</format>
			</formats>
		</cpt>
		<cpt id="SCPTdelayTime" idx="96" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-722"/>
			<comment id="0-723"/>
			<p-name>SCPTdelayTime</p-name>
			<formats>
				<format id="SCPTdelayTime">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTentryExit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsceneController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdeltaNight" idx="134" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-794"/>
			<comment id="0-795"/>
			<p-name>SCPTdeltaNight</p-name>
			<formats>
				<format id="SCPTdeltaNight#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTdeltaNight#US">text(&quot;%f&quot;, *1.8+0(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdevListDesc" idx="322" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*31</default>
			<size>31</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_str_asc</ref>
			<name id="0-3645"/>
			<comment id="0-3646"/>
			<p-name>SCPTdevListDesc</p-name>
			<formats>
				<format id="SCPTdevListDesc">text(&quot;%s&quot;, ascii)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdeviceMonitor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdevListEntry" idx="323" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0UNKNOWN</default>
			<size>7</size>
			<aggregate cat="union">
				<members>
					<member>
						<enum>
							<min>-1</min>
							<max>2</max>
							<idx>81</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">address_type_t</ref>
						</enum>
						<p-name>address_type</p-name>
					</member>
					<member>
						<aggregate cat="struct">
							<members>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>1</min>
										<max>255</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-3653"/>
									<comment id="0-3654"/>
									<p-name>subnet</p-name>
								</member>
								<member>
									<bitfield>
										<signed>no</signed>
										<width>1</width>
										<offset>0</offset>
										<min>0</min>
										<max>1</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</bitfield>
									<name id="0-3655"/>
									<comment id="0-3656"/>
									<p-name>unused</p-name>
								</member>
								<member>
									<bitfield>
										<signed>no</signed>
										<width>7</width>
										<offset>1</offset>
										<min>1</min>
										<max>127</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</bitfield>
									<name id="0-3657"/>
									<comment id="0-3658"/>
									<p-name>node</p-name>
								</member>
							</members>
						</aggregate>
						<name id="0-3649"/>
						<comment id="0-3650"/>
						<p-name>sn</p-name>
					</member>
					<member>
						<aggregate cat="struct">
							<members>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>255</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-3661"/>
									<comment id="0-3662"/>
									<p-name>subnet</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned char</nc-type>
										<min>0</min>
										<max>255</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
										<array-size>6</array-size>
									</scalar>
									<p-name>nid</p-name>
								</member>
							</members>
						</aggregate>
						<name id="0-3659"/>
						<comment id="0-3660"/>
						<p-name>ni</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-3647"/>
			<comment id="0-3648"/>
			<p-name>SCPTdevListEntry</p-name>
			<formats>
				<format id="SCPTdevListEntry">
					text((&quot;%m&quot;, address_type),((address_type == 1) ?	(&quot;%d/%d&quot;, sn.subnet, sn.node) :((address_type == 2) ?	(&quot;%d/%x-%x-%x-%x-%x-%x&quot;, ni.subnet, ni.nid[0], ni.nid[1], ni.nid[2], ni.nid[3], ni.nid[4], ni.nid[5]) :(&quot;UNKNOWN&quot;))))
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdeviceMonitor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdevMajVer" idx="165" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>255</max>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-1032"/>
			<comment id="0-1033"/>
			<p-name>SCPTdevMajVer</p-name>
			<formats>
				<format id="SCPTdevMajVer">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTnodeObject</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdevMinVer" idx="166" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>255</max>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-1034"/>
			<comment id="0-1035"/>
			<p-name>SCPTdevMinVer</p-name>
			<formats>
				<format id="SCPTdevMinVer">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTnodeObject</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdeviceControlMode" idx="238" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>DCM_SPEED_CONST</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_dev_c_mode</ref>
			<name id="0-1196"/>
			<comment id="0-1364"/>
			<p-name>SCPTdeviceControlMode</p-name>
			<formats>
				<format id="SCPTdeviceControlMode">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdeviceGroupID" idx="172" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<scalar>
				<nc-type>unsigned long</nc-type>
				<min>0</min>
				<max>65535</max>
				<invalid>0</invalid>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-1231"/>
			<comment id="0-1232"/>
			<unit id="0-1097"/>
			<p-name>SCPTdeviceGroupID</p-name>
			<formats>
				<format id="SCPTdeviceGroupID">text(&quot;%d&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTdeviceOutSelection" idx="347" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>OLC_DEFAULT</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>4</max>
				<idx>82</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">olc_select_t</ref>
			</enum>
			<name id="0-4954"/>
			<comment id="0-4955"/>
			<p-name>SCPTdeviceOutSelection</p-name>
			<formats>
				<format id="SCPTdeviceOutSelection">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPToutdoorLuminairController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdialString" idx="178" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*31</default>
			<size>31</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_str_asc</ref>
			<name id="0-1243"/>
			<comment id="0-1244"/>
			<p-name>SCPTdialString</p-name>
			<formats>
				<format id="SCPTdialString">text(&quot;%s&quot;, ascii)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTtelephoneDirectory</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdiffNight" idx="122" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-770"/>
			<comment id="0-771"/>
			<p-name>SCPTdiffNight</p-name>
			<formats>
				<format id="SCPTdiffNight#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTdiffNight#US">text(&quot;%f&quot;, *1.8+0(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdiffTempSetpoint" idx="201" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>5,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_diff_p</ref>
			<name id="0-1289"/>
			<comment id="0-1290"/>
			<p-name>SCPTdiffTempSetpoint</p-name>
			<formats>
				<format id="SCPTdiffTempSetpoint#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTdiffTempSetpoint#US">text(&quot;%f&quot;, *1.8+0(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdiffValue" idx="130" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-786"/>
			<comment id="0-787"/>
			<p-name>SCPTdiffValue</p-name>
			<formats>
				<format id="SCPTdiffValue#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTdiffValue#US">text(&quot;%f&quot;, *1.8+0(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdirection" idx="44" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_state</ref>
			<name id="0-666"/>
			<comment id="0-976"/>
			<p-name>SCPTdirection</p-name>
			<formats>
				<format id="SCPTdirection">
					text(&quot;%d,%d,%d,%d,%d,%d,%d,%d,%d,%d,%d,%d,%d,%d,%d,%d&quot;, bit0,  bit1,  bit2,  bit3,  bit4,  bit5,  bit6,  bit7,  bit8, bit9,  bit10,  bit11,  bit12,  bit13,  bit14,  bit15)
				</format>
				<format id="SCPTdirection#LO">
					text(&quot;%d|%d|%d|%d|%d|%d|%d|%d|%d|%d|%d|%d|%d|%d|%d|%d&quot;, bit0,  bit1,  bit2,  bit3,  bit4,  bit5,  bit6,  bit7,  bit8, bit9,  bit10,  bit11,  bit12,  bit13,  bit14,  bit15)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfireSmokeDamperActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdischargeAirCoolingSetpoint" idx="183" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>13,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-1253"/>
			<comment id="0-1254"/>
			<p-name>SCPTdischargeAirCoolingSetpoint</p-name>
			<formats>
				<format id="SCPTdischargeAirCoolingSetpoint#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTdischargeAirCoolingSetpoint#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdischargeAirDewpointSetpoint" idx="204" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>10,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-1295"/>
			<comment id="0-1296"/>
			<p-name>SCPTdischargeAirDewpointSetpoint</p-name>
			<formats>
				<format id="SCPTdischargeAirDewpointSetpoint#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTdischargeAirDewpointSetpoint#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdischargeAirHeatingSetpoint" idx="184" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>10,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-1255"/>
			<comment id="0-1256"/>
			<p-name>SCPTdischargeAirHeatingSetpoint</p-name>
			<formats>
				<format id="SCPTdischargeAirHeatingSetpoint#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTdischargeAirHeatingSetpoint#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdrainDelay" idx="108" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-739"/>
			<comment id="0-740"/>
			<p-name>SCPTdrainDelay</p-name>
			<formats>
				<format id="SCPTdrainDelay">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerDefrost</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdriveT" idx="8" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>0 17:59:59:999</max>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-422"/>
			<comment id="0-423"/>
			<p-name>SCPTdriveT</p-name>
			<formats>
				<format id="SCPTdriveT">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTdriveT#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTdriveTime" idx="45" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>150,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-422"/>
			<comment id="0-977"/>
			<p-name>SCPTdriveTime</p-name>
			<formats>
				<format id="SCPTdriveTime">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfireSmokeDamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTductArea" idx="46" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>13,1070</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_area</ref>
			<name id="0-667"/>
			<comment id="0-978"/>
			<p-name>SCPTductArea</p-name>
			<formats>
				<format id="SCPTductArea">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTairVelocitySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableAirVolume</ref>
			</refs>
		</cpt>
		<cpt id="SCPTductStaticPressureLimit" idx="192" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>1500</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_press_p</ref>
			<name id="0-1271"/>
			<comment id="0-1272"/>
			<p-name>SCPTductStaticPressureLimit</p-name>
			<formats>
				<format id="SCPTductStaticPressureLimit#SI">text(&quot;%f&quot;)</format>
				<format id="SCPTductStaticPressureLimit#US">text(&quot;%f&quot;, *0.0040217+0(0:954))</format>
				<format id="SCPTductStaticPressureLimit#US_psi">text(&quot;%f&quot;, *1.4504e-4+0(0:875))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTductStaticPressureSetpoint" idx="189" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>500</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_press_p</ref>
			<name id="0-1265"/>
			<comment id="0-1266"/>
			<p-name>SCPTductStaticPressureSetpoint</p-name>
			<formats>
				<format id="SCPTductStaticPressureSetpoint#SI">text(&quot;%f&quot;)</format>
				<format id="SCPTductStaticPressureSetpoint#US">text(&quot;%f&quot;, *0.0040217+0(0:954))</format>
				<format id="SCPTductStaticPressureSetpoint#US_psi">text(&quot;%f&quot;, *1.4504e-4+0(0:875))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTeffectivePeriod" idx="272" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>-1 1 1 -1 1 1</default>
			<size>8</size>
			<aggregate cat="struct">
				<members>
					<member>
						<aggregate cat="struct">
							<members>
								<member>
									<scalar>
										<nc-type>signed long</nc-type>
										<min>-1</min>
										<max>3000</max>
										<invalid>-1</invalid>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-26"/>
									<comment id="0-2471"/>
									<p-name>year</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>1</min>
										<max>12</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-29"/>
									<comment id="0-2472"/>
									<p-name>month</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>1</min>
										<max>31</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-31"/>
									<comment id="0-2473"/>
									<p-name>day</p-name>
								</member>
							</members>
						</aggregate>
						<name id="0-2469"/>
						<comment id="0-2470"/>
						<p-name>start</p-name>
					</member>
					<member>
						<aggregate cat="struct">
							<members>
								<member>
									<scalar>
										<nc-type>signed long</nc-type>
										<min>-1</min>
										<max>3000</max>
										<invalid>-1</invalid>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-2476"/>
									<comment id="0-2477"/>
									<p-name>year</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>1</min>
										<max>12</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-2478"/>
									<comment id="0-2479"/>
									<p-name>month</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>1</min>
										<max>31</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-2480"/>
									<comment id="0-2481"/>
									<p-name>day</p-name>
								</member>
							</members>
						</aggregate>
						<name id="0-2474"/>
						<comment id="0-2475"/>
						<p-name>end</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-2467"/>
			<comment id="0-2468"/>
			<p-name>SCPTeffectivePeriod</p-name>
			<formats>
				<format id="SCPTeffectivePeriod">text(&quot;%d %d %d %d %d %d&quot;, start.year,  start.month,  start.day, end.year,  end.month,  end.day)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTcalendar</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTemergCnfg" idx="258" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTemergCnfg">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTentryExit</ref>
			</refs>
		</cpt>
		<cpt id="SCPTemergencyPosition" idx="250" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,000</min>
			<max>100,000</max>
			<default>100,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-1392"/>
			<comment id="0-1393"/>
			<p-name>SCPTemergencyPosition</p-name>
			<formats>
				<format id="SCPTemergencyPosition">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTenableStatusMsg" idx="348" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0</default>
			<size>5</size>
			<aggregate cat="struct">
				<members>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>0</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5034"/>
						<p-name>lamp_current_high</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>1</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5035"/>
						<p-name>lamp_current_low</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>2</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5036"/>
						<p-name>main_current_high</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>3</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5037"/>
						<p-name>main_current_low</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>4</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5038"/>
						<p-name>lamp_voltage_high</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>5</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5039"/>
						<p-name>lamp_voltage_low</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>6</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5040"/>
						<p-name>main_voltage_high</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>7</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5041"/>
						<p-name>main_voltage_low</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>0</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5042"/>
						<p-name>power_factor_low</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>1</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5043"/>
						<p-name>OLC_temp_high</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>2</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5044"/>
						<p-name>power_high</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>3</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5045"/>
						<p-name>power_low</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>4</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5046"/>
						<p-name>relay_failure</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>5</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5047"/>
						<p-name>cap_failure</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>6</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5048"/>
						<p-name>lamp_failure</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>7</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5049"/>
						<p-name>ballast_failure</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>0</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5050"/>
						<p-name>inter_com_failure</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>1</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5051"/>
						<p-name>exter_com_failure</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>2</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5052"/>
						<p-name>main_volt_below_spec</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>3</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5053"/>
						<p-name>lamp_restart_count</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>4</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5054"/>
						<p-name>fading_ready</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>5</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5055"/>
						<p-name>ballast_temp_high</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>6</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5056"/>
						<p-name>digi_in_A</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>7</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5057"/>
						<p-name>digi_in_B</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>0</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_25_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>1</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_26_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>2</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_27_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>3</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_28_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>4</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_29_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>5</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_30_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>6</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_31_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>7</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_32_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>0</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_33_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>1</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_34_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>2</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_35_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>3</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_36_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>4</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_37_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>5</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_38_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>6</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_39_res</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>7</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5058"/>
						<p-name>bit_40_res</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5090"/>
			<p-name>SCPTenableStatusMsg</p-name>
			<formats>
				<format id="SCPTenableStatusMsg">
					text(&quot;%d %d %d %d %d %d %d %d %d %d %d %d %d %d %d %d %d %d %d %d %d %d %d %d&quot;,  lamp_current_high,  lamp_current_low,  main_current_high,  main_current_low,  lamp_voltage_high,  lamp_voltage_low,  main_voltage_high,  main_voltage_low,  power_factor_low,  OLC_temp_high,  power_high,  power_low, relay_failure,  cap_failure,  lamp_failure,  ballast_failure,  inter_com_failure,  exter_com_failure,  main_volt_below_spec,  lamp_restart_count,  fading_ready,  ballast_temp_high,  digi_in_A,  digi_in_B)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPToutdoorLuminairController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTenergyCntInit" idx="137" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elec_kwh</ref>
			<name id="0-800"/>
			<comment id="0-801"/>
			<p-name>SCPTenergyCntInit</p-name>
			<formats>
				<format id="SCPTenergyCntInit">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTlampActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTexhaustEnablePosition" idx="202" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>25,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-1291"/>
			<comment id="0-1292"/>
			<p-name>SCPTexhaustEnablePosition</p-name>
			<formats>
				<format id="SCPTexhaustEnablePosition">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTfadeTime" idx="95" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,0</min>
			<default>1,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-720"/>
			<comment id="0-721"/>
			<p-name>SCPTfadeTime</p-name>
			<formats>
				<format id="SCPTfadeTime">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsceneController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTfanDifferentialSetpoint" idx="195" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>10,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-1277"/>
			<comment id="0-1278"/>
			<p-name>SCPTfanDifferentialSetpoint</p-name>
			<formats>
				<format id="SCPTfanDifferentialSetpoint">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTfanInEnable" idx="328" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>1</max>
				<invalid>255</invalid>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-3985"/>
			<comment id="0-3986"/>
			<p-name>SCPTfanInEnable</p-name>
			<formats>
				<format id="SCPTfanInEnable">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
			</refs>
		</cpt>
		<cpt id="SCPTfanOperation" idx="260" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>HVF_CONTINUOUS</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>4</max>
				<idx>53</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">fan_operation_t</ref>
			</enum>
			<name id="0-2222"/>
			<p-name>SCPTfanOperation</p-name>
			<formats>
				<format id="SCPTfanOperation">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTfieldCalib" idx="90" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lux</ref>
			<name id="0-710"/>
			<comment id="0-711"/>
			<p-name>SCPTfieldCalib</p-name>
			<formats>
				<format id="SCPTfieldCalib">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTlightSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTfireIndicate" idx="153" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>FN_UNDEFINED</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_fire_indcte</ref>
			<name id="0-888"/>
			<comment id="0-889"/>
			<p-name>SCPTfireIndicate</p-name>
			<formats>
				<format id="SCPTfireIndicate">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTaudibleFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvisibleFireIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTfireInitType" idx="38" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>FI_UNDEFINED</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_fire_init</ref>
			<name id="0-887"/>
			<comment id="0-658"/>
			<p-name>SCPTfireInitType</p-name>
			<formats>
				<format id="SCPTfireInitType">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireInitiator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTfireTxt1" idx="149" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>00*31</min>
			<max>FF*30-00</max>
			<default>00*31</default>
			<size>31</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_str_asc</ref>
			<name id="0-826"/>
			<comment id="0-827"/>
			<p-name>SCPTfireTxt1</p-name>
			<formats>
				<format id="SCPTfireTxt1">text(&quot;%s&quot;, ascii)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTaudibleFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpullStationFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorConvent</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvisibleFireIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTfireTxt2" idx="150" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>00*31</min>
			<max>FF*30-00</max>
			<default>00*31</default>
			<size>31</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_str_asc</ref>
			<name id="0-828"/>
			<comment id="0-829"/>
			<p-name>SCPTfireTxt2</p-name>
			<formats>
				<format id="SCPTfireTxt2">text(&quot;%s&quot;, ascii)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTaudibleFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpullStationFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorConvent</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvisibleFireIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTfireTxt3" idx="151" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>00*31</min>
			<max>FF*30-00</max>
			<default>00*31</default>
			<size>31</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_str_asc</ref>
			<name id="0-830"/>
			<comment id="0-831"/>
			<p-name>SCPTfireTxt3</p-name>
			<formats>
				<format id="SCPTfireTxt3">text(&quot;%s&quot;, ascii)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTaudibleFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpullStationFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorConvent</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvisibleFireIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTflashFreq" idx="145" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,1</min>
			<max>5,0</max>
			<default>1,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_freq_hz</ref>
			<name id="0-818"/>
			<comment id="0-819"/>
			<p-name>SCPTflashFreq</p-name>
			<formats>
				<format id="SCPTflashFreq">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTvisibleFireIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTfreeCoolPosition" idx="247" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,000</min>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-1386"/>
			<comment id="0-1387"/>
			<p-name>SCPTfreeCoolPosition</p-name>
			<formats>
				<format id="SCPTfreeCoolPosition">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTgain" idx="31" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>1/1</default>
			<size>4</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_muldiv</ref>
			<name id="0-462"/>
			<comment id="0-463"/>
			<p-name>SCPTgain</p-name>
			<formats>
				<format id="SCPTgain">text(&quot;%d/%d&quot;, multiplier, divisor)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTairVelocitySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTglobalSolarRadiation</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTgainVAV" idx="66" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>1,0000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_multiplier</ref>
			<name id="0-684"/>
			<comment id="0-987"/>
			<p-name>SCPTgainVAV</p-name>
			<formats>
				<format id="SCPTgainVAV">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableAirVolume</ref>
			</refs>
		</cpt>
		<cpt id="SCPTgainVAVHeat" idx="268" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>1,0000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_multiplier</ref>
			<name id="0-685"/>
			<comment id="0-1010"/>
			<p-name>SCPTgainVAVHeat</p-name>
			<formats>
				<format id="SCPTgainVAVHeat">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTgeoLocation" idx="350" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0000000 0,0000000 0 </default>
			<size>31</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_geo_loc</ref>
			<name id="0-5060"/>
			<p-name>SCPTgeoLocation</p-name>
			<formats>
				<format id="SCPTgeoLocation">text(&quot;%f %f %f %s&quot;,  longitude, latitude, elevation, name)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTnodeObject</ref>
			</refs>
		</cpt>
		<cpt id="SCPTheatLowerSP" idx="79" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>10,00</min>
			<max>35,00</max>
			<default>10,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-693"/>
			<comment id="0-996"/>
			<p-name>SCPTheatLowerSP</p-name>
			<formats>
				<format id="SCPTheatLowerSP#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTheatLowerSP#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTthermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTheatSetpt" idx="78" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>-40,00</min>
			<max>93,00</max>
			<default>35,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-692"/>
			<comment id="0-995"/>
			<p-name>SCPTheatSetpt</p-name>
			<formats>
				<format id="SCPTheatSetpt#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTheatSetpt#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTboilerController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchiller</ref>
			</refs>
		</cpt>
		<cpt id="SCPTheatUpperSP" idx="80" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>10,00</min>
			<max>35,00</max>
			<default>35,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-694"/>
			<comment id="0-997"/>
			<p-name>SCPTheatUpperSP</p-name>
			<formats>
				<format id="SCPTheatUpperSP#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTheatUpperSP#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTthermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTheatingLockout" idx="210" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>20,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-1307"/>
			<comment id="0-1308"/>
			<p-name>SCPTheatingLockout</p-name>
			<formats>
				<format id="SCPTheatingLockout#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTheatingLockout#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTheatingResetEnable" idx="212" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>BOOL_FALSE</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>1</max>
				<idx>41</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">boolean_t</ref>
			</enum>
			<name id="0-1311"/>
			<comment id="0-1312"/>
			<unit id="0-153"/>
			<p-name>SCPTheatingResetEnable</p-name>
			<formats>
				<format id="SCPTheatingResetEnable">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPThighLimDefrDly" idx="133" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-792"/>
			<comment id="0-793"/>
			<p-name>SCPThighLimDefrDly</p-name>
			<formats>
				<format id="SCPThighLimDefrDly">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPThighLimDly" idx="124" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-774"/>
			<comment id="0-775"/>
			<p-name>SCPThighLimDly</p-name>
			<formats>
				<format id="SCPThighLimDly">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPThighLimTemp" idx="123" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-772"/>
			<comment id="0-773"/>
			<p-name>SCPThighLimTemp</p-name>
			<formats>
				<format id="SCPThighLimTemp#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPThighLimTemp#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPThighLimit1" idx="9" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPThighLimit1">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelMonitor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTutilityDataLoggerRegister</ref>
			</refs>
		</cpt>
		<cpt id="SCPThighLimit1Enable" idx="302" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>BOOL_FALSE</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>1</max>
				<idx>41</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">boolean_t</ref>
			</enum>
			<name id="0-3383"/>
			<comment id="0-3328"/>
			<p-name>SCPThighLimit1Enable</p-name>
			<formats>
				<format id="SCPThighLimit1Enable">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelMonitor</ref>
			</refs>
		</cpt>
		<cpt id="SCPThighLimit2" idx="10" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPThighLimit2">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPThighLimit2Enable" idx="303" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>BOOL_FALSE</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>1</max>
				<idx>41</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">boolean_t</ref>
			</enum>
			<name id="0-3384"/>
			<comment id="0-3329"/>
			<p-name>SCPThighLimit2Enable</p-name>
			<formats>
				<format id="SCPThighLimit2Enable">text(&quot;%m&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTholdTime" idx="91" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>1,0</min>
			<default>30,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-712"/>
			<comment id="0-713"/>
			<p-name>SCPTholdTime</p-name>
			<formats>
				<format id="SCPTholdTime">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTentryExit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiOccupancySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPToccupancyController</ref>
			</refs>
		</cpt>
		<cpt id="SCPThumSetpt" idx="36" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-654"/>
			<comment id="0-655"/>
			<p-name>SCPThumSetpt</p-name>
			<formats>
				<format id="SCPThumSetpt">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTunitVentilatorController</ref>
			</refs>
		</cpt>
		<cpt id="SCPThvacMode" idx="74" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>HVAC_COOL</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_hvac_mode</ref>
			<name id="0-383"/>
			<comment id="0-991"/>
			<p-name>SCPThvacMode</p-name>
			<formats>
				<format id="SCPThvacMode">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchiller</ref>
			</refs>
		</cpt>
		<cpt id="SCPThvacType" idx="169" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>HVT_GENERIC</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_hvac_type</ref>
			<name id="0-1056"/>
			<comment id="0-1058"/>
			<p-name>SCPThvacType</p-name>
			<formats>
				<format id="SCPThvacType">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPThystHigh1" idx="11" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPThystHigh1">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelMonitor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPThystHigh2" idx="12" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPThystHigh2">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPThystLow1" idx="13" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPThystLow1">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPThystLow2" idx="14" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPThystLow2">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelMonitor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTidentity" idx="294" stlp_std="yes">
			<obsolete>yes</obsolete>
			<default>0</default>
			<size>2</size>
			<scalar>
				<nc-type>unsigned long</nc-type>
				<min>0</min>
				<max>65535</max>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-3370"/>
			<comment id="0-3371"/>
			<p-name>SCPTidentity</p-name>
			<formats>
				<format id="SCPTidentity">text(&quot;%d&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTifaceDesc" idx="318" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*31</default>
			<size>31</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_str_asc</ref>
			<name id="0-3639"/>
			<comment id="0-3640"/>
			<p-name>SCPTifaceDesc</p-name>
			<formats>
				<format id="SCPTifaceDesc">text(&quot;%s&quot;, ascii)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelMonitor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTinFbDly" idx="15" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>0 0:0:59:999</max>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-436"/>
			<comment id="0-437"/>
			<p-name>SCPTinFbDly</p-name>
			<formats>
				<format id="SCPTinFbDly">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTinFbDly#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiOccupancySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTlampActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTinjDelay" idx="109" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-741"/>
			<comment id="0-740"/>
			<p-name>SCPTinjDelay</p-name>
			<formats>
				<format id="SCPTinjDelay">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerDefrost</ref>
			</refs>
		</cpt>
		<cpt id="SCPTinstallDate" idx="146" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0/0/0 0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp</ref>
			<name id="0-820"/>
			<comment id="0-821"/>
			<p-name>SCPTinstallDate</p-name>
			<formats>
				<format id="SCPTinstallDate">text(&quot;%d/%d/%d %d:%d:%d&quot;,  year,  month,  day,  hour,  minute,  second)</format>
				<format id="SCPTinstallDate#LO">text(date(year, month, day), (&quot; &quot;),  time(hour,  minute,  second))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTaudibleFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfireSmokeDamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpullStationFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorConvent</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvisibleFireIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTinstalledLevel" idx="232" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<scalar>
				<nc-type>unsigned long</nc-type>
				<min>0</min>
				<max>65535</max>
				<invalid>65535</invalid>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-1349"/>
			<comment id="0-1350"/>
			<unit id="0-1351"/>
			<p-name>SCPTinstalledLevel</p-name>
			<formats>
				<format id="SCPTinstalledLevel">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorArrivalGong</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorHallLantern</ref>
			</refs>
		</cpt>
		<cpt id="SCPTinvrtOut" idx="16" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>ST_OFF</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_disc</ref>
			<name id="0-438"/>
			<comment id="0-439"/>
			<p-name>SCPTinvrtOut</p-name>
			<formats>
				<format id="SCPTinvrtOut">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireInitiator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlampPower" idx="346" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_power</ref>
			<name id="0-5033"/>
			<p-name>SCPTlampPower</p-name>
			<formats>
				<format id="SCPTlampPower">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPToutdoorLuminairController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlightingGroupEnable" idx="342" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0 0 0</default>
			<size>8</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
							<array-size>8</array-size>
						</scalar>
						<p-name>flags</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-4140"/>
			<comment id="0-4141"/>
			<p-name>SCPTlightingGroupEnable</p-name>
			<formats>
				<format id="SCPTlightingGroupEnable">text(&quot;%d %d %d %d %d %d %d %d&quot;,  flags[0], flags[1], flags[2], flags[3], flags[4], flags[5], flags[6], flags[7])</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlightingGroupMembership" idx="361" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0 0 0</default>
			<size>8</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
							<array-size>8</array-size>
						</scalar>
						<p-name>flags</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5186"/>
			<comment id="0-5187"/>
			<p-name>SCPTlightingGroupMembership</p-name>
			<formats>
				<format id="SCPTlightingGroupMembership">text(&quot;%d %d %d %d %d %d %d %d&quot;,  flags[0], flags[1], flags[2], flags[3], flags[4], flags[5], flags[6], flags[7])</format>
			</formats>
		</cpt>
		<cpt id="SCPTlimitCO2" idx="42" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_ppm</ref>
			<name id="0-664"/>
			<comment id="0-1005"/>
			<p-name>SCPTlimitCO2</p-name>
			<formats>
				<format id="SCPTlimitCO2">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTroofTopUnit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTunitVentilatorController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlimitChlrCap" idx="81" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,000</min>
			<max>160,000</max>
			<default>100,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-695"/>
			<comment id="0-998"/>
			<p-name>SCPTlimitChlrCap</p-name>
			<formats>
				<format id="SCPTlimitChlrCap">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchiller</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlinkPowerDetectEnable" idx="320" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_switch</ref>
			<name id="0-3643"/>
			<comment id="0-3644"/>
			<p-name>SCPTlinkPowerDetectEnable</p-name>
			<formats>
				<format id="SCPTlinkPowerDetectEnable">text(&quot;%d %d&quot;, value,state)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelMonitor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTloadControlOffset" idx="362" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000 0 0,000 0</default>
			<size>6</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_load_offsets</ref>
			<name id="0-5204"/>
			<comment id="0-5205"/>
			<unit id="0-5206"/>
			<p-name>SCPTloadControlOffset</p-name>
			<formats>
				<format id="SCPTloadControlOffset">text(&quot;%f %d %f %d&quot;,  standby_offset, standby_rotation, demand_response_offset, demand_response_rotation)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlocation" idx="17" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*31</default>
			<size>31</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_str_asc</ref>
			<name id="0-274"/>
			<comment id="0-440"/>
			<p-name>SCPTlocation</p-name>
			<formats>
				<format id="SCPTlocation">text(&quot;%s&quot;, ascii)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTaudibleFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTautomaticTransferSwitch</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTboilerController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchilledCeilingController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchiller</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclothesWasherDomestic</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTconstantLightController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorArrivalGong</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorDirectionLantern</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorFireSystemsPort</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorHallLantern</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorPositionIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorVoiceAnnouncer</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTentryExit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfanCoilUnit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfireSmokeDamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTgeneratorSet</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTheatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTidentifierSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiOccupancySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTlampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTlightSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTlightingPanelController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTnodeObject</ref>
				<ref href="0000000000000000-0/fps.xml">SFPToccupancyController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPToccupancySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpartitionWallController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpressureSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpullStationFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrailcarAudioController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrailcarAudioSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerDefrost</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerEvaporator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTroofTopUnit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccCommandModule</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTscenePanel</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorConvent</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsunblindActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsunblindController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTswitch</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermostat</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTunitVentilatorController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTutilityMeter</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableAirVolume</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableSpeedMotorDrive</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvisibleFireIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlogAlarmThreshold" idx="339" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>95,5</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>200</max>
				<invalid>255</invalid>
				<scaling>
					<a>5</a>
					<b>-1</b>
					<c>0</c>
					<s>0.5</s>
				</scaling>
			</scalar>
			<name id="0-4055"/>
			<comment id="0-4056"/>
			<unit id="0-4057"/>
			<p-name>SCPTlogAlarmThreshold</p-name>
			<formats>
				<format id="SCPTlogAlarmThreshold">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlogCapacity" idx="324" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>4</size>
			<scalar>
				<nc-type>unsigned quad</nc-type>
				<min>1</min>
				<max>4294967295</max>
				<invalid>0</invalid>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-3976"/>
			<comment id="0-3977"/>
			<unit id="0-176"/>
			<p-name>SCPTlogCapacity</p-name>
			<formats>
				<format id="SCPTlogCapacity">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlogFileHeader" idx="338" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 v0.0 0 0 0 0,00 0 0,00</default>
			<size>20</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned long</nc-type>
							<min>2049</min>
							<max>2049</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-4045"/>
						<comment id="0-4046"/>
						<p-name>file_type</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>1</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-4047"/>
						<p-name>major_version_number</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>0</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-4048"/>
						<p-name>minor_version_number</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned long</nc-type>
							<min>0</min>
							<max>65534</max>
							<invalid>65535</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-4049"/>
						<comment id="0-4050"/>
						<p-name>log_number</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>s32_type</nc-type>
							<min>0</min>
							<max>2147483646</max>
							<invalid>2147483647</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-4051"/>
						<comment id="0-4052"/>
						<unit id="0-43"/>
						<p-name>record_count</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp_p</ref>
						<name id="0-4053"/>
						<unit id="0-43"/>
						<p-name>start_time</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp_p</ref>
						<name id="0-4054"/>
						<unit id="0-43"/>
						<p-name>end_time</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-4043"/>
			<comment id="0-4044"/>
			<p-name>SCPTlogFileHeader</p-name>
			<formats>
				<format id="SCPTlogFileHeader">
					text(&quot;%d v%d.%d %d %d %d %f %d %f&quot;,  file_type,  major_version_number,  minor_version_number,  log_number,  record_count,  start_time.second,  start_time.hundredths,  end_time.second,  end_time.hundredths)
				</format>
			</formats>
		</cpt>
		<cpt id="SCPTlogHighLimit" idx="330" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTlogHighLimit">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlogLowLimit" idx="331" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTlogLowLimit">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlogMinDeltaTime" idx="333" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>4</size>
			<scalar>
				<nc-type>unsigned quad</nc-type>
				<min>0</min>
				<max>4294967294</max>
				<invalid>4294967295</invalid>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-3996"/>
			<comment id="0-3997"/>
			<p-name>SCPTlogMinDeltaTime</p-name>
			<formats>
				<format id="SCPTlogMinDeltaTime">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlogMinDeltaValue" idx="334" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTlogMinDeltaValue">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlogNotificationThreshold" idx="325" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>45,0</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>200</max>
				<invalid>255</invalid>
				<scaling>
					<a>5</a>
					<b>-1</b>
					<c>0</c>
					<s>0.5</s>
				</scaling>
			</scalar>
			<name id="0-3978"/>
			<comment id="0-3979"/>
			<unit id="0-3980"/>
			<p-name>SCPTlogNotificationThreshold</p-name>
			<formats>
				<format id="SCPTlogNotificationThreshold">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlogRecord" idx="337" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0 0 0,00 SINGLE_INPUT NO_FANIN 0 NO_POINT_STATUS</default>
			<size>16</size>
			<aggregate cat="struct">
				<members>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>2</width>
							<offset>0</offset>
							<min>0</min>
							<max>3</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-4012"/>
						<comment id="0-4013"/>
						<p-name>timestamp_type</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>3</width>
							<offset>2</offset>
							<min>0</min>
							<max>3</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-4014"/>
						<comment id="0-4015"/>
						<p-name>record_type</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>5</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-4016"/>
						<comment id="0-4017"/>
						<p-name>multiple_input</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>6</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-4018"/>
						<comment id="0-4019"/>
						<p-name>fan_in</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>7</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-4020"/>
						<comment id="0-4021"/>
						<p-name>point_status</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-4022"/>
						<comment id="0-4023"/>
						<unit id="0-176"/>
						<p-name>data_length</p-name>
					</member>
					<member>
						<aggregate cat="union">
							<members>
								<member>
									<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp_p</ref>
									<name id="0-4025"/>
									<comment id="0-4026"/>
									<unit id="0-43"/>
									<p-name>timestamp</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned long</nc-type>
										<min>0</min>
										<max>65534</max>
										<invalid>65535</invalid>
										<scaling>
											<a>1</a>
											<b>-2</b>
											<c>0</c>
											<s>0.0099999997764826</s>
										</scaling>
									</scalar>
									<name id="0-4027"/>
									<comment id="0-4028"/>
									<unit id="0-43"/>
									<p-name>offset_stamp</p-name>
								</member>
							</members>
						</aggregate>
						<name id="0-4024"/>
						<p-name>time</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>1</min>
							<max>255</max>
							<invalid>0</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-4029"/>
						<comment id="0-4030"/>
						<p-name>member_index</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>signed long</nc-type>
							<min>0</min>
							<max>32767</max>
							<invalid>-1</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-4031"/>
						<comment id="0-4032"/>
						<p-name>data_source_index</p-name>
					</member>
					<member>
						<aggregate cat="union">
							<members>
								<member>
									<enum>
										<min>-1</min>
										<max>5</max>
										<idx>73</idx>
										<selector>0</selector>
										<ref href="0000000000000000-0/enums.xml">log_status_t</ref>
									</enum>
									<name id="0-4035"/>
									<comment id="0-4036"/>
									<p-name>log_status</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>s32_type</nc-type>
										<min>-2147483648</min>
										<max>2147483647</max>
										<invalid>0</invalid>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-4037"/>
									<comment id="0-4038"/>
									<p-name>value</p-name>
								</member>
								<member>
									<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp_p</ref>
									<name id="0-4039"/>
									<comment id="0-4040"/>
									<unit id="0-43"/>
									<p-name>old_time</p-name>
								</member>
							</members>
						</aggregate>
						<name id="0-4033"/>
						<comment id="0-4034"/>
						<p-name>data</p-name>
					</member>
					<member>
						<enum>
							<min>-1</min>
							<max>4</max>
							<idx>77</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">point_status_t</ref>
						</enum>
						<name id="0-4041"/>
						<comment id="0-4042"/>
						<p-name>point_status_value</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-4010"/>
			<comment id="0-4011"/>
			<p-name>SCPTlogRecord</p-name>
			<formats>
				<format id="SCPTlogRecord">
					text((&quot;%d %d %d %d %d %d &quot;, timestamp_type, record_type, multiple_input, fan_in, point_status, data_length),((timestamp_type == 0) ? (&quot;%d %f &quot;, time.timestamp.second, time.timestamp.hundredths) :((timestamp_type == 1) ? (&quot;%f &quot;, time.offset_stamp) :((timestamp_type == 2) ? (&quot;NO_TIMESTAMP &quot;) : (&quot;UNKNOWN &quot;)))), ((multiple_input == 1) ? (&quot;%d &quot;, member_index) :(&quot;SINGLE_INPUT &quot;)),((fan_in == 1) ? (&quot;%d &quot;, data_source_index) :(&quot;NO_FANIN &quot;)),((record_type == 0) ? (&quot;%d &quot;, data.value) : ((record_type == 1) ? (&quot;%m &quot;, data.log_status) :((record_type == 2) ? (&quot;%d %f &quot;, data.old_time.second, data.old_time.hundredths) :(&quot;UNKNOWN &quot;)))), ((point_status == 1) ? (&quot;%m &quot;, point_status_value) :(&quot;NO_POINT_STATUS&quot;)))
				</format>
			</formats>
		</cpt>
		<cpt id="SCPTlogRequest" idx="340" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0,00</default>
			<size>8</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>1</min>
							<max>255</max>
							<invalid>0</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-4060"/>
						<comment id="0-4061"/>
						<p-name>dlap_version</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned long</nc-type>
							<min>1</min>
							<max>65535</max>
							<invalid>0</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-4062"/>
						<comment id="0-4063"/>
						<p-name>requested_log</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp_p</ref>
						<name id="0-4064"/>
						<comment id="0-4065"/>
						<p-name>last_time</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-4058"/>
			<comment id="0-4059"/>
			<p-name>SCPTlogRequest</p-name>
			<formats>
				<format id="SCPTlogRequest">text(&quot;%d %d %d %f&quot;,  dlap_version,  requested_log,  last_time.second,  last_time.hundredths)</format>
			</formats>
		</cpt>
		<cpt id="SCPTlogResponse" idx="341" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0</default>
			<size>16</size>
			<aggregate cat="struct">
				<members>
					<member>
						<aggregate cat="union">
							<members>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>255</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
										<array-size>16</array-size>
									</scalar>
									<p-name>log_record</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>255</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-4070"/>
									<comment id="0-4071"/>
									<p-name>closest_version</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned long</nc-type>
										<min>1</min>
										<max>65535</max>
										<invalid>0</invalid>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-4072"/>
									<comment id="0-4073"/>
									<p-name>number_of_logs</p-name>
								</member>
							</members>
						</aggregate>
						<p-name>response</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-4066"/>
			<comment id="0-4067"/>
			<p-name>SCPTlogResponse</p-name>
			<formats>
				<format id="SCPTlogResponse">
					text(&quot;%d %d %d %d %d %d %d %d %d %d %d %d %d %d %d %d&quot;,  response.log_record[0], response.log_record[1], response.log_record[2], response.log_record[3], response.log_record[4], response.log_record[5], response.log_record[6], response.log_record[7], response.log_record[8], response.log_record[9], response.log_record[10], response.log_record[11], response.log_record[12], response.log_record[13], response.log_record[14], response.log_record[15])
				</format>
			</formats>
		</cpt>
		<cpt id="SCPTlogSize" idx="326" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>4</size>
			<scalar>
				<nc-type>unsigned quad</nc-type>
				<min>0</min>
				<max>4294967294</max>
				<invalid>4294967295</invalid>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-3981"/>
			<comment id="0-3982"/>
			<unit id="0-176"/>
			<p-name>SCPTlogSize</p-name>
			<formats>
				<format id="SCPTlogSize">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlogTimestampEnable" idx="329" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>1</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>1</max>
				<invalid>255</invalid>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-3987"/>
			<comment id="0-3988"/>
			<p-name>SCPTlogTimestampEnable</p-name>
			<formats>
				<format id="SCPTlogTimestampEnable">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlogType" idx="327" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>LT_CIRCULAR</min>
			<max>3</max>
			<default>LT_CIRCULAR</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>2</max>
				<idx>74</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">log_type_t</ref>
			</enum>
			<name id="0-3983"/>
			<comment id="0-3984"/>
			<p-name>SCPTlogType</p-name>
			<formats>
				<format id="SCPTlogType">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlowLimDly" idx="129" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-784"/>
			<comment id="0-785"/>
			<p-name>SCPTlowLimDly</p-name>
			<formats>
				<format id="SCPTlowLimDly">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlowLimTemp" idx="128" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-782"/>
			<comment id="0-783"/>
			<p-name>SCPTlowLimTemp</p-name>
			<formats>
				<format id="SCPTlowLimTemp#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTlowLimTemp#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlowLimit1" idx="18" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTlowLimit1">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelMonitor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlowLimit1Enable" idx="298" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>BOOL_FALSE</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>1</max>
				<idx>41</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">boolean_t</ref>
			</enum>
			<name id="0-3381"/>
			<comment id="0-3330"/>
			<p-name>SCPTlowLimit1Enable</p-name>
			<formats>
				<format id="SCPTlowLimit1Enable">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelMonitor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlowLimit2" idx="19" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTlowLimit2">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTlowLimit2Enable" idx="299" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>BOOL_FALSE</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>1</max>
				<idx>41</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">boolean_t</ref>
			</enum>
			<name id="0-3382"/>
			<comment id="0-3331"/>
			<p-name>SCPTlowLimit2Enable</p-name>
			<formats>
				<format id="SCPTlowLimit2Enable">text(&quot;%m&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTluxSetpoint" idx="82" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lux</ref>
			<name id="0-696"/>
			<comment id="0-697"/>
			<p-name>SCPTluxSetpoint</p-name>
			<formats>
				<format id="SCPTluxSetpoint">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTconstantLightController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaintDate" idx="147" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0/0/0 0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp</ref>
			<name id="0-822"/>
			<comment id="0-823"/>
			<p-name>SCPTmaintDate</p-name>
			<formats>
				<format id="SCPTmaintDate">text(&quot;%d/%d/%d %d:%d:%d&quot;,  year,  month,  day,  hour,  minute,  second)</format>
				<format id="SCPTmaintDate#LO">text(date(year, month, day), (&quot; &quot;),  time(hour,  minute,  second))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTaudibleFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfireSmokeDamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpullStationFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorConvent</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvisibleFireIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmanOvrTime" idx="35" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_min</ref>
			<name id="0-652"/>
			<comment id="0-653"/>
			<p-name>SCPTmanOvrTime</p-name>
			<formats>
				<format id="SCPTmanOvrTime">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchilledCeilingController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTunitVentilatorController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmanfDate" idx="148" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0/0/0 0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp</ref>
			<name id="0-824"/>
			<comment id="0-825"/>
			<p-name>SCPTmanfDate</p-name>
			<formats>
				<format id="SCPTmanfDate">text(&quot;%d/%d/%d %d:%d:%d&quot;,  year,  month,  day,  hour,  minute,  second)</format>
				<format id="SCPTmanfDate#LO">text(date(year, month, day), (&quot; &quot;),  time(hour,  minute,  second))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTaudibleFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfireSmokeDamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpullStationFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorConvent</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvisibleFireIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmanualAllowed" idx="101" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>1</max>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-732"/>
			<comment id="0-733"/>
			<unit id="0-153"/>
			<p-name>SCPTmanualAllowed</p-name>
			<formats>
				<format id="SCPTmanualAllowed">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTlightingPanelController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrealTimeKeeper</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmasterSlave" idx="97" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>1</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>1</max>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-724"/>
			<comment id="0-725"/>
			<unit id="0-153"/>
			<p-name>SCPTmasterSlave</p-name>
			<formats>
				<format id="SCPTmasterSlave">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrealTimeKeeper</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxCameraPrepositions" idx="174" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>255</max>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-1235"/>
			<comment id="0-1236"/>
			<unit id="0-20"/>
			<p-name>SCPTmaxCameraPrepositions</p-name>
			<formats>
				<format id="SCPTmaxCameraPrepositions">text(&quot;%d&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTmaxDefrostTime" idx="221" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_min</ref>
			<name id="0-737"/>
			<comment id="0-1329"/>
			<p-name>SCPTmaxDefrostTime</p-name>
			<formats>
				<format id="SCPTmaxDefrostTime">text(&quot;%d&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTmaxDefrstTemp" idx="110" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>-100,00</min>
			<max>150,00</max>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-742"/>
			<comment id="0-743"/>
			<p-name>SCPTmaxDefrstTemp</p-name>
			<formats>
				<format id="SCPTmaxDefrstTemp#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTmaxDefrstTemp#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerDefrost</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxDefrstTime" idx="107" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>3600,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-737"/>
			<comment id="0-738"/>
			<p-name>SCPTmaxDefrstTime</p-name>
			<formats>
				<format id="SCPTmaxDefrstTime">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerDefrost</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxDischargeAirCoolingSetpoint" idx="205" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>20,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-1297"/>
			<comment id="0-1298"/>
			<p-name>SCPTmaxDischargeAirCoolingSetpoint</p-name>
			<formats>
				<format id="SCPTmaxDischargeAirCoolingSetpoint#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTmaxDischargeAirCoolingSetpoint#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxDischargeAirHeatingSetpoint" idx="207" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>50,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-1301"/>
			<comment id="0-1302"/>
			<p-name>SCPTmaxDischargeAirHeatingSetpoint</p-name>
			<formats>
				<format id="SCPTmaxDischargeAirHeatingSetpoint#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTmaxDischargeAirHeatingSetpoint#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxDuctStaticPressureSetpoint" idx="190" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>1000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_press_p</ref>
			<name id="0-1267"/>
			<comment id="0-1268"/>
			<p-name>SCPTmaxDuctStaticPressureSetpoint</p-name>
			<formats>
				<format id="SCPTmaxDuctStaticPressureSetpoint#SI">text(&quot;%f&quot;)</format>
				<format id="SCPTmaxDuctStaticPressureSetpoint#US">text(&quot;%f&quot;, *0.0040217+0(0:954))</format>
				<format id="SCPTmaxDuctStaticPressureSetpoint#US_psi">text(&quot;%f&quot;, *1.4504e-4+0(0:875))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxFanIn" idx="332" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<scalar>
				<nc-type>unsigned long</nc-type>
				<min>0</min>
				<max>65534</max>
				<invalid>65535</invalid>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-3993"/>
			<comment id="0-3994"/>
			<unit id="0-3995"/>
			<p-name>SCPTmaxFanIn</p-name>
			<formats>
				<format id="SCPTmaxFanIn">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxFlow" idx="51" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>65535</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow</ref>
			<name id="0-671"/>
			<comment id="0-979"/>
			<p-name>SCPTmaxFlow</p-name>
			<formats>
				<format id="SCPTmaxFlow#SI">text(&quot;%d&quot;)</format>
				<format id="SCPTmaxFlow#US">text(&quot;%d&quot;, *0.26418+0(0:837))</format>
				<format id="SCPTmaxFlow#US_cfm">text(&quot;%d&quot;, *2.1189+0(0:966))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableAirVolume</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxFlowHeat" idx="37" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>65535</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow</ref>
			<name id="0-656"/>
			<comment id="0-657"/>
			<p-name>SCPTmaxFlowHeat</p-name>
			<formats>
				<format id="SCPTmaxFlowHeat#SI">text(&quot;%d&quot;)</format>
				<format id="SCPTmaxFlowHeat#US">text(&quot;%d&quot;, *0.26418+0(0:837))</format>
				<format id="SCPTmaxFlowHeat#US_cfm">text(&quot;%d&quot;, *2.1189+0(0:966))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxFlowSetpoint" idx="237" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>10,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow_p</ref>
			<name id="0-671"/>
			<comment id="0-1363"/>
			<p-name>SCPTmaxFlowSetpoint</p-name>
			<formats>
				<format id="SCPTmaxFlowSetpoint#SI">text(&quot;%f&quot;, *1+0(0:1408))</format>
				<format id="SCPTmaxFlowSetpoint#US">text(&quot;%f&quot;, *0.588578+0(0:1405))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxFlowUnit" idx="262" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow</ref>
			<name id="0-2225"/>
			<comment id="0-2226"/>
			<p-name>SCPTmaxFlowUnit</p-name>
			<formats>
				<format id="SCPTmaxFlowUnit#SI">text(&quot;%d&quot;)</format>
				<format id="SCPTmaxFlowUnit#US">text(&quot;%d&quot;, *0.26418+0(0:837))</format>
				<format id="SCPTmaxFlowUnit#US_cfm">text(&quot;%d&quot;, *2.1189+0(0:966))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxLevelVolt" idx="349" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_volt</ref>
			<name id="0-5059"/>
			<p-name>SCPTmaxLevelVolt</p-name>
			<formats>
				<format id="SCPTmaxLevelVolt">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPToutdoorLuminairController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxNVLength" idx="255" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>1</min>
				<max>31</max>
				<invalid>0</invalid>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-2102"/>
			<comment id="0-2103"/>
			<unit id="0-176"/>
			<p-name>SCPTmaxNVLength</p-name>
			<formats>
				<format id="SCPTmaxNVLength">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxOut" idx="93" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>100,0</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_cont</ref>
			<name id="0-716"/>
			<comment id="0-717"/>
			<p-name>SCPTmaxOut</p-name>
			<formats>
				<format id="SCPTmaxOut">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTswitch</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxPower" idx="317" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_power</ref>
			<name id="0-3669"/>
			<comment id="0-3670"/>
			<p-name>SCPTmaxPower</p-name>
			<formats>
				<format id="SCPTmaxPower">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxPressureSetpoint" idx="235" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_press</ref>
			<name id="0-1356"/>
			<comment id="0-1361"/>
			<p-name>SCPTmaxPressureSetpoint</p-name>
			<formats>
				<format id="SCPTmaxPressureSetpoint#SI">text(&quot;%f&quot;)</format>
				<format id="SCPTmaxPressureSetpoint#US">text(&quot;%f&quot;, *0.2953+0(0:1402))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxPrivacyZones" idx="173" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>1</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>255</max>
				<invalid>0</invalid>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-1233"/>
			<comment id="0-1234"/>
			<unit id="0-20"/>
			<p-name>SCPTmaxPrivacyZones</p-name>
			<formats>
				<format id="SCPTmaxPrivacyZones">text(&quot;%d&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTmaxRcvT" idx="21" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>0 17:59:59:999</max>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-446"/>
			<comment id="0-447"/>
			<p-name>SCPTmaxRcvT</p-name>
			<formats>
				<format id="SCPTmaxRcvT">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTmaxRcvT#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxRcvTime" idx="48" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-446"/>
			<comment id="0-669"/>
			<p-name>SCPTmaxRcvTime</p-name>
			<formats>
				<format id="SCPTmaxRcvTime">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTaudibleFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTboilerController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchilledCeilingController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchiller</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorArrivalGong</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorDirectionLantern</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorFireSystemsPort</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorHallLantern</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorPositionIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTentryExit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfanCoilUnit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfireSmokeDamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTheatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTroofTopUnit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccCommandModule</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsunblindController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermostat</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTunitVentilatorController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableAirVolume</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableSpeedMotorDrive</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvisibleFireIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxRemoteFlowSetpoint" idx="242" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow_p</ref>
			<name id="0-1371"/>
			<comment id="0-1372"/>
			<p-name>SCPTmaxRemoteFlowSetpoint</p-name>
			<formats>
				<format id="SCPTmaxRemoteFlowSetpoint#SI">text(&quot;%f&quot;, *1+0(0:1408))</format>
				<format id="SCPTmaxRemoteFlowSetpoint#US">text(&quot;%f&quot;, *0.588578+0(0:1405))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxRemotePressureSetpoint" idx="240" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_press</ref>
			<name id="0-1367"/>
			<comment id="0-1368"/>
			<p-name>SCPTmaxRemotePressureSetpoint</p-name>
			<formats>
				<format id="SCPTmaxRemotePressureSetpoint#SI">text(&quot;%f&quot;)</format>
				<format id="SCPTmaxRemotePressureSetpoint#US">text(&quot;%f&quot;, *0.2953+0(0:1402))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxRemoteTempSetpoint" idx="244" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-1375"/>
			<comment id="0-1376"/>
			<p-name>SCPTmaxRemoteTempSetpoint</p-name>
			<formats>
				<format id="SCPTmaxRemoteTempSetpoint#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTmaxRemoteTempSetpoint#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxReturnExhaustFanCapacity" idx="187" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>100,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-1261"/>
			<comment id="0-1262"/>
			<p-name>SCPTmaxReturnExhaustFanCapacity</p-name>
			<formats>
				<format id="SCPTmaxReturnExhaustFanCapacity">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxRnge" idx="20" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTmaxRnge">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxSendTime" idx="49" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-448"/>
			<comment id="0-449"/>
			<p-name>SCPTmaxSendTime</p-name>
			<formats>
				<format id="SCPTmaxSendTime">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTairVelocitySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTaudibleFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTautomaticTransferSwitch</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTboilerController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelContinuityMonitor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchilledCeilingController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchiller</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclothesWasherDomestic</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTco2Sensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTconstantLightController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdeviceMonitor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorFireSystemsPort</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTentryExit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfanCoilUnit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfireSmokeDamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfrostSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTgeneratorSet</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTglobalSolarRadiation</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTheatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacRelativeHumiditySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacTempSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTidentifierSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiOccupancySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTlightSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPToccupancySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPToutdoorLuminairController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpressureSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpullStationFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrailcarAudioController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrainSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerDefrost</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerEvaporator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTroofTopUnit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccCommandModule</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorConvent</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsunblindActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsunblindController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTswitch</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermostat</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTunitVentilatorController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableAirVolume</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableSpeedMotorDrive</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvisibleFireIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxSetpoint" idx="50" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-670"/>
			<comment id="0-1008"/>
			<p-name>SCPTmaxSetpoint</p-name>
			<formats>
				<format id="SCPTmaxSetpoint">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableSpeedMotorDrive</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxSndT" idx="22" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>0 17:59:59:999</max>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-448"/>
			<comment id="0-449"/>
			<p-name>SCPTmaxSndT</p-name>
			<formats>
				<format id="SCPTmaxSndT">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTmaxSndT#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTnodeObject</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxStroke" idx="253" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_length_mil</ref>
			<name id="0-1398"/>
			<comment id="0-1399"/>
			<p-name>SCPTmaxStroke</p-name>
			<formats>
				<format id="SCPTmaxStroke#SI">text(&quot;%f&quot;)</format>
				<format id="SCPTmaxStroke#US">text(&quot;%f&quot;, *0.03937+0(0:844))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmaxSupplyFanCapacity" idx="185" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>100,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-1257"/>
			<comment id="0-1258"/>
			<p-name>SCPTmaxSupplyFanCapacity</p-name>
			<formats>
				<format id="SCPTmaxSupplyFanCapacity">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmeasurementInterval" idx="360" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-5183"/>
			<comment id="0-5184"/>
			<unit id="0-5185"/>
			<p-name>SCPTmeasurementInterval</p-name>
			<formats>
				<format id="SCPTmeasurementInterval">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminDefrostTime" idx="220" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_min</ref>
			<name id="0-1327"/>
			<comment id="0-1328"/>
			<p-name>SCPTminDefrostTime</p-name>
			<formats>
				<format id="SCPTminDefrostTime">text(&quot;%d&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTminDeltaAngl" idx="43" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,00</min>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_angle_deg</ref>
			<name id="0-665"/>
			<comment id="0-1006"/>
			<p-name>SCPTminDeltaAngl</p-name>
			<formats>
				<format id="SCPTminDeltaAngl">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminDeltaCO2" idx="63" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>10</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_ppm</ref>
			<name id="0-549"/>
			<comment id="0-550"/>
			<p-name>SCPTminDeltaCO2</p-name>
			<formats>
				<format id="SCPTminDeltaCO2">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTco2Sensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccCommandModule</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminDeltaFlow" idx="47" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow</ref>
			<name id="0-668"/>
			<comment id="0-1007"/>
			<p-name>SCPTminDeltaFlow</p-name>
			<formats>
				<format id="SCPTminDeltaFlow#SI">text(&quot;%d&quot;)</format>
				<format id="SCPTminDeltaFlow#US">text(&quot;%d&quot;, *0.26418+0(0:837))</format>
				<format id="SCPTminDeltaFlow#US_cfm">text(&quot;%d&quot;, *2.1189+0(0:966))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminDeltaLevel" idx="88" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_cont</ref>
			<name id="0-455"/>
			<comment id="0-546"/>
			<p-name>SCPTminDeltaLevel</p-name>
			<formats>
				<format id="SCPTminDeltaLevel">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTconstantLightController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTlightSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminDeltaRH" idx="62" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,000</min>
			<default>1,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-547"/>
			<comment id="0-548"/>
			<p-name>SCPTminDeltaRH</p-name>
			<formats>
				<format id="SCPTminDeltaRH">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacRelativeHumiditySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccCommandModule</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminDeltaTemp" idx="64" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,00</min>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-551"/>
			<comment id="0-552"/>
			<p-name>SCPTminDeltaTemp</p-name>
			<formats>
				<format id="SCPTminDeltaTemp#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTminDeltaTemp#US">text(&quot;%f&quot;, *1.8+0(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacTempSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccCommandModule</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminDischargeAirCoolingSetpoint" idx="206" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>10,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-1299"/>
			<comment id="0-1300"/>
			<p-name>SCPTminDischargeAirCoolingSetpoint</p-name>
			<formats>
				<format id="SCPTminDischargeAirCoolingSetpoint#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTminDischargeAirCoolingSetpoint#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminDischargeAirHeatingSetpoint" idx="208" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>30,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-1303"/>
			<comment id="0-1304"/>
			<p-name>SCPTminDischargeAirHeatingSetpoint</p-name>
			<formats>
				<format id="SCPTminDischargeAirHeatingSetpoint#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTminDischargeAirHeatingSetpoint#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminDuctStaticPressureSetpoint" idx="191" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>100</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_press_p</ref>
			<name id="0-1269"/>
			<comment id="0-1270"/>
			<p-name>SCPTminDuctStaticPressureSetpoint</p-name>
			<formats>
				<format id="SCPTminDuctStaticPressureSetpoint#SI">text(&quot;%f&quot;)</format>
				<format id="SCPTminDuctStaticPressureSetpoint#US">text(&quot;%f&quot;, *0.0040217+0(0:954))</format>
				<format id="SCPTminDuctStaticPressureSetpoint#US_psi">text(&quot;%f&quot;, *1.4504e-4+0(0:875))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminFlow" idx="54" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow</ref>
			<name id="0-673"/>
			<comment id="0-981"/>
			<p-name>SCPTminFlow</p-name>
			<formats>
				<format id="SCPTminFlow#SI">text(&quot;%d&quot;)</format>
				<format id="SCPTminFlow#US">text(&quot;%d&quot;, *0.26418+0(0:837))</format>
				<format id="SCPTminFlow#US_cfm">text(&quot;%d&quot;, *2.1189+0(0:966))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableAirVolume</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminFlowHeat" idx="55" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow</ref>
			<name id="0-674"/>
			<comment id="0-982"/>
			<p-name>SCPTminFlowHeat</p-name>
			<formats>
				<format id="SCPTminFlowHeat#SI">text(&quot;%d&quot;)</format>
				<format id="SCPTminFlowHeat#US">text(&quot;%d&quot;, *0.26418+0(0:837))</format>
				<format id="SCPTminFlowHeat#US_cfm">text(&quot;%d&quot;, *2.1189+0(0:966))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableAirVolume</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminFlowHeatStby" idx="263" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow</ref>
			<name id="0-2227"/>
			<comment id="0-2228"/>
			<p-name>SCPTminFlowHeatStby</p-name>
			<formats>
				<format id="SCPTminFlowHeatStby#SI">text(&quot;%d&quot;)</format>
				<format id="SCPTminFlowHeatStby#US">text(&quot;%d&quot;, *0.26418+0(0:837))</format>
				<format id="SCPTminFlowHeatStby#US_cfm">text(&quot;%d&quot;, *2.1189+0(0:966))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminFlowSetpoint" idx="236" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow_p</ref>
			<name id="0-673"/>
			<comment id="0-1362"/>
			<p-name>SCPTminFlowSetpoint</p-name>
			<formats>
				<format id="SCPTminFlowSetpoint#SI">text(&quot;%f&quot;, *1+0(0:1408))</format>
				<format id="SCPTminFlowSetpoint#US">text(&quot;%f&quot;, *0.588578+0(0:1405))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminFlowStby" idx="56" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow</ref>
			<name id="0-675"/>
			<comment id="0-983"/>
			<p-name>SCPTminFlowStby</p-name>
			<formats>
				<format id="SCPTminFlowStby#SI">text(&quot;%d&quot;)</format>
				<format id="SCPTminFlowStby#US">text(&quot;%d&quot;, *0.26418+0(0:837))</format>
				<format id="SCPTminFlowStby#US_cfm">text(&quot;%d&quot;, *2.1189+0(0:966))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableAirVolume</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminFlowUnit" idx="261" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow</ref>
			<name id="0-2223"/>
			<comment id="0-2224"/>
			<p-name>SCPTminFlowUnit</p-name>
			<formats>
				<format id="SCPTminFlowUnit#SI">text(&quot;%d&quot;)</format>
				<format id="SCPTminFlowUnit#US">text(&quot;%d&quot;, *0.26418+0(0:837))</format>
				<format id="SCPTminFlowUnit#US_cfm">text(&quot;%d&quot;, *2.1189+0(0:966))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminFlowUnitHeat" idx="270" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow</ref>
			<name id="0-2239"/>
			<comment id="0-2240"/>
			<p-name>SCPTminFlowUnitHeat</p-name>
			<formats>
				<format id="SCPTminFlowUnitHeat#SI">text(&quot;%d&quot;)</format>
				<format id="SCPTminFlowUnitHeat#US">text(&quot;%d&quot;, *0.26418+0(0:837))</format>
				<format id="SCPTminFlowUnitHeat#US_cfm">text(&quot;%d&quot;, *2.1189+0(0:966))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminFlowUnitStby" idx="264" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow</ref>
			<name id="0-2229"/>
			<comment id="0-2230"/>
			<p-name>SCPTminFlowUnitStby</p-name>
			<formats>
				<format id="SCPTminFlowUnitStby#SI">text(&quot;%d&quot;)</format>
				<format id="SCPTminFlowUnitStby#US">text(&quot;%d&quot;, *0.26418+0(0:837))</format>
				<format id="SCPTminFlowUnitStby#US_cfm">text(&quot;%d&quot;, *2.1189+0(0:966))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminOutdoorAirFlowSetpoint" idx="198" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow</ref>
			<name id="0-1283"/>
			<comment id="0-1284"/>
			<p-name>SCPTminOutdoorAirFlowSetpoint</p-name>
			<formats>
				<format id="SCPTminOutdoorAirFlowSetpoint#SI">text(&quot;%d&quot;)</format>
				<format id="SCPTminOutdoorAirFlowSetpoint#US">text(&quot;%d&quot;, *2.1189+0(0:966))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminPressureSetpoint" idx="234" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_press</ref>
			<name id="0-1359"/>
			<comment id="0-1360"/>
			<p-name>SCPTminPressureSetpoint</p-name>
			<formats>
				<format id="SCPTminPressureSetpoint#SI">text(&quot;%f&quot;)</format>
				<format id="SCPTminPressureSetpoint#US">text(&quot;%f&quot;, *0.2953+0(0:1402))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminRemoteFlowSetpoint" idx="241" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow_p</ref>
			<name id="0-1369"/>
			<comment id="0-1370"/>
			<p-name>SCPTminRemoteFlowSetpoint</p-name>
			<formats>
				<format id="SCPTminRemoteFlowSetpoint#SI">text(&quot;%f&quot;, *1+0(0:1408))</format>
				<format id="SCPTminRemoteFlowSetpoint#US">text(&quot;%f&quot;, *0.588578+0(0:1405))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminRemotePressureSetpoint" idx="239" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_press</ref>
			<name id="0-1365"/>
			<comment id="0-1366"/>
			<p-name>SCPTminRemotePressureSetpoint</p-name>
			<formats>
				<format id="SCPTminRemotePressureSetpoint#SI">text(&quot;%f&quot;)</format>
				<format id="SCPTminRemotePressureSetpoint#US">text(&quot;%f&quot;, *0.2953+0(0:1402))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminRemoteTempSetpoint" idx="243" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-1373"/>
			<comment id="0-1374"/>
			<p-name>SCPTminRemoteTempSetpoint</p-name>
			<formats>
				<format id="SCPTminRemoteTempSetpoint#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTminRemoteTempSetpoint#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminReturnExhaustFanCapacity" idx="188" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-1263"/>
			<comment id="0-1264"/>
			<p-name>SCPTminReturnExhaustFanCapacity</p-name>
			<formats>
				<format id="SCPTminReturnExhaustFanCapacity">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminRnge" idx="23" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTminRnge">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTunitVentilatorController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminSendTime" idx="52" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-451"/>
			<comment id="0-452"/>
			<p-name>SCPTminSendTime</p-name>
			<formats>
				<format id="SCPTminSendTime">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTairVelocitySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTboilerController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTcalendar</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelContinuityMonitor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchilledCeilingController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchiller</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTco2Sensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTconstantLightController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTentryExit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfanCoilUnit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfrostSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTglobalSolarRadiation</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacRelativeHumiditySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacTempSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTlightSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPToutdoorLuminairController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpressureSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrailcarAudioController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrainSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerDefrost</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccCommandModule</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsceneController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTscenePanel</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTswitch</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTunitVentilatorController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableAirVolume</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableSpeedMotorDrive</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminSetpoint" idx="53" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-672"/>
			<comment id="0-980"/>
			<p-name>SCPTminSetpoint</p-name>
			<formats>
				<format id="SCPTminSetpoint">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
				<ref href="0000000000000000-0/fps.xml">SFPToutdoorLuminairController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableSpeedMotorDrive</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminSndT" idx="24" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>0 17:59:59:999</max>
			<default>0 0:0:15:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-451"/>
			<comment id="0-452"/>
			<p-name>SCPTminSndT</p-name>
			<formats>
				<format id="SCPTminSndT">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTminSndT#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminStroke" idx="252" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_length_mil</ref>
			<name id="0-1396"/>
			<comment id="0-1397"/>
			<p-name>SCPTminStroke</p-name>
			<formats>
				<format id="SCPTminStroke#SI">text(&quot;%f&quot;)</format>
				<format id="SCPTminStroke#US">text(&quot;%f&quot;, *0.03937+0(0:844))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTminSupplyFanCapacity" idx="186" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-1259"/>
			<comment id="0-1260"/>
			<p-name>SCPTminSupplyFanCapacity</p-name>
			<formats>
				<format id="SCPTminSupplyFanCapacity">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmixedAirLowLimitSetpoint" idx="196" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>7,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-1279"/>
			<comment id="0-1280"/>
			<p-name>SCPTmixedAirLowLimitSetpoint</p-name>
			<formats>
				<format id="SCPTmixedAirLowLimitSetpoint#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTmixedAirLowLimitSetpoint#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmixedAirTempSetpoint" idx="197" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>11,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-1281"/>
			<comment id="0-1282"/>
			<p-name>SCPTmixedAirTempSetpoint</p-name>
			<formats>
				<format id="SCPTmixedAirTempSetpoint#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTmixedAirTempSetpoint#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmodeHrtBt" idx="105" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-734"/>
			<comment id="0-735"/>
			<p-name>SCPTmodeHrtBt</p-name>
			<formats>
				<format id="SCPTmodeHrtBt">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrealTimeBasedScheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTmonInterval" idx="319" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0 0:0:1:0</min>
			<max>0 17:59:59:999</max>
			<default>0 0:0:5:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-3641"/>
			<comment id="0-3642"/>
			<p-name>SCPTmonInterval</p-name>
			<formats>
				<format id="SCPTmonInterval">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTmonInterval#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelMonitor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTname1" idx="306" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>CE_UTF_8 </default>
			<size>13</size>
			<aggregate cat="struct">
				<members>
					<member>
						<enum>
							<min>-1</min>
							<max>2</max>
							<idx>69</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">char_encoding_t</ref>
						</enum>
						<name id="0-3673"/>
						<comment id="0-3674"/>
						<p-name>encoding</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned char</nc-type>
							<min>0</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
							<array-size>12</array-size>
						</scalar>
						<p-name>name</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-3486"/>
			<comment id="0-3511"/>
			<p-name>SCPTname1</p-name>
			<formats>
				<format id="SCPTname1">
					text((&quot;%m &quot;, encoding),((encoding == 0) ? (&quot;%s&quot;, name) :(&quot;%x %x %x %x %x %x %x %x %x %x %x %x&quot;,  name[0],  name[1],  name[2],  name[3],  name[4],  name[5],  name[6],  name[7],  name[8],  name[9],  name[10],  name[11])))
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiOccupancySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTname2" idx="309" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*12</default>
			<size>12</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned char</nc-type>
							<min>0</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
							<array-size>12</array-size>
						</scalar>
						<p-name>name</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-3499"/>
			<comment id="0-3500"/>
			<p-name>SCPTname2</p-name>
			<formats>
				<format id="SCPTname2">text(&quot;%c %c %c %c %c %c %c %c %c %c %c %c&quot;,  name[0], name[1], name[2], name[3], name[4], name[5], name[6], name[7], name[8], name[9], name[10], name[11])</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiOccupancySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTname3" idx="310" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*12</default>
			<size>12</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned char</nc-type>
							<min>0</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
							<array-size>12</array-size>
						</scalar>
						<p-name>name</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-3706"/>
			<comment id="0-3707"/>
			<p-name>SCPTname3</p-name>
			<formats>
				<format id="SCPTname3">text(&quot;%c %c %c %c %c %c %c %c %c %c %c %c&quot;,  name[0], name[1], name[2], name[3], name[4], name[5], name[6], name[7], name[8], name[9], name[10], name[11])</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiOccupancySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTneuronId" idx="301" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0-0-0-0-0-0</default>
			<size>6</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned char</nc-type>
							<min>0</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
							<array-size>6</array-size>
						</scalar>
						<p-name>id</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-3386"/>
			<comment id="0-3334"/>
			<p-name>SCPTneuronId</p-name>
			<formats>
				<format id="SCPTneuronId">text(&quot;%x-%x-%x-%x-%x-%x&quot;,  id[0], id[1], id[2], id[3], id[4], id[5])</format>
			</formats>
		</cpt>
		<cpt id="SCPTnightPurgePosition" idx="246" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,000</min>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-1384"/>
			<comment id="0-1385"/>
			<p-name>SCPTnightPurgePosition</p-name>
			<formats>
				<format id="SCPTnightPurgePosition">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTnomAirFlow" idx="57" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow</ref>
			<name id="0-676"/>
			<comment id="0-984"/>
			<p-name>SCPTnomAirFlow</p-name>
			<formats>
				<format id="SCPTnomAirFlow#SI">text(&quot;%d&quot;)</format>
				<format id="SCPTnomAirFlow#US">text(&quot;%d&quot;, *2.1189+0(0:966))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableAirVolume</ref>
			</refs>
		</cpt>
		<cpt id="SCPTnomAirFlowHeat" idx="267" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow</ref>
			<name id="0-2235"/>
			<comment id="0-2236"/>
			<p-name>SCPTnomAirFlowHeat</p-name>
			<formats>
				<format id="SCPTnomAirFlowHeat#SI">text(&quot;%d&quot;)</format>
				<format id="SCPTnomAirFlowHeat#US">text(&quot;%d&quot;, *2.1189+0(0:966))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTnomAngle" idx="58" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,00</min>
			<max>95,00</max>
			<default>90,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_angle_deg</ref>
			<name id="0-677"/>
			<comment id="0-985"/>
			<p-name>SCPTnomAngle</p-name>
			<formats>
				<format id="SCPTnomAngle">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTnomFreq" idx="159" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0,0</min>
			<max>100,0</max>
			<default>60,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_freq_hz</ref>
			<name id="0-1046"/>
			<comment id="0-1047"/>
			<p-name>SCPTnomFreq</p-name>
			<formats>
				<format id="SCPTnomFreq">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableSpeedMotorDrive</ref>
			</refs>
		</cpt>
		<cpt id="SCPTnomRPM" idx="158" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>1800</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_rpm</ref>
			<name id="0-1044"/>
			<comment id="0-1045"/>
			<p-name>SCPTnomRPM</p-name>
			<formats>
				<format id="SCPTnomRPM">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableSpeedMotorDrive</ref>
			</refs>
		</cpt>
		<cpt id="SCPTnormalRotationalSpeed" idx="180" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_freq_hz</ref>
			<name id="0-1247"/>
			<comment id="0-1248"/>
			<p-name>SCPTnormalRotationalSpeed</p-name>
			<formats>
				<format id="SCPTnormalRotationalSpeed">text(&quot;%f&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTnsdsFbIndex" idx="358" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<scalar>
				<nc-type>unsigned long</nc-type>
				<min>0</min>
				<max>65535</max>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-5171"/>
			<p-name>SCPTnsdsFbIndex</p-name>
			<formats>
				<format id="SCPTnsdsFbIndex">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTstaticProgrammable</ref>
			</refs>
		</cpt>
		<cpt id="SCPTnumDampers" idx="269" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>1</min>
			<max>2</max>
			<default>1</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_count</ref>
			<name id="0-2237"/>
			<comment id="0-2238"/>
			<p-name>SCPTnumDampers</p-name>
			<formats>
				<format id="SCPTnumDampers">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTnumDigits" idx="293" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_count</ref>
			<name id="0-3239"/>
			<comment id="0-3240"/>
			<p-name>SCPTnumDigits</p-name>
			<formats>
				<format id="SCPTnumDigits">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTutilityMeter</ref>
			</refs>
		</cpt>
		<cpt id="SCPTnumValves" idx="59" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>1</min>
			<max>2</max>
			<default>2</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_count</ref>
			<name id="0-678"/>
			<comment id="0-679"/>
			<p-name>SCPTnumValves</p-name>
			<formats>
				<format id="SCPTnumValves">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTfanCoilUnit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTunitVentilatorController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTnvDynamicAssignment" idx="256" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>NV 65535 = FBlock 65535, Member 65535 PID 0:0:0:0:0:0:0:0, Scope 0, Index 1, NVT_CAT_INITIAL, 1 bytes, A=0, B=0, C=0</default>
			<size>25</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned long</nc-type>
							<min>0</min>
							<max>4095</max>
							<invalid>65535</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-2106"/>
						<comment id="0-2107"/>
						<unit id="0-2108"/>
						<p-name>nv_index</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned long</nc-type>
							<min>0</min>
							<max>4095</max>
							<invalid>65535</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-2109"/>
						<comment id="0-2110"/>
						<unit id="0-2111"/>
						<p-name>fblock_index</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned long</nc-type>
							<min>1</min>
							<max>4095</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-2112"/>
						<comment id="0-2113"/>
						<unit id="0-2114"/>
						<p-name>member_number</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_nv_type</ref>
						<p-name>nv_type</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-2104"/>
			<comment id="0-2105"/>
			<p-name>SCPTnvDynamicAssignment</p-name>
			<formats>
				<format id="SCPTnvDynamicAssignment">
					text(&quot;NV %d = FBlock %d, Member %d PID %x:%x:%x:%x:%x:%x:%x:%x, Scope %d, Index %d, %m, %d bytes, A=%d, B=%d, C=%d&quot;, nv_index,  fblock_index,  member_number, nv_type.type_program_ID[0],  nv_type.type_program_ID[1], nv_type.type_program_ID[2],  nv_type.type_program_ID[3], nv_type.type_program_ID[4],  nv_type.type_program_ID[5], nv_type.type_program_ID[6],  nv_type.type_program_ID[7], nv_type.type_scope,  nv_type.type_index, nv_type.type_category,  nv_type.type_length, nv_type.scaling_factor_a,  nv_type.scaling_factor_b,  nv_type.scaling_factor_c)
				</format>
			</formats>
		</cpt>
		<cpt id="SCPTnvPriority" idx="296" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0</default>
			<size>1</size>
			<aggregate cat="struct">
				<members>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>0</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-3377"/>
						<comment id="0-3378"/>
						<p-name>user_flag</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>7</width>
							<offset>1</offset>
							<min>0</min>
							<max>127</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-3379"/>
						<comment id="0-3380"/>
						<p-name>nv</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-3377"/>
			<comment id="0-3378"/>
			<p-name>SCPTnvPriority</p-name>
			<formats>
				<format id="SCPTnvPriority">text(&quot;%d %d&quot;, user_flag,nv)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsunblindController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTnvType" idx="254" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>PID 0:0:0:0:0:0:0:0, Scope 0, Index 1, NVT_CAT_INITIAL, 1 bytes, A=0, B=0, C=0</default>
			<size>19</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_nv_type</ref>
			<name id="0-2079"/>
			<comment id="0-2101"/>
			<p-name>SCPTnvType</p-name>
			<formats>
				<format id="SCPTnvType">
					text(&quot;PID %x:%x:%x:%x:%x:%x:%x:%x, Scope %d, Index %d, %m, %d bytes, A=%d, B=%d, C=%d&quot;, type_program_ID[0],  type_program_ID[1], type_program_ID[2],  type_program_ID[3], type_program_ID[4],  type_program_ID[5], type_program_ID[6],  type_program_ID[7], type_scope,  type_index, type_category,  type_length, scaling_factor_a,  scaling_factor_b,  scaling_factor_c)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTnvUsage" idx="364" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>in_use:0, mfg:0</default>
			<size>1</size>
			<aggregate cat="struct">
				<members>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>0</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<p-name>in_use</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>7</width>
							<offset>1</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<p-name>mfg</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5220"/>
			<comment id="0-5219"/>
			<p-name>SCPTnvUsage</p-name>
			<formats>
				<format id="SCPTnvUsage">text(&quot;in_use:%d, mfg:%d&quot;, in_use,mfg)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTstaticProgrammable</ref>
			</refs>
		</cpt>
		<cpt id="SCPTnwrkCnfg" idx="25" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>CFG_EXTERNAL</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_config_src</ref>
			<name id="0-453"/>
			<comment id="0-454"/>
			<p-name>SCPTnwrkCnfg</p-name>
			<formats>
				<format id="SCPTnwrkCnfg">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorArrivalGong</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorDirectionLantern</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorHallLantern</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorPositionIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorVoiceAnnouncer</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTentryExit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTidentifierSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTnodeObject</ref>
			</refs>
		</cpt>
		<cpt id="SCPTobjMajVer" idx="167" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>255</max>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-1036"/>
			<comment id="0-1037"/>
			<p-name>SCPTobjMajVer</p-name>
			<formats>
				<format id="SCPTobjMajVer">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTcalendar</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelContinuityMonitor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelMonitor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclothesWasherDomestic</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdeviceMonitor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorArrivalGong</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorDirectionLantern</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorFireSystemsPort</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorHallLantern</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorPositionIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorVoiceAnnouncer</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTentryExit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTidentifierSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiOccupancySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrailcarAudioController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrailcarAudioSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTstaticProgrammable</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsunblindActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsunblindController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTutilityMeter</ref>
			</refs>
		</cpt>
		<cpt id="SCPTobjMinVer" idx="168" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>255</max>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-1038"/>
			<comment id="0-1039"/>
			<p-name>SCPTobjMinVer</p-name>
			<formats>
				<format id="SCPTobjMinVer">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTcalendar</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelContinuityMonitor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchannelMonitor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclothesWasherDomestic</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdeviceMonitor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorArrivalGong</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorDirectionLantern</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorFireSystemsPort</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorHallLantern</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorPositionIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorVoiceAnnouncer</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTentryExit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTidentifierSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiOccupancySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrailcarAudioController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrailcarAudioSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTstaticProgrammable</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsunblindActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsunblindController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTutilityMeter</ref>
			</refs>
		</cpt>
		<cpt id="SCPToccupancyBehavior" idx="372" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>OC_OCCUPIED OC_OCCUPIED OC_OCCUPIED OC_OCCUPIED OC_OCCUPIED</default>
			<size>5</size>
			<aggregate cat="struct">
				<members>
					<member>
						<enum>
							<min>-1</min>
							<max>3</max>
							<idx>15</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">occup_t</ref>
						</enum>
						<name id="0-5457"/>
						<comment id="0-5458"/>
						<p-name>ob_nul_value</p-name>
					</member>
					<member>
						<enum>
							<min>-1</min>
							<max>3</max>
							<idx>15</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">occup_t</ref>
						</enum>
						<name id="0-5459"/>
						<comment id="0-5460"/>
						<p-name>ob_occupied_value</p-name>
					</member>
					<member>
						<enum>
							<min>-1</min>
							<max>3</max>
							<idx>15</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">occup_t</ref>
						</enum>
						<name id="0-5461"/>
						<comment id="0-5462"/>
						<p-name>ob_unoccupied_value</p-name>
					</member>
					<member>
						<enum>
							<min>-1</min>
							<max>3</max>
							<idx>15</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">occup_t</ref>
						</enum>
						<name id="0-5463"/>
						<comment id="0-5464"/>
						<p-name>ob_bypass_value</p-name>
					</member>
					<member>
						<enum>
							<min>-1</min>
							<max>3</max>
							<idx>15</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">occup_t</ref>
						</enum>
						<name id="0-5465"/>
						<comment id="0-5466"/>
						<p-name>ob_standby_value</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5455"/>
			<comment id="0-5456"/>
			<p-name>SCPToccupancyBehavior</p-name>
			<formats>
				<format id="SCPToccupancyBehavior">text(&quot;%m %m %m %m %m&quot;,  ob_nul_value, ob_occupied_value, ob_unoccupied_value, ob_bypass_value, ob_standby_value)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPToccupancyThresholds" idx="380" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0</default>
			<size>3</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>50</max>
							<invalid>255</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-5489"/>
						<comment id="0-5490"/>
						<p-name>occupied</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>50</max>
							<invalid>255</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-5491"/>
						<comment id="0-5492"/>
						<p-name>standby_to_occupied</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>50</max>
							<invalid>255</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-5493"/>
						<comment id="0-5494"/>
						<p-name>unoccupied_to_occupied</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5487"/>
			<comment id="0-5488"/>
			<p-name>SCPToccupancyThresholds</p-name>
			<formats>
				<format id="SCPToccupancyThresholds">text(&quot;%d %d %d&quot;,  occupied, standby_to_occupied, unoccupied_to_occupied)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPToemType" idx="61" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>00*31</min>
			<max>FF*16-00*15</max>
			<default>00*31</default>
			<size>31</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_str_asc</ref>
			<name id="0-682"/>
			<comment id="0-986"/>
			<p-name>SCPToemType</p-name>
			<formats>
				<format id="SCPToemType">text(&quot;%s&quot;, ascii)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTaudibleFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfireSmokeDamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpullStationFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorConvent</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvisibleFireIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPToffDely" idx="30" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>0 17:59:59:999</max>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-460"/>
			<comment id="0-461"/>
			<p-name>SCPToffDely</p-name>
			<formats>
				<format id="SCPToffDely">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPToffDely#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfireSmokeDamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPToffset" idx="26" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPToffset">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTairVelocitySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTglobalSolarRadiation</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpressureSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPToffsetCO2" idx="68" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_ppm</ref>
			<name id="0-553"/>
			<comment id="0-496"/>
			<p-name>SCPToffsetCO2</p-name>
			<formats>
				<format id="SCPToffsetCO2">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTco2Sensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccCommandModule</ref>
			</refs>
		</cpt>
		<cpt id="SCPToffsetFlow" idx="265" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>4</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow_f</ref>
			<name id="0-2231"/>
			<comment id="0-2232"/>
			<p-name>SCPToffsetFlow</p-name>
			<formats>
				<format id="SCPToffsetFlow#SI">text(&quot;%f&quot;)</format>
				<format id="SCPToffsetFlow#US">text(&quot;%f&quot;, *2.1189+0(0:966))</format>
				<format id="SCPToffsetFlow#US_cfm">text(&quot;%f&quot;, *2.1189+0(0:966))</format>
				<format id="SCPToffsetFlow#US_liq">text(&quot;%f&quot;, *0.26418+0(0:837))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPToffsetRH" idx="69" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-554"/>
			<comment id="0-496"/>
			<p-name>SCPToffsetRH</p-name>
			<formats>
				<format id="SCPToffsetRH">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacRelativeHumiditySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccCommandModule</ref>
			</refs>
		</cpt>
		<cpt id="SCPToffsetTemp" idx="70" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-555"/>
			<comment id="0-496"/>
			<p-name>SCPToffsetTemp</p-name>
			<formats>
				<format id="SCPToffsetTemp#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPToffsetTemp#US">text(&quot;%f&quot;, *1.8+0(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacTempSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccCommandModule</ref>
			</refs>
		</cpt>
		<cpt id="SCPTonOffHysteresis" idx="84" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_cont</ref>
			<name id="0-700"/>
			<comment id="0-701"/>
			<p-name>SCPTonOffHysteresis</p-name>
			<formats>
				<format id="SCPTonOffHysteresis">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTconstantLightController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTorientation" idx="231" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_angle_deg</ref>
			<name id="0-1347"/>
			<comment id="0-1348"/>
			<p-name>SCPTorientation</p-name>
			<formats>
				<format id="SCPTorientation">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorPositionIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPToutdoorAirEnthalpySetpoint" idx="200" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>40,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_enthalpy</ref>
			<name id="0-1287"/>
			<comment id="0-1288"/>
			<p-name>SCPToutdoorAirEnthalpySetpoint</p-name>
			<formats>
				<format id="SCPToutdoorAirEnthalpySetpoint#SI">text(&quot;%f&quot;)</format>
				<format id="SCPToutdoorAirEnthalpySetpoint#US">text(&quot;%f&quot;, *0.429923+7.67(0:1400))</format>
				<format id="SCPToutdoorAirEnthalpySetpoint#US_diff">text(&quot;%f&quot;, *0.429923+0(0:1400))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPToutdoorAirTempSetpoint" idx="199" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>10,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-1285"/>
			<comment id="0-1286"/>
			<p-name>SCPToutdoorAirTempSetpoint</p-name>
			<formats>
				<format id="SCPToutdoorAirTempSetpoint#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPToutdoorAirTempSetpoint#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTovrBehave" idx="32" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>OV_RETAIN</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_override</ref>
			<name id="0-464"/>
			<comment id="0-465"/>
			<p-name>SCPTovrBehave</p-name>
			<formats>
				<format id="SCPTovrBehave">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTcalendar</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTovrValue" idx="33" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTovrValue">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTcalendar</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTpartNumber" idx="182" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*31</default>
			<size>31</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_str_asc</ref>
			<name id="0-1251"/>
			<comment id="0-1252"/>
			<p-name>SCPTpartNumber</p-name>
			<formats>
				<format id="SCPTpartNumber">text(&quot;%s&quot;,ascii)</format>
			</formats>
		</cpt>
		<cpt id="SCPTpollRate" idx="335" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>4</size>
			<scalar>
				<nc-type>s32_type</nc-type>
				<min>0</min>
				<max>2147483646</max>
				<invalid>2147483647</invalid>
				<scaling>
					<a>1</a>
					<b>-1</b>
					<c>0</c>
					<s>0.10000000149012</s>
				</scaling>
			</scalar>
			<name id="0-4000"/>
			<comment id="0-4001"/>
			<unit id="0-43"/>
			<p-name>SCPTpollRate</p-name>
			<formats>
				<format id="SCPTpollRate">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
			</refs>
		</cpt>
		<cpt id="SCPTpowerupState" idx="87" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>SET_OFF 0,0 0,00</default>
			<size>4</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_setting</ref>
			<name id="0-706"/>
			<comment id="0-707"/>
			<p-name>SCPTpowerupState</p-name>
			<formats>
				<format id="SCPTpowerupState">text(&quot;%m %f %f&quot;, function, setting, rotation)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTconstantLightController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTprimeVal" idx="155" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>100,0 1</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_switch</ref>
			<name id="0-957"/>
			<comment id="0-958"/>
			<p-name>SCPTprimeVal</p-name>
			<formats>
				<format id="SCPTprimeVal">text(&quot;%f %d&quot;, value, state)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPToccupancyController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTprogCmdHistory" idx="356" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0/0/0 0:0:0 - RQ_NORMAL: </default>
			<size>88</size>
			<aggregate cat="struct">
				<members>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp</ref>
						<p-name>timestamp</p-name>
					</member>
					<member>
						<enum>
							<min>-1</min>
							<max>24</max>
							<idx>10</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">object_request_t</ref>
						</enum>
						<p-name>command</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned char</nc-type>
							<min>0</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
							<array-size>80</array-size>
						</scalar>
						<p-name>description</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5144"/>
			<comment id="0-5145"/>
			<p-name>SCPTprogCmdHistory</p-name>
			<formats>
				<format id="SCPTprogCmdHistory">text(&quot;%d/%d/%d %d:%d:%d - %m: %s&quot;,  timestamp.year, timestamp.month, timestamp.day, timestamp.hour, timestamp.minute, timestamp.second, command, description)</format>
				<format id="SCPTprogCmdHistory#LO">text(date(timestamp.year, timestamp.month, timestamp.day), (&quot; &quot;), time(timestamp.hour, timestamp.minute, timestamp.second),(&quot; - %m: %s&quot;, command, description))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTstaticProgrammable</ref>
			</refs>
		</cpt>
		<cpt id="SCPTprogErrorHistory" idx="363" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0/0/0 0:0:0 PSE_NO_ERROR</default>
			<size>8</size>
			<aggregate cat="struct">
				<members>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp</ref>
						<p-name>time_of_error</p-name>
					</member>
					<member>
						<enum>
							<min>-1</min>
							<max>63</max>
							<idx>85</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">program_status_error_t</ref>
						</enum>
						<p-name>error</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5146"/>
			<comment id="0-5147"/>
			<p-name>SCPTprogErrorHistory</p-name>
			<formats>
				<format id="SCPTprogErrorHistory">text(&quot;%d/%d/%d %d:%d:%d %m&quot;,  time_of_error.year, time_of_error.month, time_of_error.day, time_of_error.hour, time_of_error.minute, time_of_error.second, error)</format>
				<format id="SCPTprogErrorHistory#LO">
					text(date(time_of_error.year, time_of_error.month, time_of_error.day), (&quot; &quot;), time(time_of_error.hour, time_of_error.minute, time_of_error.second),(&quot; - %m&quot;,  error))
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTstaticProgrammable</ref>
			</refs>
		</cpt>
		<cpt id="SCPTprogFileIndexes" idx="355" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>3 - 3</default>
			<size>2</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>3</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<p-name>first_file_index</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>3</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<p-name>last_file_index</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5142"/>
			<comment id="0-5143"/>
			<p-name>SCPTprogFileIndexes</p-name>
			<formats>
				<format id="SCPTprogFileIndexes">text(&quot;%d - %d&quot;,  first_file_index, last_file_index)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTstaticProgrammable</ref>
			</refs>
		</cpt>
		<cpt id="SCPTprogName" idx="351" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*31</default>
			<size>31</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_str_asc</ref>
			<name id="0-5134"/>
			<comment id="0-5135"/>
			<p-name>SCPTprogName</p-name>
			<formats>
				<format id="SCPTprogName">text(&quot;%s&quot;, ascii)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTstaticProgrammable</ref>
			</refs>
		</cpt>
		<cpt id="SCPTprogRevision" idx="352" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>v0.0.0 (0/0/0 0:0:0)</default>
			<size>11</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<p-name>major_version</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<p-name>minor_version</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned long</nc-type>
							<min>0</min>
							<max>65535</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<p-name>build_number</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp</ref>
						<p-name>build_date</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5136"/>
			<comment id="0-5137"/>
			<p-name>SCPTprogRevision</p-name>
			<formats>
				<format id="SCPTprogRevision">
					text(&quot;v%d.%d.%d (%d/%d/%d %d:%d:%d)&quot;,  major_version, minor_version, build_number, build_date.year, build_date.month, build_date.day, build_date.hour, build_date.minute, build_date.second)
				</format>
				<format id="SCPTprogRevision#LO">
					text((&quot;v%d.%d.%d (&quot;, major_version,minor_version,build_number),date(build_date.year, build_date.month, build_date.day), (&quot; &quot;), time(build_date.hour, build_date.minute, build_date.second), (&quot;) &quot;))
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTstaticProgrammable</ref>
			</refs>
		</cpt>
		<cpt id="SCPTprogSelect" idx="353" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>255</max>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-5138"/>
			<comment id="0-5139"/>
			<p-name>SCPTprogSelect</p-name>
			<formats>
				<format id="SCPTprogSelect">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTstaticProgrammable</ref>
			</refs>
		</cpt>
		<cpt id="SCPTprogSourceLocation" idx="354" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*255</default>
			<size>255</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned char</nc-type>
							<min>0</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
							<array-size>255</array-size>
						</scalar>
						<p-name>location</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5140"/>
			<comment id="0-5141"/>
			<p-name>SCPTprogSourceLocation</p-name>
			<formats>
				<format id="SCPTprogSourceLocation">text(&quot;%s&quot;, location)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTstaticProgrammable</ref>
			</refs>
		</cpt>
		<cpt id="SCPTprogStateHistory" idx="357" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0/0/0 0:0:0 PRS_NO_PROGRAM</default>
			<size>8</size>
			<aggregate cat="struct">
				<members>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp</ref>
						<p-name>time_of_state_change</p-name>
					</member>
					<member>
						<enum>
							<min>-1</min>
							<max>5</max>
							<idx>83</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">program_state_t</ref>
						</enum>
						<p-name>state</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5146"/>
			<comment id="0-5147"/>
			<p-name>SCPTprogStateHistory</p-name>
			<formats>
				<format id="SCPTprogStateHistory">
					text(&quot;%d/%d/%d %d:%d:%d %m&quot;,  time_of_state_change.year, time_of_state_change.month, time_of_state_change.day, time_of_state_change.hour, time_of_state_change.minute, time_of_state_change.second, state)
				</format>
				<format id="SCPTprogStateHistory#LO">
					text(date(time_of_state_change.year, time_of_state_change.month, time_of_state_change.day), (&quot; &quot;), time(time_of_state_change.hour, time_of_state_change.minute, time_of_state_change.second),(&quot; - %m&quot;,  state))
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTstaticProgrammable</ref>
			</refs>
		</cpt>
		<cpt id="SCPTpulseValue" idx="292" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0</default>
			<size>4</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_muldiv</ref>
			<name id="0-3237"/>
			<comment id="0-3238"/>
			<p-name>SCPTpulseValue</p-name>
			<formats>
				<format id="SCPTpulseValue">text(&quot;%d %d&quot;, multiplier,divisor)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTutilityMeter</ref>
			</refs>
		</cpt>
		<cpt id="SCPTpumpCharacteristic" idx="233" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0,0 0,00</default>
			<size>6</size>
			<aggregate cat="struct">
				<members>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_rpm</ref>
						<name id="0-1355"/>
						<p-name>speedMax</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_press</ref>
						<name id="0-1356"/>
						<comment id="0-1357"/>
						<p-name>pressMax</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_flow_p</ref>
						<name id="0-671"/>
						<comment id="0-1358"/>
						<p-name>flowMax</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-1352"/>
			<comment id="0-1353"/>
			<unit id="0-1354"/>
			<p-name>SCPTpumpCharacteristic</p-name>
			<formats>
				<format id="SCPTpumpCharacteristic#SI">text(&quot;%d %f %f&quot;,  speedMax,  pressMax,  flowMax*1+0(0:1408))</format>
				<format id="SCPTpumpCharacteristic#US">text(&quot;%d %f %f&quot;,  speedMax,  pressMax*0.2953+0(0:1402),    flowMax*0.588578+0(0:1405))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTpumpController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTpumpDownDelay" idx="113" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-748"/>
			<comment id="0-749"/>
			<p-name>SCPTpumpDownDelay</p-name>
			<formats>
				<format id="SCPTpumpDownDelay">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTboilerController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerDefrost</ref>
			</refs>
		</cpt>
		<cpt id="SCPTpwmPeriod" idx="216" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-1319"/>
			<comment id="0-1320"/>
			<p-name>SCPTpwmPeriod</p-name>
			<formats>
				<format id="SCPTpwmPeriod">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTpwmPeriod#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
		</cpt>
		<cpt id="SCPTpwrSendOnDelta" idx="315" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,5</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_power</ref>
			<name id="0-3675"/>
			<comment id="0-3676"/>
			<p-name>SCPTpwrSendOnDelta</p-name>
			<formats>
				<format id="SCPTpwrSendOnDelta">text(&quot;%f&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTpwrUpDelay" idx="72" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-687"/>
			<comment id="0-989"/>
			<p-name>SCPTpwrUpDelay</p-name>
			<formats>
				<format id="SCPTpwrUpDelay">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchiller</ref>
			</refs>
		</cpt>
		<cpt id="SCPTpwrUpState" idx="73" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0 0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_switch</ref>
			<name id="0-688"/>
			<comment id="0-990"/>
			<p-name>SCPTpwrUpState</p-name>
			<formats>
				<format id="SCPTpwrUpState">text(&quot;%f %d&quot;, value, state)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTboilerController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTchiller</ref>
				<ref href="0000000000000000-0/fps.xml">SFPToutdoorLuminairController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTrampDownTm" idx="161" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>10,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-1050"/>
			<comment id="0-1051"/>
			<p-name>SCPTrampDownTm</p-name>
			<formats>
				<format id="SCPTrampDownTm">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableSpeedMotorDrive</ref>
			</refs>
		</cpt>
		<cpt id="SCPTrampUpTm" idx="160" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>10,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-1048"/>
			<comment id="0-1049"/>
			<p-name>SCPTrampUpTm</p-name>
			<formats>
				<format id="SCPTrampUpTm">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPToutdoorLuminairController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableSpeedMotorDrive</ref>
			</refs>
		</cpt>
		<cpt id="SCPTrandomizationInterval" idx="376" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0 0,0</default>
			<size>4</size>
			<aggregate cat="struct">
				<members>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
						<name id="0-5475"/>
						<p-name>earliest_time_offset</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
						<name id="0-5476"/>
						<p-name>latest_time_offset</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5473"/>
			<comment id="0-5474"/>
			<p-name>SCPTrandomizationInterval</p-name>
			<formats>
				<format id="SCPTrandomizationInterval">text(&quot;%f %f&quot;,  earliest_time_offset, latest_time_offset)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPTreflection" idx="89" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-708"/>
			<comment id="0-709"/>
			<p-name>SCPTreflection</p-name>
			<formats>
				<format id="SCPTreflection">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTlightSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTrefrigGlide" idx="117" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>-274,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp</ref>
			<name id="0-756"/>
			<comment id="0-757"/>
			<p-name>SCPTrefrigGlide</p-name>
			<formats>
				<format id="SCPTrefrigGlide#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTrefrigGlide#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerEvaporator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTrefrigType" idx="119" stlp_std="yes">
			<obsolete>no</obsolete>
			<default> 0,0,0</default>
			<size>18</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned char</nc-type>
							<min>0</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
							<array-size>6</array-size>
						</scalar>
						<name id="0-762"/>
						<unit id="0-763"/>
						<p-name>refrigerant</p-name>
					</member>
					<member>
						<float>
							<min>-3.4028234663853E+038</min>
							<max>3.4028234663853E+038</max>
						</float>
						<name id="0-764"/>
						<p-name>A</p-name>
					</member>
					<member>
						<float>
							<min>-3.4028234663853E+038</min>
							<max>3.4028234663853E+038</max>
						</float>
						<name id="0-765"/>
						<p-name>B</p-name>
					</member>
					<member>
						<float>
							<min>-3.4028234663853E+038</min>
							<max>3.4028234663853E+038</max>
						</float>
						<name id="0-766"/>
						<p-name>C</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-760"/>
			<unit id="0-761"/>
			<p-name>SCPTrefrigType</p-name>
			<formats>
				<format id="SCPTrefrigType">text(&quot;%s %f,%f,%f&quot;, refrigerant, A, B, C)</format>
				<format id="SCPTrefrigType#LO">text(&quot;%s %f|%f|%f&quot;, refrigerant, A, B, C)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerEvaporator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTregName" idx="163" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*31</default>
			<size>31</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_str_asc</ref>
			<name id="0-1028"/>
			<comment id="0-1029"/>
			<p-name>SCPTregName</p-name>
			<formats>
				<format id="SCPTregName">text(&quot;%s&quot;, ascii)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTutilityDataLoggerRegister</ref>
			</refs>
		</cpt>
		<cpt id="SCPTreturnFanStaticPressureSetpoint" idx="194" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>10</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_press_p</ref>
			<name id="0-1275"/>
			<comment id="0-1276"/>
			<p-name>SCPTreturnFanStaticPressureSetpoint</p-name>
			<formats>
				<format id="SCPTreturnFanStaticPressureSetpoint#SI">text(&quot;%f&quot;)</format>
				<format id="SCPTreturnFanStaticPressureSetpoint#US">text(&quot;%f&quot;, *0.0040217+0(0:954))</format>
				<format id="SCPTreturnFanStaticPressureSetpoint#US_psi">text(&quot;%f&quot;, *1.4504e-4+0(0:875))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTrunHrAlarm" idx="136" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>65535 23:0:0:0</max>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-798"/>
			<comment id="0-799"/>
			<p-name>SCPTrunHrAlarm</p-name>
			<formats>
				<format id="SCPTrunHrAlarm">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTrunHrAlarm#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTlampActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTrunHrInit" idx="135" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>65535 23:0:0:0</max>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-796"/>
			<comment id="0-797"/>
			<p-name>SCPTrunHrInit</p-name>
			<formats>
				<format id="SCPTrunHrInit">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTrunHrInit#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTlampActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTrunTimeAlarm" idx="290" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-3223"/>
			<comment id="0-3224"/>
			<p-name>SCPTrunTimeAlarm</p-name>
			<formats>
				<format id="SCPTrunTimeAlarm">text(&quot;%d %d %d %d %d&quot;,  day, hour, minute, second, millisecond)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsafExtCnfg" idx="257" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTsafExtCnfg">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTentryExit</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsaturationDelay" idx="271" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_min</ref>
			<name id="0-2241"/>
			<p-name>SCPTsaturationDelay</p-name>
			<formats>
				<format id="SCPTsaturationDelay">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscanTime" idx="321" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0:0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_elapsed_tm</ref>
			<name id="0-3667"/>
			<comment id="0-3668"/>
			<p-name>SCPTscanTime</p-name>
			<formats>
				<format id="SCPTscanTime">text(&quot;%d %d:%d:%d:%d&quot;,  day,  hour,  minute,  second,  millisecond)</format>
				<format id="SCPTscanTime#LO">text((&quot;%d &quot;,  day),  time(hour,  minute,  second,  millisecond))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdeviceMonitor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscene" idx="307" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0,0 0 0</default>
			<size>4</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>1</min>
							<max>255</max>
							<invalid>0</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-3683"/>
						<comment id="0-3714"/>
						<p-name>scene_number</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>200</max>
							<invalid>255</invalid>
							<scaling>
								<a>5</a>
								<b>-1</b>
								<c>0</c>
								<s>0.5</s>
							</scaling>
						</scalar>
						<name id="0-3715"/>
						<comment id="0-3717"/>
						<unit id="0-3716"/>
						<p-name>setting</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>signed short</nc-type>
							<min>-90</min>
							<max>90</max>
							<invalid>-128</invalid>
							<scaling>
								<a>2</a>
								<b>0</b>
								<c>0</c>
								<s>2</s>
							</scaling>
						</scalar>
						<name id="0-3718"/>
						<comment id="0-3719"/>
						<unit id="0-375"/>
						<p-name>rotation</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>1</min>
							<max>255</max>
							<invalid>0</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-3720"/>
						<comment id="0-3721"/>
						<p-name>unoccupied_scene</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-3495"/>
			<comment id="0-3713"/>
			<p-name>SCPTscene</p-name>
			<formats>
				<format id="SCPTscene">text(&quot;%d %f %d %d&quot;,  scene_number, setting, rotation, unoccupied_scene)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsceneColor" idx="343" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>EC=COLOR_CIE31_LUMEN X=0,000 Y=0,000 ABSOLUT_Y=0</default>
			<size>5</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_color_2</ref>
			<name id="0-4143"/>
			<comment id="0-4144"/>
			<p-name>SCPTsceneColor</p-name>
			<formats>
				<format id="SCPTsceneColor">
					text((&quot;EC=%m &quot;,encoding),((encoding == 0)?(&quot;X=%f Y=%f ABSOLUT_Y=%d&quot;,color_value.CIE1931_lumen.x,color_value.CIE1931_lumen.y,color_value.CIE1931_lumen.absolute_Y):((encoding == 1) ?(&quot;X=%f Y=%f PERCENT_Y=%f&quot;,color_value.CIE1931_percent.x,color_value.CIE1931_percent.y,color_value.CIE1931_percent.percent_Y):((encoding == 2) ?(&quot;RED=%d GREEN=%d BLUE=%d&quot;,color_value.RGB.red,color_value.RGB.green,color_value.RGB.blue):((encoding == 3) ?(&quot;COL_TEMP=%d&quot;,color_value.color_temperature):(&quot;UNKNOWN&quot;))))))
				</format>
			</formats>
		</cpt>
		<cpt id="SCPTsceneName" idx="316" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>CE_UTF_8 </default>
			<size>13</size>
			<aggregate cat="struct">
				<members>
					<member>
						<enum>
							<min>-1</min>
							<max>2</max>
							<idx>69</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">char_encoding_t</ref>
						</enum>
						<name id="0-3673"/>
						<comment id="0-3674"/>
						<p-name>encoding</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
							<array-size>12</array-size>
						</scalar>
						<p-name>name</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-3671"/>
			<comment id="0-3672"/>
			<p-name>SCPTsceneName</p-name>
			<formats>
				<format id="SCPTsceneName">
					text((&quot;%m &quot;, encoding),((encoding == 0) ? (&quot;%s&quot;, name) :(&quot;%x %x %x %x %x %x %x %x %x %x %x %x&quot;,  name[0],  name[1],  name[2],  name[3],  name[4],  name[5],  name[6],  name[7],  name[8],  name[9],  name[10],  name[11])))
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiKeypad</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsceneNmbr" idx="94" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>1</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>1</min>
				<max>255</max>
				<invalid>0</invalid>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-585"/>
			<comment id="0-718"/>
			<unit id="0-719"/>
			<p-name>SCPTsceneNmbr</p-name>
			<formats>
				<format id="SCPTsceneNmbr">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTscenePanel</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsceneOffset" idx="157" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>1</size>
			<scalar>
				<nc-type>unsigned short</nc-type>
				<min>0</min>
				<max>255</max>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-961"/>
			<comment id="0-962"/>
			<p-name>SCPTsceneOffset</p-name>
			<formats>
				<format id="SCPTsceneOffset">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTpartitionWallController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsceneTiming" idx="308" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0 0,0</default>
			<size>4</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned long</nc-type>
							<min>0</min>
							<max>65535</max>
							<scaling>
								<a>1</a>
								<b>-1</b>
								<c>0</c>
								<s>0.10000000149012</s>
							</scaling>
						</scalar>
						<name id="0-3709"/>
						<comment id="0-3710"/>
						<unit id="0-43"/>
						<p-name>fade_time</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned long</nc-type>
							<min>0</min>
							<max>65535</max>
							<scaling>
								<a>1</a>
								<b>-1</b>
								<c>0</c>
								<s>0.10000000149012</s>
							</scaling>
						</scalar>
						<name id="0-3711"/>
						<comment id="0-3712"/>
						<unit id="0-43"/>
						<p-name>delay_time</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-3497"/>
			<comment id="0-3708"/>
			<p-name>SCPTsceneTiming</p-name>
			<formats>
				<format id="SCPTsceneTiming">text(&quot;%f %f&quot;, fade_time,delay_time)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiSunblindActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTschedule" idx="274" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 127 65535</default>
			<size>3</size>
			<aggregate cat="struct">
				<members>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>0</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-2490"/>
						<comment id="0-2491"/>
						<p-name>temporary</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>7</width>
							<offset>1</offset>
							<min>0</min>
							<max>127</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-2502"/>
						<comment id="0-2503"/>
						<p-name>schedule_priority</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned long</nc-type>
							<min>0</min>
							<max>65535</max>
							<invalid>65535</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-2504"/>
						<comment id="0-2505"/>
						<p-name>time_value_index</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-2500"/>
			<comment id="0-2501"/>
			<p-name>SCPTschedule</p-name>
			<formats>
				<format id="SCPTschedule">text(&quot;%d %d %d&quot;, temporary,  schedule_priority,  time_value_index)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscheduleDates" idx="273" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>-1 0 DM_EVERY_DAY -1 0 0 DM_EVERY_DAY MN_EVERY_MONTH DM_EVERY_DAY 65535</default>
			<size>12</size>
			<aggregate cat="struct">
				<members>
					<member>
						<aggregate cat="struct">
							<members>
								<member>
									<scalar>
										<nc-type>signed long</nc-type>
										<min>-1</min>
										<max>3000</max>
										<invalid>-1</invalid>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-2471"/>
									<comment id="0-2485"/>
									<p-name>year</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>12</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-2472"/>
									<comment id="0-2486"/>
									<p-name>month</p-name>
								</member>
								<member>
									<enum>
										<min>-1</min>
										<max>117</max>
										<idx>54</idx>
										<selector>0</selector>
										<ref href="0000000000000000-0/enums.xml">days_of_month_t</ref>
									</enum>
									<name id="0-2473"/>
									<comment id="0-2487"/>
									<p-name>day</p-name>
								</member>
							</members>
						</aggregate>
						<name id="0-2484"/>
						<p-name>start</p-name>
					</member>
					<member>
						<aggregate cat="struct">
							<members>
								<member>
									<scalar>
										<nc-type>signed long</nc-type>
										<min>-1</min>
										<max>3000</max>
										<invalid>-1</invalid>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<name id="0-2476"/>
									<comment id="0-2489"/>
									<p-name>year</p-name>
								</member>
								<member>
									<bitfield>
										<signed>no</signed>
										<width>1</width>
										<offset>0</offset>
										<min>0</min>
										<max>1</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</bitfield>
									<name id="0-2490"/>
									<comment id="0-2491"/>
									<p-name>temporary</p-name>
								</member>
								<member>
									<bitfield>
										<signed>no</signed>
										<width>7</width>
										<offset>1</offset>
										<min>0</min>
										<max>12</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</bitfield>
									<name id="0-2478"/>
									<comment id="0-2492"/>
									<p-name>month</p-name>
								</member>
								<member>
									<enum>
										<min>-1</min>
										<max>117</max>
										<idx>54</idx>
										<selector>0</selector>
										<ref href="0000000000000000-0/enums.xml">days_of_month_t</ref>
									</enum>
									<name id="0-2480"/>
									<comment id="0-2493"/>
									<p-name>day</p-name>
								</member>
							</members>
						</aggregate>
						<name id="0-2488"/>
						<p-name>end</p-name>
					</member>
					<member>
						<aggregate cat="struct">
							<members>
								<member>
									<enum>
										<min>-1</min>
										<max>24</max>
										<idx>55</idx>
										<selector>0</selector>
										<ref href="0000000000000000-0/enums.xml">months_t</ref>
									</enum>
									<name id="0-2494"/>
									<comment id="0-2495"/>
									<p-name>months</p-name>
								</member>
								<member>
									<enum>
										<min>-1</min>
										<max>117</max>
										<idx>54</idx>
										<selector>0</selector>
										<ref href="0000000000000000-0/enums.xml">days_of_month_t</ref>
									</enum>
									<name id="0-2496"/>
									<comment id="0-2497"/>
									<p-name>days</p-name>
								</member>
							</members>
						</aggregate>
						<p-name>qualifier</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned long</nc-type>
							<min>0</min>
							<max>65535</max>
							<invalid>65535</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-2498"/>
						<comment id="0-2499"/>
						<p-name>schedule_index</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-2482"/>
			<comment id="0-2483"/>
			<p-name>SCPTscheduleDates</p-name>
			<formats>
				<format id="SCPTscheduleDates">
					text(&quot;%d %d %m %d %d %d %m %m %m %d&quot;,  start.year, start.month, start.day, end.year, end.temporary, end.month, end.day, qualifier.months, qualifier.days, schedule_index)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTcalendar</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscheduleException" idx="374" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>MN_NUL DM_EVERY_DAY 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0</default>
			<size>8</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_sched_exc</ref>
			<name id="0-5469"/>
			<comment id="0-5470"/>
			<p-name>SCPTscheduleException</p-name>
			<formats>
				<format id="SCPTscheduleException">
					text(&quot;%m %m %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d&quot;,  months, days, start_time_value.sunrise_relative_flag, start_time_value.sunset_relative_flag, start_time_value.negative_time_offset_flag, start_time_value.hour, start_time_value.occ_value_ignored_flag, start_time_value.gp_value_ignored_flag, start_time_value.minutes, start_time_value.occupancy, start_time_value.gp_value, end_time.sunrise_relative_flag, end_time.sunset_relative_flag, end_time.negative_time_offset_flag, end_time.hour, end_time.start_offset_enable_flag, end_time.stop_offset_enable_flag, end_time.minutes)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscheduleFriday" idx="370" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>
				0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0
			</default>
			<size>28</size>
			<aggregate cat="struct">
				<members>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_val_2</ref>
						<array-size>7</array-size>
						<p-name>time_value</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5451"/>
			<comment id="0-5452"/>
			<p-name>SCPTscheduleFriday</p-name>
			<formats>
				<format id="SCPTscheduleFriday">
					text(&quot;%d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d&quot;,  time_value[0].sunrise_relative_flag, time_value[0].sunset_relative_flag, time_value[0].negative_time_offset_flag, time_value[0].hour, time_value[0].occ_value_ignored_flag, time_value[0].gp_value_ignored_flag, time_value[0].minutes, time_value[0].occupancy, time_value[0].gp_value, time_value[1].sunrise_relative_flag, time_value[1].sunset_relative_flag, time_value[1].negative_time_offset_flag, time_value[1].hour, time_value[1].occ_value_ignored_flag, time_value[1].gp_value_ignored_flag, time_value[1].minutes, time_value[1].occupancy, time_value[1].gp_value, time_value[2].sunrise_relative_flag, time_value[2].sunset_relative_flag, time_value[2].negative_time_offset_flag, time_value[2].hour, time_value[2].occ_value_ignored_flag, time_value[2].gp_value_ignored_flag, time_value[2].minutes, time_value[2].occupancy, time_value[2].gp_value, time_value[3].sunrise_relative_flag, time_value[3].sunset_relative_flag, time_value[3].negative_time_offset_flag, time_value[3].hour, time_value[3].occ_value_ignored_flag, time_value[3].gp_value_ignored_flag, time_value[3].minutes, time_value[3].occupancy, time_value[3].gp_value, time_value[4].sunrise_relative_flag, time_value[4].sunset_relative_flag, time_value[4].negative_time_offset_flag, time_value[4].hour, time_value[4].occ_value_ignored_flag, time_value[4].gp_value_ignored_flag, time_value[4].minutes, time_value[4].occupancy, time_value[4].gp_value, time_value[5].sunrise_relative_flag, time_value[5].sunset_relative_flag, time_value[5].negative_time_offset_flag, time_value[5].hour, time_value[5].occ_value_ignored_flag, time_value[5].gp_value_ignored_flag, time_value[5].minutes, time_value[5].occupancy, time_value[5].gp_value, time_value[6].sunrise_relative_flag, time_value[6].sunset_relative_flag, time_value[6].negative_time_offset_flag, time_value[6].hour, time_value[6].occ_value_ignored_flag, time_value[6].gp_value_ignored_flag, time_value[6].minutes, time_value[6].occupancy, time_value[6].gp_value)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscheduleHoliday" idx="375" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>MN_EVERY_MONTH DM_EVERY_DAY 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0</default>
			<size>8</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_sched_exc</ref>
			<name id="0-5471"/>
			<comment id="0-5472"/>
			<p-name>SCPTscheduleHoliday</p-name>
			<formats>
				<format id="SCPTscheduleHoliday">
					text(&quot;%m %m %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d&quot;,  months, days, start_time_value.sunrise_relative_flag, start_time_value.sunset_relative_flag, start_time_value.negative_time_offset_flag, start_time_value.hour, start_time_value.occ_value_ignored_flag, start_time_value.gp_value_ignored_flag, start_time_value.minutes, start_time_value.occupancy, start_time_value.gp_value, end_time.sunrise_relative_flag, end_time.sunset_relative_flag, end_time.negative_time_offset_flag, end_time.hour, end_time.start_offset_enable_flag, end_time.stop_offset_enable_flag, end_time.minutes)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscheduleInternal" idx="226" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>BOOL_FALSE</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>1</max>
				<idx>41</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">boolean_t</ref>
			</enum>
			<name id="0-1338"/>
			<comment id="0-1339"/>
			<unit id="0-153"/>
			<p-name>SCPTscheduleInternal</p-name>
			<formats>
				<format id="SCPTscheduleInternal">text(&quot;%m&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTscheduleMonday" idx="366" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>
				0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0
			</default>
			<size>28</size>
			<aggregate cat="struct">
				<members>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_val_2</ref>
						<array-size>7</array-size>
						<p-name>time_value</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5445"/>
			<comment id="0-5446"/>
			<p-name>SCPTscheduleMonday</p-name>
			<formats>
				<format id="SCPTscheduleMonday">
					text(&quot;%d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d&quot;,  time_value[0].sunrise_relative_flag, time_value[0].sunset_relative_flag, time_value[0].negative_time_offset_flag, time_value[0].hour, time_value[0].occ_value_ignored_flag, time_value[0].gp_value_ignored_flag, time_value[0].minutes, time_value[0].occupancy, time_value[0].gp_value, time_value[1].sunrise_relative_flag, time_value[1].sunset_relative_flag, time_value[1].negative_time_offset_flag, time_value[1].hour, time_value[1].occ_value_ignored_flag, time_value[1].gp_value_ignored_flag, time_value[1].minutes, time_value[1].occupancy, time_value[1].gp_value, time_value[2].sunrise_relative_flag, time_value[2].sunset_relative_flag, time_value[2].negative_time_offset_flag, time_value[2].hour, time_value[2].occ_value_ignored_flag, time_value[2].gp_value_ignored_flag, time_value[2].minutes, time_value[2].occupancy, time_value[2].gp_value, time_value[3].sunrise_relative_flag, time_value[3].sunset_relative_flag, time_value[3].negative_time_offset_flag, time_value[3].hour, time_value[3].occ_value_ignored_flag, time_value[3].gp_value_ignored_flag, time_value[3].minutes, time_value[3].occupancy, time_value[3].gp_value, time_value[4].sunrise_relative_flag, time_value[4].sunset_relative_flag, time_value[4].negative_time_offset_flag, time_value[4].hour, time_value[4].occ_value_ignored_flag, time_value[4].gp_value_ignored_flag, time_value[4].minutes, time_value[4].occupancy, time_value[4].gp_value, time_value[5].sunrise_relative_flag, time_value[5].sunset_relative_flag, time_value[5].negative_time_offset_flag, time_value[5].hour, time_value[5].occ_value_ignored_flag, time_value[5].gp_value_ignored_flag, time_value[5].minutes, time_value[5].occupancy, time_value[5].gp_value, time_value[6].sunrise_relative_flag, time_value[6].sunset_relative_flag, time_value[6].negative_time_offset_flag, time_value[6].hour, time_value[6].occ_value_ignored_flag, time_value[6].gp_value_ignored_flag, time_value[6].minutes, time_value[6].occupancy, time_value[6].gp_value)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscheduleName" idx="279" stlp_std="yes">
			<obsolete>no</obsolete>
			<max>~~~~~~~~~~~~~~~~~~~~~~</max>
			<default>00*22</default>
			<size>22</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned char</nc-type>
							<min>0</min>
							<max>126</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
							<array-size>22</array-size>
						</scalar>
						<p-name>name</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-2463"/>
			<comment id="0-2525"/>
			<p-name>SCPTscheduleName</p-name>
			<formats>
				<format id="SCPTscheduleName">text(&quot;%s&quot;, name)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTcalendar</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscheduleSaturday" idx="371" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>
				0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0
			</default>
			<size>28</size>
			<aggregate cat="struct">
				<members>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_val_2</ref>
						<array-size>7</array-size>
						<p-name>time_value</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5453"/>
			<comment id="0-5454"/>
			<p-name>SCPTscheduleSaturday</p-name>
			<formats>
				<format id="SCPTscheduleSaturday">
					text(&quot;%d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d&quot;,  time_value[0].sunrise_relative_flag, time_value[0].sunset_relative_flag, time_value[0].negative_time_offset_flag, time_value[0].hour, time_value[0].occ_value_ignored_flag, time_value[0].gp_value_ignored_flag, time_value[0].minutes, time_value[0].occupancy, time_value[0].gp_value, time_value[1].sunrise_relative_flag, time_value[1].sunset_relative_flag, time_value[1].negative_time_offset_flag, time_value[1].hour, time_value[1].occ_value_ignored_flag, time_value[1].gp_value_ignored_flag, time_value[1].minutes, time_value[1].occupancy, time_value[1].gp_value, time_value[2].sunrise_relative_flag, time_value[2].sunset_relative_flag, time_value[2].negative_time_offset_flag, time_value[2].hour, time_value[2].occ_value_ignored_flag, time_value[2].gp_value_ignored_flag, time_value[2].minutes, time_value[2].occupancy, time_value[2].gp_value, time_value[3].sunrise_relative_flag, time_value[3].sunset_relative_flag, time_value[3].negative_time_offset_flag, time_value[3].hour, time_value[3].occ_value_ignored_flag, time_value[3].gp_value_ignored_flag, time_value[3].minutes, time_value[3].occupancy, time_value[3].gp_value, time_value[4].sunrise_relative_flag, time_value[4].sunset_relative_flag, time_value[4].negative_time_offset_flag, time_value[4].hour, time_value[4].occ_value_ignored_flag, time_value[4].gp_value_ignored_flag, time_value[4].minutes, time_value[4].occupancy, time_value[4].gp_value, time_value[5].sunrise_relative_flag, time_value[5].sunset_relative_flag, time_value[5].negative_time_offset_flag, time_value[5].hour, time_value[5].occ_value_ignored_flag, time_value[5].gp_value_ignored_flag, time_value[5].minutes, time_value[5].occupancy, time_value[5].gp_value, time_value[6].sunrise_relative_flag, time_value[6].sunset_relative_flag, time_value[6].negative_time_offset_flag, time_value[6].hour, time_value[6].occ_value_ignored_flag, time_value[6].gp_value_ignored_flag, time_value[6].minutes, time_value[6].occupancy, time_value[6].gp_value)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscheduleSunday" idx="365" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>
				0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0
			</default>
			<size>28</size>
			<aggregate cat="struct">
				<members>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_val_2</ref>
						<array-size>7</array-size>
						<p-name>time_value</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5441"/>
			<comment id="0-5442"/>
			<p-name>SCPTscheduleSunday</p-name>
			<formats>
				<format id="SCPTscheduleSunday">
					text(&quot;%d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d&quot;,  time_value[0].sunrise_relative_flag, time_value[0].sunset_relative_flag, time_value[0].negative_time_offset_flag, time_value[0].hour, time_value[0].occ_value_ignored_flag, time_value[0].gp_value_ignored_flag, time_value[0].minutes, time_value[0].occupancy, time_value[0].gp_value, time_value[1].sunrise_relative_flag, time_value[1].sunset_relative_flag, time_value[1].negative_time_offset_flag, time_value[1].hour, time_value[1].occ_value_ignored_flag, time_value[1].gp_value_ignored_flag, time_value[1].minutes, time_value[1].occupancy, time_value[1].gp_value, time_value[2].sunrise_relative_flag, time_value[2].sunset_relative_flag, time_value[2].negative_time_offset_flag, time_value[2].hour, time_value[2].occ_value_ignored_flag, time_value[2].gp_value_ignored_flag, time_value[2].minutes, time_value[2].occupancy, time_value[2].gp_value, time_value[3].sunrise_relative_flag, time_value[3].sunset_relative_flag, time_value[3].negative_time_offset_flag, time_value[3].hour, time_value[3].occ_value_ignored_flag, time_value[3].gp_value_ignored_flag, time_value[3].minutes, time_value[3].occupancy, time_value[3].gp_value, time_value[4].sunrise_relative_flag, time_value[4].sunset_relative_flag, time_value[4].negative_time_offset_flag, time_value[4].hour, time_value[4].occ_value_ignored_flag, time_value[4].gp_value_ignored_flag, time_value[4].minutes, time_value[4].occupancy, time_value[4].gp_value, time_value[5].sunrise_relative_flag, time_value[5].sunset_relative_flag, time_value[5].negative_time_offset_flag, time_value[5].hour, time_value[5].occ_value_ignored_flag, time_value[5].gp_value_ignored_flag, time_value[5].minutes, time_value[5].occupancy, time_value[5].gp_value, time_value[6].sunrise_relative_flag, time_value[6].sunset_relative_flag, time_value[6].negative_time_offset_flag, time_value[6].hour, time_value[6].occ_value_ignored_flag, time_value[6].gp_value_ignored_flag, time_value[6].minutes, time_value[6].occupancy, time_value[6].gp_value)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscheduleThursday" idx="369" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>
				0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0
			</default>
			<size>28</size>
			<aggregate cat="struct">
				<members>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_val_2</ref>
						<array-size>7</array-size>
						<p-name>time_value</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5449"/>
			<comment id="0-5450"/>
			<p-name>SCPTscheduleThursday</p-name>
			<formats>
				<format id="SCPTscheduleThursday">
					text(&quot;%d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d&quot;,  time_value[0].sunrise_relative_flag, time_value[0].sunset_relative_flag, time_value[0].negative_time_offset_flag, time_value[0].hour, time_value[0].occ_value_ignored_flag, time_value[0].gp_value_ignored_flag, time_value[0].minutes, time_value[0].occupancy, time_value[0].gp_value, time_value[1].sunrise_relative_flag, time_value[1].sunset_relative_flag, time_value[1].negative_time_offset_flag, time_value[1].hour, time_value[1].occ_value_ignored_flag, time_value[1].gp_value_ignored_flag, time_value[1].minutes, time_value[1].occupancy, time_value[1].gp_value, time_value[2].sunrise_relative_flag, time_value[2].sunset_relative_flag, time_value[2].negative_time_offset_flag, time_value[2].hour, time_value[2].occ_value_ignored_flag, time_value[2].gp_value_ignored_flag, time_value[2].minutes, time_value[2].occupancy, time_value[2].gp_value, time_value[3].sunrise_relative_flag, time_value[3].sunset_relative_flag, time_value[3].negative_time_offset_flag, time_value[3].hour, time_value[3].occ_value_ignored_flag, time_value[3].gp_value_ignored_flag, time_value[3].minutes, time_value[3].occupancy, time_value[3].gp_value, time_value[4].sunrise_relative_flag, time_value[4].sunset_relative_flag, time_value[4].negative_time_offset_flag, time_value[4].hour, time_value[4].occ_value_ignored_flag, time_value[4].gp_value_ignored_flag, time_value[4].minutes, time_value[4].occupancy, time_value[4].gp_value, time_value[5].sunrise_relative_flag, time_value[5].sunset_relative_flag, time_value[5].negative_time_offset_flag, time_value[5].hour, time_value[5].occ_value_ignored_flag, time_value[5].gp_value_ignored_flag, time_value[5].minutes, time_value[5].occupancy, time_value[5].gp_value, time_value[6].sunrise_relative_flag, time_value[6].sunset_relative_flag, time_value[6].negative_time_offset_flag, time_value[6].hour, time_value[6].occ_value_ignored_flag, time_value[6].gp_value_ignored_flag, time_value[6].minutes, time_value[6].occupancy, time_value[6].gp_value)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscheduleTimeValue" idx="275" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>1 0 0 0 255</default>
			<size>3</size>
			<aggregate cat="struct">
				<members>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>0</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-2508"/>
						<comment id="0-2509"/>
						<p-name>invalid</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>1</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-2510"/>
						<comment id="0-2511"/>
						<p-name>terminator</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>6</width>
							<offset>2</offset>
							<min>0</min>
							<max>47</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-37"/>
						<comment id="0-2512"/>
						<p-name>hour</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>59</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-40"/>
						<comment id="0-2513"/>
						<p-name>minute</p-name>
					</member>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_sched_val</ref>
						<name id="0-2465"/>
						<comment id="0-2514"/>
						<p-name>value</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-2506"/>
			<comment id="0-2507"/>
			<p-name>SCPTscheduleTimeValue</p-name>
			<formats>
				<format id="SCPTscheduleTimeValue">text(&quot;%d %d %d %d %d&quot;, invalid,  terminator,  hour,  minute,  value)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscheduleTuesday" idx="367" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>
				0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0
			</default>
			<size>28</size>
			<aggregate cat="struct">
				<members>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_val_2</ref>
						<array-size>7</array-size>
						<p-name>time_value</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5447"/>
			<comment id="0-5448"/>
			<p-name>SCPTscheduleTuesday</p-name>
			<formats>
				<format id="SCPTscheduleTuesday">
					text(&quot;%d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d&quot;,  time_value[0].sunrise_relative_flag, time_value[0].sunset_relative_flag, time_value[0].negative_time_offset_flag, time_value[0].hour, time_value[0].occ_value_ignored_flag, time_value[0].gp_value_ignored_flag, time_value[0].minutes, time_value[0].occupancy, time_value[0].gp_value, time_value[1].sunrise_relative_flag, time_value[1].sunset_relative_flag, time_value[1].negative_time_offset_flag, time_value[1].hour, time_value[1].occ_value_ignored_flag, time_value[1].gp_value_ignored_flag, time_value[1].minutes, time_value[1].occupancy, time_value[1].gp_value, time_value[2].sunrise_relative_flag, time_value[2].sunset_relative_flag, time_value[2].negative_time_offset_flag, time_value[2].hour, time_value[2].occ_value_ignored_flag, time_value[2].gp_value_ignored_flag, time_value[2].minutes, time_value[2].occupancy, time_value[2].gp_value, time_value[3].sunrise_relative_flag, time_value[3].sunset_relative_flag, time_value[3].negative_time_offset_flag, time_value[3].hour, time_value[3].occ_value_ignored_flag, time_value[3].gp_value_ignored_flag, time_value[3].minutes, time_value[3].occupancy, time_value[3].gp_value, time_value[4].sunrise_relative_flag, time_value[4].sunset_relative_flag, time_value[4].negative_time_offset_flag, time_value[4].hour, time_value[4].occ_value_ignored_flag, time_value[4].gp_value_ignored_flag, time_value[4].minutes, time_value[4].occupancy, time_value[4].gp_value, time_value[5].sunrise_relative_flag, time_value[5].sunset_relative_flag, time_value[5].negative_time_offset_flag, time_value[5].hour, time_value[5].occ_value_ignored_flag, time_value[5].gp_value_ignored_flag, time_value[5].minutes, time_value[5].occupancy, time_value[5].gp_value, time_value[6].sunrise_relative_flag, time_value[6].sunset_relative_flag, time_value[6].negative_time_offset_flag, time_value[6].hour, time_value[6].occ_value_ignored_flag, time_value[6].gp_value_ignored_flag, time_value[6].minutes, time_value[6].occupancy, time_value[6].gp_value)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscheduleWednesday" idx="368" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>
				0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0 0 0 0 0 0 0 0 OC_OCCUPIED 0
			</default>
			<size>28</size>
			<aggregate cat="struct">
				<members>
					<member>
						<ref href="0000000000000000-0/nvs.xml">SNVT_time_val_2</ref>
						<array-size>7</array-size>
						<p-name>time_value</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-5534"/>
			<comment id="0-5535"/>
			<p-name>SCPTscheduleWednesday</p-name>
			<formats>
				<format id="SCPTscheduleWednesday">
					text(&quot;%d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d %d %d %d %d %d %d %d %m %d&quot;,  time_value[0].sunrise_relative_flag, time_value[0].sunset_relative_flag, time_value[0].negative_time_offset_flag, time_value[0].hour, time_value[0].occ_value_ignored_flag, time_value[0].gp_value_ignored_flag, time_value[0].minutes, time_value[0].occupancy, time_value[0].gp_value, time_value[1].sunrise_relative_flag, time_value[1].sunset_relative_flag, time_value[1].negative_time_offset_flag, time_value[1].hour, time_value[1].occ_value_ignored_flag, time_value[1].gp_value_ignored_flag, time_value[1].minutes, time_value[1].occupancy, time_value[1].gp_value, time_value[2].sunrise_relative_flag, time_value[2].sunset_relative_flag, time_value[2].negative_time_offset_flag, time_value[2].hour, time_value[2].occ_value_ignored_flag, time_value[2].gp_value_ignored_flag, time_value[2].minutes, time_value[2].occupancy, time_value[2].gp_value, time_value[3].sunrise_relative_flag, time_value[3].sunset_relative_flag, time_value[3].negative_time_offset_flag, time_value[3].hour, time_value[3].occ_value_ignored_flag, time_value[3].gp_value_ignored_flag, time_value[3].minutes, time_value[3].occupancy, time_value[3].gp_value, time_value[4].sunrise_relative_flag, time_value[4].sunset_relative_flag, time_value[4].negative_time_offset_flag, time_value[4].hour, time_value[4].occ_value_ignored_flag, time_value[4].gp_value_ignored_flag, time_value[4].minutes, time_value[4].occupancy, time_value[4].gp_value, time_value[5].sunrise_relative_flag, time_value[5].sunset_relative_flag, time_value[5].negative_time_offset_flag, time_value[5].hour, time_value[5].occ_value_ignored_flag, time_value[5].gp_value_ignored_flag, time_value[5].minutes, time_value[5].occupancy, time_value[5].gp_value, time_value[6].sunrise_relative_flag, time_value[6].sunset_relative_flag, time_value[6].negative_time_offset_flag, time_value[6].hour, time_value[6].occ_value_ignored_flag, time_value[6].gp_value_ignored_flag, time_value[6].minutes, time_value[6].occupancy, time_value[6].gp_value)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPTschedulerOptions" idx="379" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0</default>
			<size>1</size>
			<aggregate cat="struct">
				<members>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>5</width>
							<offset>0</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<p-name>reserved</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>5</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5481"/>
						<comment id="0-5482"/>
						<p-name>alternate_time_source</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>6</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5483"/>
						<comment id="0-5484"/>
						<p-name>general_purpose_output</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>7</offset>
							<min>0</min>
							<max>1</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-5485"/>
						<comment id="0-5486"/>
						<p-name>sunrise_sunset_relative</p-name>
					</member>
				</members>
			</aggregate>
			<p-name>SCPTschedulerOptions</p-name>
			<formats>
				<format id="SCPTschedulerOptions">text(&quot;%d %d %d %d&quot;,  reserved, alternate_time_source, general_purpose_output, sunrise_sunset_relative)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPTscrollSpeed" idx="229" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0 0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_switch</ref>
			<name id="0-1343"/>
			<comment id="0-1344"/>
			<p-name>SCPTscrollSpeed</p-name>
			<formats>
				<format id="SCPTscrollSpeed">text(&quot;%f %d&quot;, value, state)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorDirectionLantern</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorHallLantern</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorPositionIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsecondVal" idx="156" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0 0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_switch</ref>
			<name id="0-959"/>
			<comment id="0-960"/>
			<p-name>SCPTsecondVal</p-name>
			<formats>
				<format id="SCPTsecondVal">text(&quot;%f %d&quot;, value, state)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPToccupancyController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsensConstTmp" idx="65" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>1,0000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_multiplier</ref>
			<name id="0-683"/>
			<comment id="0-1009"/>
			<p-name>SCPTsensConstTmp</p-name>
			<formats>
				<format id="SCPTsensConstTmp">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsensConstVAV" idx="67" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>1,0000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_multiplier</ref>
			<name id="0-685"/>
			<comment id="0-1010"/>
			<p-name>SCPTsensConstVAV</p-name>
			<formats>
				<format id="SCPTsensConstVAV">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTserialNumber" idx="179" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*31</default>
			<size>31</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_str_asc</ref>
			<name id="0-1245"/>
			<comment id="0-1246"/>
			<p-name>SCPTserialNumber</p-name>
			<formats>
				<format id="SCPTserialNumber">text(&quot;%s&quot;, ascii)</format>
			</formats>
		</cpt>
		<cpt id="SCPTsetPnts" idx="60" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>-10,00,-10,00,-10,00,-10,00,-10,00,-10,00</min>
			<max>35,00,35,00,35,00,35,00,35,00,35,00</max>
			<default>23,00,25,00,28,00,21,00,19,00,16,00</default>
			<size>12</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_setpt</ref>
			<name id="0-680"/>
			<comment id="0-681"/>
			<p-name>SCPTsetPnts</p-name>
			<formats>
				<format id="SCPTsetPnts#SI">text(&quot;%f,%f,%f,%f,%f,%f&quot;, occupied_cool,  standby_cool,  unoccupied_cool, occupied_heat,  standby_heat,  unoccupied_heat)</format>
				<format id="SCPTsetPnts#SI_LO">text(&quot;%f|%f|%f|%f|%f|%f&quot;, occupied_cool,  standby_cool,  unoccupied_cool, occupied_heat,  standby_heat,  unoccupied_heat)</format>
				<format id="SCPTsetPnts#US">
					text(&quot;%f,%f,%f,%f,%f,%f&quot;,   occupied_cool*1.8+32(0:855),  standby_cool*1.8+32(0:855),  unoccupied_cool*1.8+32(0:855), occupied_heat*1.8+32(0:855),  standby_heat*1.8+32(0:855),  unoccupied_heat*1.8+32(0:855))
				</format>
				<format id="SCPTsetPnts#US_LO">
					text(&quot;%f|%f|%f|%f|%f|%f&quot;,   occupied_cool*1.8+32(0:855),  standby_cool*1.8+32(0:855),  unoccupied_cool*1.8+32(0:855), occupied_heat*1.8+32(0:855),  standby_heat*1.8+32(0:855),  unoccupied_heat*1.8+32(0:855))
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTchilledCeilingController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfanCoilUnit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTheatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTroofTopUnit</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccAHU</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccChilledCeiling</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccCommandModule</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccFanCoil</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccHeatPump</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRadiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccRooftop</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccSelfContained</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccUnitVentilator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsccVAV</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTspaceComfortController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermostat</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTunitVentilatorController</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvariableAirVolume</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsetpoint" idx="213" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTsetpoint">text(&quot;%d&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTsluiceCnfg" idx="259" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>MSC_UNKNOWN</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>2</max>
				<idx>52</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">master_slave_t</ref>
			</enum>
			<name id="0-2220"/>
			<comment id="0-2221"/>
			<p-name>SCPTsluiceCnfg</p-name>
			<formats>
				<format id="SCPTsluiceCnfg">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTentryExit</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsmokeDayAlrmLim" idx="40" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_smo_obscur</ref>
			<name id="0-661"/>
			<comment id="0-662"/>
			<p-name>SCPTsmokeDayAlrmLim</p-name>
			<formats>
				<format id="SCPTsmokeDayAlrmLim">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsmokeDayPreAlrmLim" idx="138" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_smo_obscur</ref>
			<name id="0-802"/>
			<comment id="0-803"/>
			<p-name>SCPTsmokeDayPreAlrmLim</p-name>
			<formats>
				<format id="SCPTsmokeDayPreAlrmLim">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsmokeNightAlrmLim" idx="127" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_smo_obscur</ref>
			<name id="0-780"/>
			<comment id="0-781"/>
			<p-name>SCPTsmokeNightAlrmLim</p-name>
			<formats>
				<format id="SCPTsmokeNightAlrmLim">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsmokeNightPreAlrmLim" idx="140" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_smo_obscur</ref>
			<name id="0-806"/>
			<comment id="0-807"/>
			<p-name>SCPTsmokeNightPreAlrmLim</p-name>
			<formats>
				<format id="SCPTsmokeNightPreAlrmLim">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsmokeNomSens" idx="39" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_smo_obscur</ref>
			<name id="0-659"/>
			<comment id="0-660"/>
			<p-name>SCPTsmokeNomSens</p-name>
			<formats>
				<format id="SCPTsmokeNomSens">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsndDelta" idx="27" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTsndDelta">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTairVelocitySensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTglobalSolarRadiation</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTisiLampActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpressureSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTutilityDataLoggerRegister</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTutilityMeter</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsourceAddress" idx="336" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0</default>
			<size>2</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>1</min>
							<max>255</max>
							<invalid>0</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-4004"/>
						<comment id="0-4005"/>
						<p-name>subnet</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>1</width>
							<offset>0</offset>
							<min>0</min>
							<max>0</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-4006"/>
						<comment id="0-4007"/>
						<p-name>reserved</p-name>
					</member>
					<member>
						<bitfield>
							<signed>no</signed>
							<width>7</width>
							<offset>1</offset>
							<min>0</min>
							<max>127</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</bitfield>
						<name id="0-4008"/>
						<comment id="0-4009"/>
						<p-name>node</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-4002"/>
			<comment id="0-4003"/>
			<p-name>SCPTsourceAddress</p-name>
			<formats>
				<format id="SCPTsourceAddress">text(&quot;%d %d&quot;, subnet, node)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdataLogger</ref>
			</refs>
		</cpt>
		<cpt id="SCPTspaceHumSetpoint" idx="203" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>30,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-1293"/>
			<comment id="0-1294"/>
			<p-name>SCPTspaceHumSetpoint</p-name>
			<formats>
				<format id="SCPTspaceHumSetpoint">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTdischargeAirController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTstandbyRotationalSpeed" idx="181" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_freq_hz</ref>
			<name id="0-1249"/>
			<comment id="0-1250"/>
			<p-name>SCPTstandbyRotationalSpeed</p-name>
			<formats>
				<format id="SCPTstandbyRotationalSpeed">text(&quot;%f&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTstep" idx="83" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_cont</ref>
			<name id="0-698"/>
			<comment id="0-699"/>
			<p-name>SCPTstep</p-name>
			<formats>
				<format id="SCPTstep">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTconstantLightController</ref>
			</refs>
		</cpt>
		<cpt id="SCPTstepValue" idx="92" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>2,5</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_cont</ref>
			<name id="0-714"/>
			<comment id="0-715"/>
			<p-name>SCPTstepValue</p-name>
			<formats>
				<format id="SCPTstepValue">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTscenePanel</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTswitch</ref>
			</refs>
		</cpt>
		<cpt id="SCPTstrtupDelay" idx="111" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-744"/>
			<comment id="0-745"/>
			<p-name>SCPTstrtupDelay</p-name>
			<formats>
				<format id="SCPTstrtupDelay">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerDefrost</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerEvaporator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTstrtupOpen" idx="115" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,000</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_lev_percent</ref>
			<name id="0-752"/>
			<comment id="0-753"/>
			<p-name>SCPTstrtupOpen</p-name>
			<formats>
				<format id="SCPTstrtupOpen">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerEvaporator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsummerTime" idx="99" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0-0-0T0:0:0</min>
			<max>0-12-31T23:0:0</max>
			<default>0-1-1T0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp</ref>
			<name id="0-728"/>
			<comment id="0-729"/>
			<p-name>SCPTsummerTime</p-name>
			<formats>
				<format id="SCPTsummerTime">text(&quot;%d/%d/%d %d:%d:%d&quot;,  year,  month,  day,  hour,  minute,  second)</format>
				<format id="SCPTsummerTime#LO">text(date(year, month, day), (&quot; &quot;),  time(hour,  minute,  second))</format>
				<format id="SCPTsummerTime#SI">text(&quot;%d-%d-%dT%d:%d:%d&quot;,  year,  month,  day,  hour,  minute,  second)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrealTimeKeeper</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsunriseTime" idx="377" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp</ref>
			<name id="0-5477"/>
			<comment id="0-5478"/>
			<p-name>SCPTsunriseTime</p-name>
			<formats>
				<format id="SCPTsunriseTime">text(&quot;%d %d %d %d %d %d&quot;,  year, month, day, hour, minute, second)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsunsetTime" idx="378" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp</ref>
			<name id="0-5479"/>
			<comment id="0-5480"/>
			<p-name>SCPTsunsetTime</p-name>
			<formats>
				<format id="SCPTsunsetTime">text(&quot;%d %d %d %d %d %d&quot;,  year, month, day, hour, minute, second)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTschedulerSimple</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsuperHtRefInit" idx="114" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-750"/>
			<comment id="0-751"/>
			<p-name>SCPTsuperHtRefInit</p-name>
			<formats>
				<format id="SCPTsuperHtRefInit#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTsuperHtRefInit#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerEvaporator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsuperHtRefMax" idx="118" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-758"/>
			<comment id="0-759"/>
			<p-name>SCPTsuperHtRefMax</p-name>
			<formats>
				<format id="SCPTsuperHtRefMax#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTsuperHtRefMax#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerEvaporator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTsuperHtRefMin" idx="116" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_p</ref>
			<name id="0-754"/>
			<comment id="0-755"/>
			<p-name>SCPTsuperHtRefMin</p-name>
			<formats>
				<format id="SCPTsuperHtRefMin#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTsuperHtRefMin#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerEvaporator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTtempOffset" idx="227" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_diff_p</ref>
			<name id="0-555"/>
			<comment id="0-1340"/>
			<p-name>SCPTtempOffset</p-name>
			<formats>
				<format id="SCPTtempOffset#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTtempOffset#US">text(&quot;%f&quot;, *1.8+0(0:855))</format>
			</formats>
		</cpt>
		<cpt id="SCPTtemperatureHysteresis" idx="214" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,00</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_diff_p</ref>
			<name id="0-1315"/>
			<comment id="0-1316"/>
			<p-name>SCPTtemperatureHysteresis</p-name>
			<formats>
				<format id="SCPTtemperatureHysteresis#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTtemperatureHysteresis#US">text(&quot;%f&quot;, *1.8+0(0:855))</format>
			</formats>
		</cpt>
		<cpt id="SCPTtermTimeTemp" idx="112" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>DFT_TERM_TEMP</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_defr_term</ref>
			<name id="0-746"/>
			<comment id="0-747"/>
			<p-name>SCPTtermTimeTemp</p-name>
			<formats>
				<format id="SCPTtermTimeTemp">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerDefrost</ref>
			</refs>
		</cpt>
		<cpt id="SCPTthermAlrmROR" idx="142" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp_ror</ref>
			<name id="0-811"/>
			<comment id="0-812"/>
			<p-name>SCPTthermAlrmROR</p-name>
			<formats>
				<format id="SCPTthermAlrmROR#SI">text(&quot;%f&quot;, *1+0(0:1012))</format>
				<format id="SCPTthermAlrmROR#US">text(&quot;%f&quot;, *1.8+0(0:1011))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTthermalFireInitiator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTthermMode" idx="120" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>THERM_NO_CONTROL</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_therm_mode</ref>
			<name id="0-602"/>
			<comment id="0-767"/>
			<p-name>SCPTthermMode</p-name>
			<formats>
				<format id="SCPTthermMode">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrefrigDisplayCaseControllerThermostat</ref>
			</refs>
		</cpt>
		<cpt id="SCPTthermThreshold" idx="152" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>-274,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_temp</ref>
			<name id="0-832"/>
			<comment id="0-833"/>
			<p-name>SCPTthermThreshold</p-name>
			<formats>
				<format id="SCPTthermThreshold#SI">text(&quot;%f&quot;, *1+0(0:854))</format>
				<format id="SCPTthermThreshold#US">text(&quot;%f&quot;, *1.8+32(0:855))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTthermalFireInitiator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTtimeEvent" idx="104" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>EMT_END_OF_LIST,0:0,0</default>
			<size>4</size>
			<aggregate cat="struct">
				<members>
					<member>
						<enum>
							<min>-1</min>
							<max>4</max>
							<idx>51</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">event_mode_type_t</ref>
						</enum>
						<name id="0-948"/>
						<unit id="0-949"/>
						<p-name>record_type</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>23</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-37"/>
						<unit id="0-39"/>
						<p-name>hour</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>59</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-40"/>
						<unit id="0-41"/>
						<p-name>minute</p-name>
					</member>
					<member>
						<scalar>
							<nc-type>unsigned short</nc-type>
							<min>0</min>
							<max>255</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
						</scalar>
						<name id="0-950"/>
						<unit id="0-951"/>
						<p-name>event_mode</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-945"/>
			<comment id="0-946"/>
			<unit id="0-947"/>
			<p-name>SCPTtimeEvent</p-name>
			<formats>
				<format id="SCPTtimeEvent">text(&quot;%m,%d:%d,%d&quot;,  record_type,  hour,  minute,  event_mode)</format>
				<format id="SCPTtimeEvent#LO">text((&quot;%m|&quot;, record_type), time(hour, minute), (&quot;|%d&quot;,  event_mode))</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrealTimeBasedScheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTtimePeriod" idx="291" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>IOM_MINUTE 0 </default>
			<size>2</size>
			<aggregate cat="struct">
				<members>
					<member>
						<enum>
							<min>-1</min>
							<max>4</max>
							<idx>58</idx>
							<selector>0</selector>
							<ref href="0000000000000000-0/enums.xml">interval_of_month_t</ref>
						</enum>
						<p-name>units</p-name>
					</member>
					<member>
						<aggregate cat="union">
							<members>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>1</min>
										<max>255</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<p-name>minutes_interval</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>1</min>
										<max>31</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<p-name>date_of_month</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>0</min>
										<max>23</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<p-name>hour_of_day</p-name>
								</member>
								<member>
									<enum>
										<min>-1</min>
										<max>6</max>
										<idx>1</idx>
										<selector>0</selector>
										<ref href="0000000000000000-0/enums.xml">days_of_week_t</ref>
									</enum>
									<p-name>day_of_week</p-name>
								</member>
								<member>
									<scalar>
										<nc-type>unsigned short</nc-type>
										<min>1</min>
										<max>255</max>
										<scaling>
											<a>1</a>
											<b>0</b>
											<c>0</c>
											<s>1</s>
										</scaling>
									</scalar>
									<p-name>hours_interval</p-name>
								</member>
							</members>
						</aggregate>
						<p-name>value</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-3235"/>
			<comment id="0-3236"/>
			<p-name>SCPTtimePeriod</p-name>
			<formats>
				<format id="SCPTtimePeriod">
					text((&quot;%m &quot;, units),((units == 0) ?	(&quot;%d &quot;, value.minutes_interval) :((units == 1) ? (&quot;%d &quot;, value.hours_interval) :((units == 2) ? (&quot;%d &quot;, value.hour_of_day) :((units == 3) ? (&quot;%d &quot;, value.day_of_week) :((units == 4) ? (&quot;%d &quot;, value.date_of_month) : (&quot;UNKNOWN&quot;)))))))
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTutilityMeter</ref>
			</refs>
		</cpt>
		<cpt id="SCPTtimeSource" idx="373" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>TMS_SCHEDULER_NV</default>
			<size>1</size>
			<enum>
				<min>-1</min>
				<max>4</max>
				<idx>86</idx>
				<selector>0</selector>
				<ref href="0000000000000000-0/enums.xml">time_source_t</ref>
			</enum>
			<name id="0-5467"/>
			<comment id="0-5468"/>
			<p-name>SCPTtimeSource</p-name>
			<formats>
				<format id="SCPTtimeSource">text(&quot;%m&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTtimeZone" idx="154" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 CAL_MEU 2:0:0 4 1 DAY_SUN 2:0:0 10 5 DAY_SUN</default>
			<size>15</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_zone</ref>
			<name id="0-891"/>
			<comment id="0-952"/>
			<p-name>SCPTtimeZone</p-name>
			<formats>
				<format id="SCPTtimeZone">
					text( (&quot;%d %m %d:%d:%d &quot;,second_time_offset, type_of_description,hour_of_start_DST, minute_of_start_DST,second_of_start_DST),((type_of_description == 0) ?(&quot;%d %d:%d:%d %d&quot; ,start_DST.G_day_of_start_DST,hour_of_end_DST,minute_of_end_DST,second_of_end_DST,end_DST.G_day_of_end_DST):((type_of_description == 1) ?(&quot;%d %d:%d:%d %d&quot; ,start_DST.J_day_of_start_DST,hour_of_end_DST,minute_of_end_DST,second_of_end_DST,end_DST.J_day_of_end_DST):((type_of_description == 2) ?(&quot;%d %d %m %d:%d:%d %d %d %m&quot;,start_DST.M_start_DST.month_of_start_DST,start_DST.M_start_DST.week_of_start_DST,start_DST.M_start_DST.dateday_of_start_DST,hour_of_end_DST,minute_of_end_DST,second_of_end_DST,end_DST.M_end_DST.month_of_end_DST,end_DST.M_end_DST.week_of_end_DST,end_DST.M_end_DST.dateday_of_end_DST):(&quot;UNKNOWN&quot;)))))
				</format>
				<format id="SCPTtimeZone#LO">
					text((&quot;%d %m &quot;, second_time_offset, type_of_description), time(hour_of_start_DST, minute_of_start_DST, second_of_start_DST), ((type_of_description == 0) ?((&quot; %d &quot; ,start_DST.G_day_of_start_DST), time(hour_of_end_DST, minute_of_end_DST, second_of_end_DST), (&quot; %d&quot;, end_DST.G_day_of_end_DST)) :((type_of_description == 1) ?((&quot; %d &quot;, start_DST.J_day_of_start_DST), time(hour_of_end_DST, minute_of_end_DST, second_of_end_DST), (&quot; %d&quot;, end_DST.J_day_of_end_DST)) :((type_of_description == 2) ?((&quot; %d %d %m &quot;, start_DST.M_start_DST.month_of_start_DST, start_DST.M_start_DST.week_of_start_DST, start_DST.M_start_DST.dateday_of_start_DST), time(hour_of_end_DST,minute_of_end_DST,second_of_end_DST), (&quot; %d %d %m&quot;,end_DST.M_end_DST.month_of_end_DST, end_DST.M_end_DST.week_of_end_DST, end_DST.M_end_DST.dateday_of_end_DST)) :(&quot;UNKNOWN&quot;)))))
				</format>
			</formats>
		</cpt>
		<cpt id="SCPTtimeout" idx="170" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-1227"/>
			<comment id="0-1228"/>
			<p-name>SCPTtimeout</p-name>
			<formats>
				<format id="SCPTtimeout">text(&quot;%f&quot;)</format>
			</formats>
		</cpt>
		<cpt id="SCPTtrnsTblX" idx="28" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0 0 0 0 0 0 0 0 0</default>
			<size>30</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_trans_table</ref>
			<name id="0-456"/>
			<comment id="0-457"/>
			<p-name>SCPTtrnsTblX</p-name>
			<formats>
				<format id="SCPTtrnsTblX">
					text(&quot;%f %f %f %f %f %f %f %d %d %d %d %d %d %d&quot;, point[0],  point[1],  point[2],  point[3],  point[4], point[5],  point[6],  interp_pts_0_to_1, interp_pts_1_to_2,  interp_pts_2_to_3,  interp_pts_3_to_4, interp_pts_4_to_5,  interp_pts_5_to_6,  interp_pts_6_to_0)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTtrnsTblX2" idx="285" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0 0 0 0 0 0 0 0 0</default>
			<size>30</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_trans_table</ref>
			<name id="0-3213"/>
			<comment id="0-3214"/>
			<p-name>SCPTtrnsTblX2</p-name>
			<formats>
				<format id="SCPTtrnsTblX2">
					text(&quot;%f %f %f %f %f %f %f %d %d %d %d %d %d %d&quot;,  point[0], point[1], point[2], point[3], point[4], point[5], point[6], interp_pts_0_to_1, interp_pts_1_to_2, interp_pts_2_to_3, interp_pts_3_to_4, interp_pts_4_to_5, interp_pts_5_to_6, interp_pts_6_to_0)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTtrnsTblX3" idx="288" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0 0 0 0 0 0 0 0 0</default>
			<size>30</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_trans_table</ref>
			<name id="0-3219"/>
			<comment id="0-3220"/>
			<p-name>SCPTtrnsTblX3</p-name>
			<formats>
				<format id="SCPTtrnsTblX3">
					text(&quot;%f %f %f %f %f %f %f %d %d %d %d %d %d %d&quot;,  point[0], point[1], point[2], point[3], point[4], point[5], point[6], interp_pts_0_to_1, interp_pts_1_to_2, interp_pts_2_to_3, interp_pts_3_to_4, interp_pts_4_to_5, interp_pts_5_to_6, interp_pts_6_to_0)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTtrnsTblY" idx="29" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0 0 0 0 0 0 0 0 0</default>
			<size>30</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_trans_table</ref>
			<name id="0-458"/>
			<comment id="0-459"/>
			<p-name>SCPTtrnsTblY</p-name>
			<formats>
				<format id="SCPTtrnsTblY">
					text(&quot;%f %f %f %f %f %f %f %d %d %d %d %d %d %d&quot;, point[0],  point[1],  point[2],  point[3],  point[4], point[5],  point[6],  interp_pts_0_to_1, interp_pts_1_to_2,  interp_pts_2_to_3,  interp_pts_3_to_4, interp_pts_4_to_5,  interp_pts_5_to_6,  interp_pts_6_to_0)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTclosedLoopSensor</ref>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTopenLoopSensor</ref>
			</refs>
		</cpt>
		<cpt id="SCPTtrnsTblY2" idx="286" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0 0 0 0 0 0 0 0 0</default>
			<size>30</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_trans_table</ref>
			<name id="0-3215"/>
			<comment id="0-3216"/>
			<p-name>SCPTtrnsTblY2</p-name>
			<formats>
				<format id="SCPTtrnsTblY2">
					text(&quot;%f %f %f %f %f %f %f %d %d %d %d %d %d %d&quot;,  point[0], point[1], point[2], point[3], point[4], point[5], point[6], interp_pts_0_to_1, interp_pts_1_to_2, interp_pts_2_to_3, interp_pts_3_to_4, interp_pts_4_to_5, interp_pts_5_to_6, interp_pts_6_to_0)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTtrnsTblY3" idx="289" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0 0 0 0 0 0 0 0 0 0 0 0 0 0</default>
			<size>30</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_trans_table</ref>
			<name id="0-3221"/>
			<comment id="0-3222"/>
			<p-name>SCPTtrnsTblY3</p-name>
			<formats>
				<format id="SCPTtrnsTblY3">
					text(&quot;%f %f %f %f %f %f %f %d %d %d %d %d %d %d&quot;,  point[0], point[1], point[2], point[3], point[4], point[5], point[6], interp_pts_0_to_1, interp_pts_1_to_2, interp_pts_2_to_3, interp_pts_3_to_4, interp_pts_4_to_5, interp_pts_5_to_6, interp_pts_6_to_0)
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTupdateRate" idx="98" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>60,0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_sec</ref>
			<name id="0-726"/>
			<comment id="0-727"/>
			<p-name>SCPTupdateRate</p-name>
			<formats>
				<format id="SCPTupdateRate">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrealTimeKeeper</ref>
			</refs>
		</cpt>
		<cpt id="SCPTvalueDefinition" idx="276" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*4</default>
			<inheriting>yes</inheriting>
			<formats>
				<format id="SCPTvalueDefinition">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTvalueName" idx="277" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>00*22</default>
			<size>22</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned char</nc-type>
							<min>32</min>
							<max>126</max>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
							<array-size>22</array-size>
						</scalar>
						<name id="0-2519"/>
						<comment id="0-2520"/>
						<unit id="0-2380"/>
						<p-name>name</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-2517"/>
			<comment id="0-2518"/>
			<p-name>SCPTvalueName</p-name>
			<formats>
				<format id="SCPTvalueName">
					text(&quot;%c %c %c %c %c %c %c %c %c %c %c %c %c %c %c %c %c %c %c %c %c %c&quot;, name[0],   name[1],   name[2],   name[3],   name[4], name[5],   name[6],   name[7],   name[8],   name[9], name[10],  name[11],  name[12],  name[13],  name[14], name[15],  name[16],  name[17],  name[18],  name[19], name[20],  name[21])
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTvalveFlowCharacteristic" idx="248" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>DCM_QUICK_OPEN</min>
			<max>DCM_FREE_DEFINED</max>
			<default>DCM_QUICK_OPEN</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_dev_c_mode</ref>
			<name id="0-1388"/>
			<comment id="0-1389"/>
			<p-name>SCPTvalveFlowCharacteristic</p-name>
			<formats>
				<format id="SCPTvalveFlowCharacteristic">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTvalveKvs" idx="282" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_flow_p</ref>
			<name id="0-3207"/>
			<comment id="0-3208"/>
			<p-name>SCPTvalveKvs</p-name>
			<formats>
				<format id="SCPTvalveKvs">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTvalveNominalSize" idx="281" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_length_mil</ref>
			<name id="0-3205"/>
			<comment id="0-3206"/>
			<p-name>SCPTvalveNominalSize</p-name>
			<formats>
				<format id="SCPTvalveNominalSize">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTvalveOperatingMode" idx="249" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>VALVE_NORMAL</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_valve_mode</ref>
			<name id="0-1390"/>
			<comment id="0-1391"/>
			<p-name>SCPTvalveOperatingMode</p-name>
			<formats>
				<format id="SCPTvalveOperatingMode">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTvalveStroke" idx="280" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_length_mil</ref>
			<name id="0-3203"/>
			<comment id="0-3204"/>
			<p-name>SCPTvalveStroke</p-name>
			<formats>
				<format id="SCPTvalveStroke">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTvalveType" idx="283" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>DCM_INVFNC_QCK_OPN</min>
			<max>DCM_INVFNC_QUAD</max>
			<default>0</default>
			<size>1</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_dev_c_mode</ref>
			<name id="0-3209"/>
			<comment id="0-3210"/>
			<p-name>SCPTvalveType</p-name>
			<formats>
				<format id="SCPTvalveType">text(&quot;%m&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPThvacValvePositioner</ref>
			</refs>
		</cpt>
		<cpt id="SCPTvisOutput" idx="143" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0,0</default>
			<size>2</size>
			<scalar>
				<nc-type>unsigned long</nc-type>
				<min>0</min>
				<max>10000</max>
				<invalid>65535</invalid>
				<scaling>
					<a>1</a>
					<b>-1</b>
					<c>0</c>
					<s>0.10000000149012</s>
				</scaling>
			</scalar>
			<name id="0-813"/>
			<comment id="0-814"/>
			<unit id="0-815"/>
			<p-name>SCPTvisOutput</p-name>
			<formats>
				<format id="SCPTvisOutput">text(&quot;%f&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTvisibleFireIndicator</ref>
			</refs>
		</cpt>
		<cpt id="SCPTweeklySchedule" idx="278" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>65535 65535 65535 65535 65535 65535 65535</default>
			<size>14</size>
			<aggregate cat="struct">
				<members>
					<member>
						<scalar>
							<nc-type>unsigned long</nc-type>
							<min>0</min>
							<max>65535</max>
							<invalid>65535</invalid>
							<scaling>
								<a>1</a>
								<b>0</b>
								<c>0</c>
								<s>1</s>
							</scaling>
							<array-size>7</array-size>
						</scalar>
						<name id="0-2523"/>
						<comment id="0-2505"/>
						<p-name>schedule_index</p-name>
					</member>
				</members>
			</aggregate>
			<name id="0-2521"/>
			<comment id="0-2522"/>
			<p-name>SCPTweeklySchedule</p-name>
			<formats>
				<format id="SCPTweeklySchedule">
					text(&quot;%d %d %d %d %d %d %d&quot;, schedule_index[0],  schedule_index[1], schedule_index[2],  schedule_index[3], schedule_index[4],  schedule_index[5], schedule_index[6])
				</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTscheduler</ref>
			</refs>
		</cpt>
		<cpt id="SCPTwinterTime" idx="100" stlp_std="yes">
			<obsolete>no</obsolete>
			<min>0-0-0T0:0:0</min>
			<max>0-12-31T23:0:0</max>
			<default>0-1-1T0:0:0</default>
			<size>7</size>
			<ref href="0000000000000000-0/nvs.xml">SNVT_time_stamp</ref>
			<name id="0-730"/>
			<comment id="0-731"/>
			<p-name>SCPTwinterTime</p-name>
			<formats>
				<format id="SCPTwinterTime">text(&quot;%d/%d/%d %d:%d:%d&quot;,  year,  month,  day,  hour,  minute,  second)</format>
				<format id="SCPTwinterTime#LO">text(date(year, month, day), (&quot; &quot;),  time(hour,  minute,  second))</format>
				<format id="SCPTwinterTime#SI">text(&quot;%d-%d-%dT%d:%d:%d&quot;,  year,  month,  day,  hour,  minute,  second)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTrealTimeKeeper</ref>
			</refs>
		</cpt>
		<cpt id="SCPTzoneNum" idx="141" stlp_std="yes">
			<obsolete>no</obsolete>
			<default>0</default>
			<size>2</size>
			<scalar>
				<nc-type>unsigned long</nc-type>
				<min>0</min>
				<max>65535</max>
				<invalid>65535</invalid>
				<scaling>
					<a>1</a>
					<b>0</b>
					<c>0</c>
					<s>1</s>
				</scaling>
			</scalar>
			<name id="0-808"/>
			<comment id="0-809"/>
			<unit id="0-810"/>
			<p-name>SCPTzoneNum</p-name>
			<formats>
				<format id="SCPTzoneNum">text(&quot;%d&quot;)</format>
			</formats>
			<refs>
				<ref href="0000000000000000-0/fps.xml">SFPTaudibleFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTelevatorFireSystemsPort</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTfireSmokeDamperActuator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTpullStationFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorConvent</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTsmokeFireInitiatorIntelli</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTthermalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireIndicator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTuniversalFireInitiator</ref>
				<ref href="0000000000000000-0/fps.xml">SFPTvisibleFireIndicator</ref>
			</refs>
		</cpt>
	</items>
	<strings>
		<string id="0-1">
			This file is the standard type file, containing Standard Network Variable Types (SNVTs), Standard Configuration Property Types (SCPTs), and the enumeration types that support them.
		</string>
		<string id="0-2">
			This file was created and is maintained by LonMark International.  Contact us at +1-408-938-5266, at http://www.lonmark.org, or at 550 Meridian Ave, San Jose CA 95126, USA.
		</string>
		<string id="0-5020">OLC Limits Setpoints</string>
		<string id="0-5021">MIN/MAX values for the status report are set here</string>
		<string id="0-5022">Limit high current</string>
		<string id="0-5023">Limit low current</string>
		<string id="0-5024">Limit main current high</string>
		<string id="0-5025">Limit main current low</string>
		<string id="0-5026">Limit lamp voltage high</string>
		<string id="0-5027">Limit lamp voltage low</string>
		<string id="0-5028">Limit main voltage high</string>
		<string id="0-5029">Limit main voltage low</string>
		<string id="0-5030">Limit power factor low</string>
		<string id="0-5031">Limit power high</string>
		<string id="0-5032">Limit power low</string>
		<string id="0-408">Actual position feedback delay</string>
		<string id="0-409">The period for updating the feedback output when the actuator position does not match the requested position</string>
		<string id="0-3211">Actuator Characteristic</string>
		<string id="0-3212">This configuration property can be used to provide the characteristic of the actuator</string>
		<string id="0-663">Actuator label</string>
		<string id="0-975">The identification of the exact actuator type or label</string>
		<string id="0-3387">AHAM Appliance Model</string>
		<string id="0-3388">Appliance Model code as defined by the Association of Home Appliance Manufacturers</string>
		<string id="0-790">Air temperature 1 percent alarm</string>
		<string id="0-791">The weighting of the air temp 1 sensor when calculating the air temp alarm</string>
		<string id="0-778">Air temperature 1 percent day</string>
		<string id="0-779">The air temperature weighting used during day control</string>
		<string id="0-788">Air temperature 1 percent night</string>
		<string id="0-789">The air temperature weighting used during night control</string>
		<string id="0-410">Alarm clear time 1</string>
		<string id="0-411">The time period that an alarm 1 condition must not exist before it is regarded as a valid cleared alarm</string>
		<string id="0-412">Alarm clear time 2</string>
		<string id="0-508">The time period that an alarm 2 condition must not exist before it is regarded as a valid cleared alarm</string>
		<string id="0-413">Alarm output inhibit time</string>
		<string id="0-414">The time period for which alarms are inhibited after an object is enabled or the node is reset</string>
		<string id="0-415">Alarm set time 1</string>
		<string id="0-416">The time period that an alarm 1 condition must exist before it is regarded as a valid alarm</string>
		<string id="0-417">Alarm set time 2</string>
		<string id="0-418">The time period that an alarm 2 condition must exist before it is regarded as a valid alarm</string>
		<string id="0-2233">Heating duct area</string>
		<string id="0-2234">Nominal cross-sectional airflow area of the hot or ventilation deck of a dual duct VAV terminal unit</string>
		<string id="0-816">Audible sound output intensity</string>
		<string id="0-817">Audible sound output intensity specification of the device at 1 meter distant</string>
		<string id="0-1341">Audible level</string>
		<string id="0-1342">The audible level output of the device</string>
		<string id="0-1241">Auto answer</string>
		<string id="0-1242">Enable the automatic call answer function of a device</string>
		<string id="0-153">boolean</string>
		<string id="0-1030">Base value</string>
		<string id="0-1031">The base value (where to begin counting)</string>
		<string id="0-5011">Backup Schedule</string>
		<string id="0-5012">Hour ON</string>
		<string id="0-5013">Time when the luminare will be switched ON in case of communication failure</string>
		<string id="0-96">Hours</string>
		<string id="0-5014">Minute ON</string>
		<string id="0-5015">Time when the luminare will be switched ON in case of communication failure</string>
		<string id="0-97">Minutes</string>
		<string id="0-5016">Hour OFF</string>
		<string id="0-5017">Time when the luminare will be switched OFF in case of communication failure</string>
		<string id="0-5018">Minute OFF</string>
		<string id="0-5019">Time when the luminare will be switched OFF in case of communication failure</string>
		<string id="0-40">Minute</string>
		<string id="0-1394">Minimum time for movement</string>
		<string id="0-1395">The minimum time in hours for movement to prevent blocking</string>
		<string id="0-1345">Brightness output</string>
		<string id="0-1346">The brightness output of a display device</string>
		<string id="0-1273">Building static pressure</string>
		<string id="0-1274">Setpoint for the default static pressure for the building</string>
		<string id="0-3689">Button color.</string>
		<string id="0-3690">
			Button color configuration for on and off states of a button. May be used to create an array that is used with a SCPTbuttonAction array to specify keypad button behavior.
		</string>
		<string id="0-3691">On color.</string>
		<string id="0-3692">RGB color for the on state.</string>
		<string id="0-3693">Red.</string>
		<string id="0-3694">Red level component of the on state color</string>
		<string id="0-3695">Green.</string>
		<string id="0-3696">Green level component of the on state color</string>
		<string id="0-3697">Blue.</string>
		<string id="0-3698">Blue level component of the on state color</string>
		<string id="0-3699">Off color.</string>
		<string id="0-3700">RGB color for the off state</string>
		<string id="0-3701">Red level component of the off state color</string>
		<string id="0-3702">Green level component of the off state color</string>
		<string id="0-3703">Blue level component of the off state color</string>
		<string id="0-3677">Button held action.</string>
		<string id="0-3678">Button action definition used to create a button held action array, with an entry per button.</string>
		<string id="0-3679">Button action.</string>
		<string id="0-3680">Button action for the associated button</string>
		<string id="0-3681">Value.</string>
		<string id="0-3682">Value for button actions that require a numeric value.</string>
		<string id="0-3683">Scene number.</string>
		<string id="0-3684">Specified scene number for the toggle and set scene actions.</string>
		<string id="0-4138">Group number</string>
		<string id="0-4139">Specified group number for the toggle, enable, and disable group actions.</string>
		<string id="0-3685">Setting.</string>
		<string id="0-3686">
			Setting level. Specifies an absoloute level for the Set Level action. Specifies a relative level for the Increase, Decrease, Move Open, Move Closed, Rotate Open, and Rotate Closed actions.
		</string>
		<string id="0-375">degrees</string>
		<string id="0-3704">Button pressed action.</string>
		<string id="0-3705">
			Button action definition used to create a button pressed action array, with an entry per button. This SCPT defines the minimum entries required by the ISI profiles.
		</string>
		<string id="0-3687">Button repeat interval</string>
		<string id="0-3688">
			Time between updates when a button is held down. The updates themselves may be throttled by the application or a SCPTminSendTime CP. Used to create an array used with a SCPTbuttonAction CP array.
		</string>
		<string id="0-100">milliseconds</string>
		<string id="0-650">Bypass time</string>
		<string id="0-651">The maximum amount of time that the controller can be in the bypass (occupancy) mode following the last bypass request. Zero disables the timer.</string>
		<string id="0-702">Controller off delay</string>
		<string id="0-703">The delay after which the controller output is switched off</string>
		<string id="0-704">Controller on delay</string>
		<string id="0-705">The delay after which the controller output is switched on</string>
		<string id="0-3385">Clock Calibration</string>
		<string id="0-3332">Corrects clock-cycle variations</string>
		<string id="0-3333">milliseconds per hour</string>
		<string id="0-3217">Combination-Flow Characteristic</string>
		<string id="0-3218">This configuration property can be used to provide the desired system control flow characteristic</string>
		<string id="0-1229">Control priority</string>
		<string id="0-1230">Priority of a control input or output, lower values mean higher priority</string>
		<string id="0-890">priority value</string>
		<string id="0-1377">Control signal</string>
		<string id="0-1378">Start and end points (X,Y) for a transition</string>
		<string id="0-1379">X1, Y1, X2, Y2</string>
		<string id="0-1380">X1</string>
		<string id="0-1381">Y1</string>
		<string id="0-1382">X2</string>
		<string id="0-1383">Y2</string>
		<string id="0-1317">Temperature weighting</string>
		<string id="0-1318">Weighting between two temperatures in percent</string>
		<string id="0-690">Cooling setpoint lower limit</string>
		<string id="0-993">Limits the lower extent of the permitted range for the cooling setpoint</string>
		<string id="0-689">Cooling setpoint</string>
		<string id="0-992">The default setpoint for the leaving chilled water temperature in cooling mode when the default behavior selector is set to zero</string>
		<string id="0-691">Cooling setpoint upper limit</string>
		<string id="0-994">Limits the upper extent of the permitted range for the cooling setpoint</string>
		<string id="0-1305">Cooling lockout</string>
		<string id="0-1306">Setpoint for the outdoor air temperature at which cooling will be disabled</string>
		<string id="0-1309">Cooling reset enable</string>
		<string id="0-1310">The cooling reset control is enabled</string>
		<string id="0-5181">Current sense enable</string>
		<string id="0-5182">Enables current sensing for manual load control</string>
		<string id="0-776">Cut-out value</string>
		<string id="0-777">The cut-out limit</string>
		<string id="0-934">Day date index</string>
		<string id="0-935">One or two dates for matching with a start index to the time-event array</string>
		<string id="0-936">First day and month, second day and month, time-event index</string>
		<string id="0-937">First day</string>
		<string id="0-955">Day of month</string>
		<string id="0-32">days</string>
		<string id="0-939">First month</string>
		<string id="0-956">Month of year</string>
		<string id="0-30">months</string>
		<string id="0-941">Second day</string>
		<string id="0-938">Day of month, zero for no date entry</string>
		<string id="0-942">Second month</string>
		<string id="0-940">Month of year, zero for no date entry</string>
		<string id="0-943">Event index</string>
		<string id="0-944">Time-event array index</string>
		<string id="0-933">index</string>
		<string id="0-768">Day/night control</string>
		<string id="0-769">Configures the day/night function</string>
		<string id="0-804">Debounce time</string>
		<string id="0-805">The debouncing time to generate the detection envelope</string>
		<string id="0-1052">Default speed scale</string>
		<string id="0-1053">Default value for the speed scale</string>
		<string id="0-927">Definition week mask</string>
		<string id="0-928">Day type definition for every day of the week</string>
		<string id="0-929">Start index array</string>
		<string id="0-930">array of 7 index values</string>
		<string id="0-1239">Default auto-pan speed</string>
		<string id="0-1240">The default auto-pan speed for a device</string>
		<string id="0-56">% of full level</string>
		<string id="0-1237">Default camera PTZ</string>
		<string id="0-1238">The default camera pan, tilt, and zoom speeds</string>
		<string id="0-3355">default Setting</string>
		<string id="0-3372">Default Security State</string>
		<string id="0-3373">Provides the default security state upon power cycle or non-detection</string>
		<string id="0-686">Default behavior</string>
		<string id="0-988">Selects which set of values will be used on power-up and communication failure, between the stated default values (0), or manufacturer-specified values (1)</string>
		<string id="0-1325">Defrost cycles</string>
		<string id="0-1326">Number of equally-spaced defrost cycles to perform per day</string>
		<string id="0-20">units</string>
		<string id="0-1336">Defrost detect temperature differential</string>
		<string id="0-1337">Temperature differential of coil refrigerant temperature above discharge air temperature that indicates defrost</string>
		<string id="0-1330">Fan delay after defrost</string>
		<string id="0-1331">Delay after refrigeration is resumed after defrost before fan is started</string>
		<string id="0-1334">Defrost hold on sync</string>
		<string id="0-1335">Enable hold in defrost mode until synchronization signal goes away</string>
		<string id="0-1321">Defrost internal schedule</string>
		<string id="0-1322">Enable the internal scheduling of defrost</string>
		<string id="0-604">Defrost mode</string>
		<string id="0-736">The type of defrost to perform</string>
		<string id="0-1332">Defrost recovery time</string>
		<string id="0-1333">Time allowed after defrost finishes for temperature to be within normal limits</string>
		<string id="0-1323">Defrost start time</string>
		<string id="0-1324">Start time for the first daily defrost</string>
		<string id="0-722">Delay time, default to scene</string>
		<string id="0-723">The delay time, default to scene</string>
		<string id="0-794">Delta night</string>
		<string id="0-795">The value to be added to the cut-out value to get the cut-out limit during night control</string>
		<string id="0-3645">Device list entry description.</string>
		<string id="0-3646">Human readable description for an entry in the device list</string>
		<string id="0-3647">Device list entry.</string>
		<string id="0-3648">Device list entry containing the address of the device to be monitored</string>
		<string id="0-3649">Device address as subnet/node address.</string>
		<string id="0-3650">This structure is filled out in case the device address is given as subnet/node address</string>
		<string id="0-3653">Destination subnet.</string>
		<string id="0-3654">Specifies the destination subnet number (1-255)</string>
		<string id="0-3655">Unused.</string>
		<string id="0-3656">Set to 0</string>
		<string id="0-3657">Destination node.</string>
		<string id="0-3658">Specifies the destination node number (1-127)</string>
		<string id="0-3659">Device address as unique node ID address.</string>
		<string id="0-3660">This structure is filled out in case the device address is given as unique node ID address</string>
		<string id="0-3661">Destination subnet.</string>
		<string id="0-3662">Specifies the destination subnet number (1-255) or 0 if the destination subnet is unknown</string>
		<string id="0-1032">Device major version number</string>
		<string id="0-1033">The major version number for the device</string>
		<string id="0-1034">Device minor version number</string>
		<string id="0-1035">The minor version number for the device</string>
		<string id="0-1196">Device control mode</string>
		<string id="0-1364">Normal default operating device control mode</string>
		<string id="0-1231">Group ID</string>
		<string id="0-1232">A logical group control ID for the device</string>
		<string id="0-1097">ID number</string>
		<string id="0-4954">Device Output Selection</string>
		<string id="0-4955">This selectes the Output which will be used on an OLC</string>
		<string id="0-1243">Dial string</string>
		<string id="0-1244">Telephone number string used in dialing, including characters used for control</string>
		<string id="0-770">Difference night</string>
		<string id="0-771">The value to be added to the cut-out value to get the cut-in limit during night control</string>
		<string id="0-1289">Differential temperature</string>
		<string id="0-1290">Setpoint for differential temperature for economizer enable</string>
		<string id="0-786">Difference value</string>
		<string id="0-787">The value to be added to the cut-out value to get the cut-in limit</string>
		<string id="0-666">Direction / Safety position</string>
		<string id="0-976">The actuator sense of rotation and safety position; bit 0 set =&gt; counterclockwise, bit 1 set =&gt; damper open</string>
		<string id="0-1253">Discharge air cooling setpoint</string>
		<string id="0-1254">Default cooling setpoint for discharge air</string>
		<string id="0-1295">Discharge air dewpoint</string>
		<string id="0-1296">Setpoint for the default discharge air dewpoint</string>
		<string id="0-1255">Discharge air heating setpoint</string>
		<string id="0-1256">Default heating setpoint for discharge air</string>
		<string id="0-739">Drain delay</string>
		<string id="0-740">The delay to use after the defrost has terminated</string>
		<string id="0-422">Drive time</string>
		<string id="0-423">Time to be taken by the actuator to move from one extreme to the other</string>
		<string id="0-977">The transition time for a full 100% stroke (change from one extreme to the other)</string>
		<string id="0-667">Duct area or size</string>
		<string id="0-978">The duct area used to calculate the air flow, relevant only for VAV actuators / controllers</string>
		<string id="0-1271">Duct static pressure limit</string>
		<string id="0-1272">The duct static pressure limit for equipment protection</string>
		<string id="0-1265">Duct static pressure</string>
		<string id="0-1266">Setpoint for default duct static pressure</string>
		<string id="0-2467">Effective period</string>
		<string id="0-2468">Time period during which a functional block is effective.</string>
		<string id="0-2469">Starting date</string>
		<string id="0-2470">Starting date of the effective period</string>
		<string id="0-26">Year</string>
		<string id="0-2471">Starting year</string>
		<string id="0-29">Month</string>
		<string id="0-2472">Starting month</string>
		<string id="0-31">Day</string>
		<string id="0-2473">Starting day</string>
		<string id="0-2474">Ending date</string>
		<string id="0-2475">Ending date of the effective period</string>
		<string id="0-2476">Ending year</string>
		<string id="0-2477">Ending year of the effective period</string>
		<string id="0-2478">Ending month</string>
		<string id="0-2479">Ending month of the effective period</string>
		<string id="0-2480">Ending day</string>
		<string id="0-2481">Ending day of the effective period</string>
		<string id="0-1392">Emergency position</string>
		<string id="0-1393">Position in percent of full scale (open) for emergency operation</string>
		<string id="0-5090">Enable Status Message</string>
		<string id="0-5034">Lamp current high</string>
		<string id="0-5035">Lamp current low</string>
		<string id="0-5036">Main current high</string>
		<string id="0-5037">Main current low</string>
		<string id="0-5038">Lamp voltage high (DALI Bit5)</string>
		<string id="0-5039">Lamp voltage low (DALI Bit5)</string>
		<string id="0-5040">Main voltage high</string>
		<string id="0-5041">Main voltage low</string>
		<string id="0-5042">Power factor low</string>
		<string id="0-5043">Temperature high (DALI Bit 4)</string>
		<string id="0-5044">Power high</string>
		<string id="0-5045">Power low</string>
		<string id="0-5046">Relay failure</string>
		<string id="0-5047">Capacity failure (DALI Bit 7)</string>
		<string id="0-5048">Lamp failure (DALI Bit 6)</string>
		<string id="0-5049">Ballast failure</string>
		<string id="0-5050">Internal communiction failure</string>
		<string id="0-5051">External communication failure</string>
		<string id="0-5052">Main voltage below performance specification (DALI Bit 1)</string>
		<string id="0-5053">Lamp restart retry counter / cycling failure (DALI Bit 2)</string>
		<string id="0-5054">Fading ready (DALI Bit 3)</string>
		<string id="0-5055">Ballast temperature too high</string>
		<string id="0-5056">digital input A active</string>
		<string id="0-5057">digital input B active</string>
		<string id="0-5058">Reserve</string>
		<string id="0-800">Energy counter initialization</string>
		<string id="0-801">The initial value of the energy counter for the associated network variable</string>
		<string id="0-1291">Exhaust enable position</string>
		<string id="0-1292">Setpoint for the exhaust-enable outdoor air damper position</string>
		<string id="0-720">Fade time, default to scene</string>
		<string id="0-721">The desired time to fade to zero</string>
		<string id="0-1277">Fan differential</string>
		<string id="0-1278">Setpoint for the percent capacity differential between the supply and return fans</string>
		<string id="0-3985">Fan-in enable.</string>
		<string id="0-3986">
			Enables fan-in of multiple data sources. When True, the application examines the source address of each input value and uses it to determine the data source of the update.
		</string>
		<string id="0-2222">Fan operation</string>
		<string id="0-710">Field calibration</string>
		<string id="0-711">Used by the light sensor to self calibrate the hardware</string>
		<string id="0-888">Fire indicator device type</string>
		<string id="0-889">Describes the fire indicator device</string>
		<string id="0-887">Fire initiator type identifier</string>
		<string id="0-658">The fire initiator type identifier, entered into the device at installation and/or configuration time</string>
		<string id="0-826">Fire text information</string>
		<string id="0-827">Text information relevant to fire conditions. A &apos;&gt;&apos; at end of string indicates presence of fire text 2.</string>
		<string id="0-828">Fire text information, continuation</string>
		<string id="0-829">Continuation text information relevant to fire conditions. A &apos;&gt;&apos; at end of string indicates presence of fire text 3.</string>
		<string id="0-830">Fire text information, second continuation</string>
		<string id="0-831">Second continuation text information relevant to fire conditions</string>
		<string id="0-818">Flash rate specification</string>
		<string id="0-819">Flash rate specification for visible indication (strobe) device</string>
		<string id="0-1386">Free cooling valve position</string>
		<string id="0-1387">Valve position in percent open for free cooling HVAC mode</string>
		<string id="0-462">Gain</string>
		<string id="0-463">This parameter is used to calibrate the external hardware.</string>
		<string id="0-684">VAV gain</string>
		<string id="0-987">The gain of the VAV controller object</string>
		<string id="0-685">VAV sensor constant</string>
		<string id="0-1010">Calibration constant used to calculate airflow</string>
		<string id="0-5060">Geographic Location</string>
		<string id="0-693">Heating setpoint lower limit</string>
		<string id="0-996">Limits the lower extent of the permitted range for the heating setpoint</string>
		<string id="0-692">Heating setpoint</string>
		<string id="0-995">The default setpoint for the leaving water temperature in heating mode when the default behavior selector is set to zero</string>
		<string id="0-694">Heating setpoint upper limit</string>
		<string id="0-997">Limits the upper extent of the permitted range for the heating setpoint</string>
		<string id="0-1307">Heating lockout</string>
		<string id="0-1308">Setpoint for the outdoor air temperature at which heating will be disabled</string>
		<string id="0-1311">Heating reset enable</string>
		<string id="0-1312">The heating reset control is enabled</string>
		<string id="0-792">High limit defrost delay</string>
		<string id="0-793">The time limit before high air temp alarm during pull-down</string>
		<string id="0-774">High limit delay</string>
		<string id="0-775">The time limit during normal operation before the alarm air temp high alarm is recognized</string>
		<string id="0-772">High limit temperature</string>
		<string id="0-773">The high alarm set point for the alarm air temp network variable</string>
		<string id="0-3383">High limit 1 Enable</string>
		<string id="0-3328">Controls whether high limit 1 is in effect</string>
		<string id="0-3384">High limit 2 Enable</string>
		<string id="0-3329">Controls whether high limit 2 is in effect</string>
		<string id="0-712">Hold time</string>
		<string id="0-713">Hold time for occupied state after there is no occupancy detected</string>
		<string id="0-654">Humidity high limit setpoint</string>
		<string id="0-655">High limit humidity setpoint for the controlled space. A zero value disables</string>
		<string id="0-383">HVAC mode</string>
		<string id="0-991">The default operating mode of the device when the default behavior selector is set to zero</string>
		<string id="0-1056">HVAC unit type</string>
		<string id="0-1058">The type of HVAC equipment being controlled</string>
		<string id="0-3370">Sensor Identity</string>
		<string id="0-3371">A number from 0 to 65535 identifying a sensor by number</string>
		<string id="0-3639">Interface description.</string>
		<string id="0-3640">Human readable description of the interface the functional block is assigned to</string>
		<string id="0-436">Input value feedback delay</string>
		<string id="0-437">The time period after the last update in a succession of changes to the input, before the feedback output is updated</string>
		<string id="0-741">Injection delay</string>
		<string id="0-820">Installation date</string>
		<string id="0-821">The date of installation for the device</string>
		<string id="0-1349">Installed level</string>
		<string id="0-1350">The floor or level on which the device is installed</string>
		<string id="0-1351">floor number</string>
		<string id="0-438">Invert output</string>
		<string id="0-439">This parameter indicates to invert the active polarity, if the value is nonzero (ON).</string>
		<string id="0-5033">Lamp Power</string>
		<string id="0-4140">Lighting group enable</string>
		<string id="0-4141">Bit masks to enable or disable up to 64 ISI lighting groups.  Group 0 is not used.  Groups may also be enabled or disabled using a SNVT_switch_2 update.</string>
		<string id="0-5186">Lighting group membership</string>
		<string id="0-5187">Bit masks to specify membership in up to 64 ISI lighting groups. Group 0 is not used.</string>
		<string id="0-664">CO2 limit</string>
		<string id="0-1005">CO2 threshold limit, controller to maintain concentration below this limit</string>
		<string id="0-695">Chiller capacity limit</string>
		<string id="0-998">The default value for the capacity limit of the chiller when the default behavior selector is set to zero</string>
		<string id="0-3643">Link Power Detection Enabled.</string>
		<string id="0-3644">Determines, whether link power detection is enabled. If yes, nvoLinkPower indicates existence of link power voltage.</string>
		<string id="0-5204">Load control offsets</string>
		<string id="0-5205">Offsets to be used during standby (unoccupied state but home, or sleep mode) and demand-response modes</string>
		<string id="0-5206">percent</string>
		<string id="0-274">Location</string>
		<string id="0-440">Provides descriptive physical location information related to the object.</string>
		<string id="0-4055">Data log alarm threshold.</string>
		<string id="0-4056">Specifies the log level required to trigger an alarm condition for the data logger.</string>
		<string id="0-4057">percent</string>
		<string id="0-3976">Data log capacity</string>
		<string id="0-3977">Specifies the total capacity of all data logs on a device. The size of each data log is specified by its cpLogSize value. The value is specified in bytes.</string>
		<string id="0-176">bytes</string>
		<string id="0-4043">Data log header.</string>
		<string id="0-4044">Describes contents of a data log.</string>
		<string id="0-4045">Data log file type.</string>
		<string id="0-4046">Constant identifying a data log.</string>
		<string id="0-4047">Data log file format major version number.</string>
		<string id="0-4048">Data log minor version number.</string>
		<string id="0-4049">Data log number.</string>
		<string id="0-4050">Index of the data log functional block that received this update.</string>
		<string id="0-4051">Data log record count.</string>
		<string id="0-4052">Number of records in data log.</string>
		<string id="0-43">seconds</string>
		<string id="0-4053">Data log start time.</string>
		<string id="0-4054">Data log end time.</string>
		<string id="0-3996">Data log minimum delta time.</string>
		<string id="0-3997">
			Minimum amount of time between logged values. This is used to throttle data entry into a data log. When a data value is logged, a subsequent update to the data value is not logged until the time specified by this value has elapsed. If additional updates are received during this time, the older values are discarded and are not stored in the data log. Time of receipt is ignored if the value of this configuration property is zero or invalid.
		</string>
		<string id="0-3978">Data log notification threshold.</string>
		<string id="0-3979">Specifies the percentage change in log level required to trigger an update to the Data Log Status (nvoStatus) output.</string>
		<string id="0-3980">percent</string>
		<string id="0-4010">Log record.</string>
		<string id="0-4011">Documents the format of a data log record. Not used as a CP. Data logs have variable sized records--unused fields are not present.</string>
		<string id="0-4012">Timestamp type.</string>
		<string id="0-4013">Specifies whether or not a timestamp is included, and if it is incljuded, specifies the format of the timestamp. Contents defined by timestamp_t.</string>
		<string id="0-4014">Log record type.</string>
		<string id="0-4015">Specifies the format of a data log record. Contents defined by log_record_t.</string>
		<string id="0-4016">Multiple tnput NV flag.</string>
		<string id="0-4017">Set to 1 if the functional block has multiple input NVs.</string>
		<string id="0-4018">Data log fan-in flag.</string>
		<string id="0-4019">Set to one if this input NV receives data from multiple data sources.</string>
		<string id="0-4020">Data log point status flag.</string>
		<string id="0-4021">Set to one if this data log record includes point status information.</string>
		<string id="0-4022">Data log record length.</string>
		<string id="0-4023">Number of bytes in the data portion of a data log record. Set to 0 if the record does not contain a data value.</string>
		<string id="0-4024">Timestamp.</string>
		<string id="0-4025">Timestamp</string>
		<string id="0-4026">Full timestamp. Only present if timestamp_type is TS_FULL.</string>
		<string id="0-4027">Offset timestamp</string>
		<string id="0-4028">Offset since last full timestamp. Only present if timestamp_type is TS_OFFSET.</string>
		<string id="0-4029">Data log member index.</string>
		<string id="0-4030">Functional block member number for the network variable input that received this update. Only present if mulitple_input is 1.</string>
		<string id="0-4031">Data log data source index.</string>
		<string id="0-4032">Index into the cpSourceAddress array. Only present if fan_in is 1.</string>
		<string id="0-4033">Data log record data.</string>
		<string id="0-4034">Data field for a data log record. Contents depend on record_type value. Unused bytes are not included.</string>
		<string id="0-4035">Data log status.</string>
		<string id="0-4036">Changed value for data log status. Only present if record_type is LR_LOG_STATUS.</string>
		<string id="0-4037">Data log data value.</string>
		<string id="0-4038">Data log value. Size depends on size logged value and is defined by data_length. Only present if record_type is LR_DATA.</string>
		<string id="0-4039">Data log old time</string>
		<string id="0-4040">Previous time after a time change. Only present if record_type is LR_TIME_CHANGE.</string>
		<string id="0-4041">Data log point status.</string>
		<string id="0-4042">Optional status for a data point value. Only present if point_status is 1.</string>
		<string id="0-4058">Data log access request.</string>
		<string id="0-4059">
			Data log access request message format. Not used as a CP. This request has a variable size--the timestamp field is only included with the get next record request.
		</string>
		<string id="0-4060">Data log access protocol version.</string>
		<string id="0-4061">Data log access protocol version number. Currently must be 1.</string>
		<string id="0-4062">Requested log number.</string>
		<string id="0-4063">The log number of the data log to be accessed. Logs are numbered from 1 to number_of_logs.</string>
		<string id="0-4064">
			Timestamp of last record fetched. The first record with a timestamp after this timestamp is returned. If this field is invalid, the first record in the data log is returned.
		</string>
		<string id="0-4065">
			Timestamp of last record fetched. The first record with a timestamp after this timestamp is returned. If this field is invalid, the first record in the data log is returned.
		</string>
		<string id="0-4066">Data log access response.</string>
		<string id="0-4067">Data log access response message format. Not used as a CP. This response has a variable size--unused fields are not included.</string>
		<string id="0-4070">Closest data log access protocol version.</string>
		<string id="0-4071">Closest data log access protocol version number supported by this device. Returned for LRC_VER_MISMATCH responses.</string>
		<string id="0-4072">Number of logs.</string>
		<string id="0-4073">Number of data logs in the device. Returned for LRC_BAD_LOG_INDEX responses.</string>
		<string id="0-3981">Log size.</string>
		<string id="0-3982">Capacity of a data log.</string>
		<string id="0-3987">Data log enable timestamp.</string>
		<string id="0-3988">Enables time stamping of each data value. When True, the data logger includes a timestamp of the receipt time for each value received by the data logger.</string>
		<string id="0-3983">Data log type.</string>
		<string id="0-3984">Specifies the method used to store data in a data log.</string>
		<string id="0-784">Low limit delay</string>
		<string id="0-785">The time limit during normal operation before the alarm air temp low alarm is recognized</string>
		<string id="0-782">Low limit temperature</string>
		<string id="0-783">The low alarm set point for the alarm air temp network variable</string>
		<string id="0-3381">Low limit 1 Enable</string>
		<string id="0-3330">Controls whether low limit 1 is in effect</string>
		<string id="0-3382">Low limit 2 Enable</string>
		<string id="0-3331">Controls whether low limit 2 is in effect</string>
		<string id="0-696">Setpoint, illumination level</string>
		<string id="0-697">The illumination level setpoint for the controller</string>
		<string id="0-822">Maintenance date</string>
		<string id="0-823">The date of last maintenance for the device</string>
		<string id="0-652">Manual override time</string>
		<string id="0-653">The maximum time that the controller will stay in a manual mode following the last request by a network variable input. Zero disables the timer.</string>
		<string id="0-824">Manufacture date</string>
		<string id="0-825">The date of manufacture for the device</string>
		<string id="0-732">Manual allowed</string>
		<string id="0-733">Provides a clock, with a manual time input, the possibility to permit manual time updating</string>
		<string id="0-724">Master-slave operation</string>
		<string id="0-725">Used to select master clock or slave clock, non-zero indicates this is master clock</string>
		<string id="0-1235">Maximum pre-positions</string>
		<string id="0-1236">The maximum number of pre-positions supported by a device</string>
		<string id="0-737">Maximum defrost time</string>
		<string id="0-1329">Maximum time for defrost to run if terminated on temperature</string>
		<string id="0-742">Defrost stop temperature</string>
		<string id="0-743">The temperature at which to terminate defrost for objects set to terminate on temperature</string>
		<string id="0-738">The maximum defrost time for defrost objects set to terminate on temperature</string>
		<string id="0-1297">Maximum discharge air cooling</string>
		<string id="0-1298">Setpoint for the maximum discharge air cooling</string>
		<string id="0-1301">Maximum discharge air heating</string>
		<string id="0-1302">Setpoint for the maximum discharge air heating</string>
		<string id="0-1267">Maximum duct static pressure</string>
		<string id="0-1268">Setpoint for maximum duct static pressure</string>
		<string id="0-3993">Maximum fan-in.</string>
		<string id="0-3994">
			Specifies the maximum number of data sources that may be connected to a network variable. The functional block determines data sources by examining the source address of each update.
		</string>
		<string id="0-3995">data sources</string>
		<string id="0-671">Maximum flow</string>
		<string id="0-979">The maximum flow</string>
		<string id="0-656">Maximum heating airflow</string>
		<string id="0-657">The maximum airflow setpoint of a VAV terminal while heating</string>
		<string id="0-1363">Setpoint for the operational high flow limit</string>
		<string id="0-2225">Unit maximum air flow</string>
		<string id="0-2226">Unit maximum airflow for dual duct VAV Terminal units</string>
		<string id="0-5059">Maximum Dim Voltage</string>
		<string id="0-2102">Maximum network variable length</string>
		<string id="0-2103">Maximum length of a type that may be assigned to the network variable</string>
		<string id="0-716">Maximum output value</string>
		<string id="0-717">The maximum value limit of the associated output network variable</string>
		<string id="0-3669">Maximum power.</string>
		<string id="0-3670">Power level at which the sunblind actuator detects a blocked motor and switches off automatically.</string>
		<string id="0-1356">Maximum pressure</string>
		<string id="0-1361">Setpoint for the operational high pressure limit</string>
		<string id="0-1233">Maximum privacy zones</string>
		<string id="0-1234">The maximum number of privacy zones supported by a device</string>
		<string id="0-446">Maximum receive time</string>
		<string id="0-447">The maximum time elapsed after the last update before the actuator adopts the default output</string>
		<string id="0-669">
			The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables
		</string>
		<string id="0-1371">Maximum remote flow</string>
		<string id="0-1372">Setpoint for the operational high flow limit (remote sensor)</string>
		<string id="0-1367">Maximum remote pressure</string>
		<string id="0-1368">Setpoint for the operational high pressure limit (remote sensor)</string>
		<string id="0-1375">Maximum remote temperature</string>
		<string id="0-1376">Setpoint for the operational high temperature limit (remote sensor)</string>
		<string id="0-1261">Maximum return/exhaust fan capacity</string>
		<string id="0-1262">Setpoint for maximum return/exhaust fan capacity</string>
		<string id="0-448">Maximum send time</string>
		<string id="0-449">The maximum period of time between consecutive transmissions of the current value</string>
		<string id="0-670">Maximum setpoint</string>
		<string id="0-1008">Either the maximum angle of rotation for an actuator or the maximum airflow for an actuator depending on actuator category</string>
		<string id="0-1398">Maximum stroke</string>
		<string id="0-1399">The maximum stroke limit</string>
		<string id="0-1257">Maximum supply fan capacity</string>
		<string id="0-1258">Setpoint for maximum supply fan capacity</string>
		<string id="0-5183">Measurement interval</string>
		<string id="0-5184">Time period used for a measurement</string>
		<string id="0-5185">seconds</string>
		<string id="0-1327">Minimum defrost time</string>
		<string id="0-1328">Minimum time for defrost to run if terminated on temperature</string>
		<string id="0-665">Damper angle send on delta</string>
		<string id="0-1006">The minimum change in damper actuator angle required to be treated as significant</string>
		<string id="0-549">Minimum delta CO2 level</string>
		<string id="0-550">The minimum change in CO2 level required to be treated as significant</string>
		<string id="0-668">Flow send on delta</string>
		<string id="0-1007">The minimum change in airflow required to be treated as significant</string>
		<string id="0-455">Send on delta</string>
		<string id="0-546">The minimum change required to force transmission of the output value</string>
		<string id="0-547">Minimum delta relative humidity</string>
		<string id="0-548">The minimum change in RH level required to be treated as significant</string>
		<string id="0-551">Minimum delta temperature</string>
		<string id="0-552">The minimum change in temperature required to be treated as significant</string>
		<string id="0-1299">Minimum discharge air cooling</string>
		<string id="0-1300">Setpoint for the minimum discharge air cooling</string>
		<string id="0-1303">Minimum discharge air heating</string>
		<string id="0-1304">Setpoint for the minimum discharge air heating</string>
		<string id="0-1269">Minimum duct static pressure</string>
		<string id="0-1270">Setpoint for minimum duct static pressure</string>
		<string id="0-673">Minimum flow</string>
		<string id="0-981">The minimum flow</string>
		<string id="0-674">Minimum heating airflow</string>
		<string id="0-982">The minimum airflow setpoint of a VAV terminal while heating</string>
		<string id="0-2227">Standby heating minimum air flow</string>
		<string id="0-2228">Heating or ventilated deck minimum flow of a dual duct VAV Terminal unit during occupied standby mode</string>
		<string id="0-1362">Setpoint for the operational low flow limit</string>
		<string id="0-675">Minimum flow for standby</string>
		<string id="0-983">The minimum flow through the VAV box in standby mode</string>
		<string id="0-2223">Unit minimum air flow</string>
		<string id="0-2224">Unit minimum air flow for dual duct VAV Terminal units</string>
		<string id="0-2239">Unit Heating Minimum Flow</string>
		<string id="0-2240">Minimum airflow setpoint of a single duct, or the unit minimum airflow setpoint of a dual duct VAV terminal when using a unit (local) heating source</string>
		<string id="0-2229">Standby unit minimum air flow</string>
		<string id="0-2230">Total unit minimum airflow for dual duct units during occupied standby mode</string>
		<string id="0-1283">Minimum outdoor air flow</string>
		<string id="0-1284">Setpoint for the default minimum outdoor air flow</string>
		<string id="0-1359">Minimum pressure</string>
		<string id="0-1360">Setpoint for the operational low pressure limit</string>
		<string id="0-1369">Minimum remote flow</string>
		<string id="0-1370">Setpoint for the operational low flow limit (remote sensor)</string>
		<string id="0-1365">Minimum remote pressure</string>
		<string id="0-1366">Setpoint for the operational low pressure limit (remote sensor)</string>
		<string id="0-1373">Minimum remote temperature</string>
		<string id="0-1374">Setpoint for the operational low temperature limit (remote sensor)</string>
		<string id="0-1263">Minimum return/exhaust fan capacity</string>
		<string id="0-1264">Setpoint for minimum return/exhaust fan capacity</string>
		<string id="0-451">Minimum send time</string>
		<string id="0-452">The minimum period of time between consecutive transmissions of the current value</string>
		<string id="0-672">Minimum setpoint</string>
		<string id="0-980">The minimum setpoint, such as minimum angle of rotation or minimum air flow</string>
		<string id="0-1396">Minimum stroke</string>
		<string id="0-1397">The minimum stroke limit</string>
		<string id="0-1259">Minimum supply fan capacity</string>
		<string id="0-1260">Setpoint for minimum supply fan capacity</string>
		<string id="0-1279">Mixed air low limit</string>
		<string id="0-1280">Setpoint for the mixed air low temperature limit</string>
		<string id="0-1281">Mixed air temperature</string>
		<string id="0-1282">Setpoint for the default mixed air temperature</string>
		<string id="0-734">Heart beat, mode output</string>
		<string id="0-735">The time that must pass without an update for mode definitions to be automatically retransmitted, zero disables</string>
		<string id="0-3641">Monitor Interval.</string>
		<string id="0-3642">This configuration property defines the interval over which statistics are collected and averages are calculated</string>
		<string id="0-3486">Name part 1</string>
		<string id="0-3511">
			Part 1 of the name of the functional block to be used by optional user interface applications. May optionally used with SCPTname2 and SCPTname3. Must be implemented as a configuration network variable.
		</string>
		<string id="0-3673">Character encoding.</string>
		<string id="0-3674">Character encoding method</string>
		<string id="0-3499">Name part 2</string>
		<string id="0-3500">
			Part 2 of the name of the functional block to be used by optional user interface applications. Must be used with SCPTname1 and may optionally be used with SCPTname3. This part is concatenated after part 1, and may optionally be followed by part 3. Must be implemented as a configuration network variable.
		</string>
		<string id="0-3706">Name part 3.</string>
		<string id="0-3707">
			Part 3 of the name of the functional block to be used by optional user interface applications. Must be used with SCPTname1 and SCPTname2. This part, if present, is concatenated with parts 1 and 2. Must be implemented as a configuration network variable.
		</string>
		<string id="0-3386">Neuron Identifier</string>
		<string id="0-3334">A unique 6-byte identifier for a CEA-709.1 / EN14908 device</string>
		<string id="0-1384">Night purge valve position</string>
		<string id="0-1385">Valve position in percent open for night purge</string>
		<string id="0-676">Nominal air flow</string>
		<string id="0-984">Value used in calculating the air flow in an airflow control actuator</string>
		<string id="0-2235">Heating nominal flow</string>
		<string id="0-2236">Nominal airflow volume of a hot or ventilation deck of a dual duct VAV terminal</string>
		<string id="0-677">Nominal angle</string>
		<string id="0-985">The nominal angle for an actuator</string>
		<string id="0-1046">Nominal motor frequency</string>
		<string id="0-1047">The nominal frequency of a motor</string>
		<string id="0-1044">Nominal motor speed</string>
		<string id="0-1045">The nominal speed of a motor in RPM</string>
		<string id="0-1247">Normal rotational speed</string>
		<string id="0-1248">The normal rotational speed in Hz</string>
		<string id="0-5171">Index of Functional Block</string>
		<string id="0-2237">Number of dampers</string>
		<string id="0-2238">Used to inform the controller if it is in a single or dual duct system</string>
		<string id="0-3239">Number of Digits on the Meter</string>
		<string id="0-3240">This configuration property is used for setting the total number of digits on the meter</string>
		<string id="0-678">Number of output valves</string>
		<string id="0-679">Used to inform the controller whether it is in a one-valve or two-valve system</string>
		<string id="0-2104">Network variable dynamic assignment</string>
		<string id="0-2105">Assigns a dynamic network variable to a functional block member</string>
		<string id="0-2106">Network variable index</string>
		<string id="0-2107">Network variable index within the device</string>
		<string id="0-2108">nv index</string>
		<string id="0-2109">Functional block index</string>
		<string id="0-2110">Index of the functional block to which the network variable is assigned</string>
		<string id="0-2111">fblock index</string>
		<string id="0-2112">Member number</string>
		<string id="0-2113">Member number of the functional block network variable member to which the network variable is assigned</string>
		<string id="0-2114">nv member number</string>
		<string id="0-3377">UNVT Flag</string>
		<string id="0-3378">Defines whether the NV is of SNVT (=0) or UNVT (=1)</string>
		<string id="0-3379">NV Declaration Index</string>
		<string id="0-3380">The member index from the profile</string>
		<string id="0-2079">Network variable type</string>
		<string id="0-2101">Network variable type for network variables that support changeable types</string>
		<string id="0-5220">NV usage</string>
		<string id="0-5219">The SCPTnvUsage CPs shall be used to indicate whether the NVs are in use by the loaded program</string>
		<string id="0-453">Network configuration source</string>
		<string id="0-454">The value of this field determines the source of the node&apos;s network configuration.</string>
		<string id="0-1036">Object major version number</string>
		<string id="0-1037">The major version number for the object</string>
		<string id="0-1038">Object minor version number</string>
		<string id="0-1039">The minor version number for the object</string>
		<string id="0-5455">Occupancy behavior</string>
		<string id="0-5456">Specifies mapping of scheduled occupancy values to primary occupancy states based on local occupancy inputs</string>
		<string id="0-5457">Invalid output value</string>
		<string id="0-5458">Primary occupancy value when the scheduled value is invalid (ob_nul) and a local occupancy condition is detected</string>
		<string id="0-5459">Occupied output value</string>
		<string id="0-5460">Primary occupancy value when the scheduled value is occupied (ob_occupied) and a local occupancy condition is detected</string>
		<string id="0-5461">Unoccupied output value</string>
		<string id="0-5462">Primary occupancy value when the scheduled value is unoccupied (ob_unoccupied) and a local occupancy condition is detected</string>
		<string id="0-5463">Bypass output value</string>
		<string id="0-5464">Primary occupancy value when the scheduled value is bypass (ob_bypass) and a local occupancy condition is detected</string>
		<string id="0-5465">Standby output value</string>
		<string id="0-5466">Primary occupancy value when the scheduled value is standby (ob_standby) and a local occupancy condition is detected</string>
		<string id="0-5487">Occupancy thresholds</string>
		<string id="0-5488">Specifies the minimum number of occupancy sensors that must report the same value to override a scheduled output value</string>
		<string id="0-5489">Occupied threshold</string>
		<string id="0-5490">
			Number of occupancy sensors that must be reporting occupied to report an occupied output when the current schedule specifies an occupied state; if the number of occupancy sensors reporting occupancy is below this value, the occupancy output is set to standby
		</string>
		<string id="0-5491">Standby to occupied override threshold</string>
		<string id="0-5492">
			Number of occupancy sensors that must be reporting occupied to report an occupied output when the current schedule specifies a standby state; if the number of occupancy sensors reporting occupancy is below this value, the occupancy output is set to standby
		</string>
		<string id="0-5493">Unoccupied to occupied override threshold</string>
		<string id="0-5494">
			Number of occupancy sensors that must be reporting occupied to report an occupied output when the current schedule specifies an unoccupied state; if the number of occupancy sensors reporting occupancy is below this value, the occupancy output is set to standby
		</string>
		<string id="0-682">OEM label</string>
		<string id="0-986">The label, programmed by the OEM, to identify the unit name</string>
		<string id="0-460">Turn-off delay</string>
		<string id="0-461">The length of time that the load remains energized after a change from ON to OFF has been received</string>
		<string id="0-553">CO2 level offset</string>
		<string id="0-496">Used to calibrate external hardware with additive offset after transformation</string>
		<string id="0-2231">Air flow offset</string>
		<string id="0-2232">Offset value used to calculate the active airflow setpoint by adding nciFlowOffset to nviAirFlowSetpt</string>
		<string id="0-554">Relative humidity offset</string>
		<string id="0-555">Temperature offset</string>
		<string id="0-700">Hysteresis, auto mode on/off</string>
		<string id="0-701">Sets the hysteresis for the level setpoint. Setting to zero disables automatic on/off switching</string>
		<string id="0-1347">Orientation</string>
		<string id="0-1348">The orientation angle of the display image (0 = landscape, 90 = portrait)</string>
		<string id="0-1287">Outdoor air enthalpy</string>
		<string id="0-1288">Setpoint for the outdoor air enthalpy economizer enable</string>
		<string id="0-1285">Outdoor air temperature</string>
		<string id="0-1286">Setpoint for the outdoor air temperature economizer enable</string>
		<string id="0-464">Override behavior</string>
		<string id="0-465">This parameter is used to define the behavior when an override request is received.</string>
		<string id="0-1251">Part number</string>
		<string id="0-1252">Manufacturer-defined part number string for the device</string>
		<string id="0-4000">Poll rate.</string>
		<string id="0-4001">
			Specifies the poll rate for each data source. When this value is greater than zero, the functional block polls each of the data sources identified in the source address array at the rate specified by this value.
		</string>
		<string id="0-706">Power-up state</string>
		<string id="0-707">The state of a light controller object after power-up or reset</string>
		<string id="0-957">Primary default value</string>
		<string id="0-958">The default output value when an area is occupied</string>
		<string id="0-5144">Command History</string>
		<string id="0-5145">Log of recent commands, with time stamp</string>
		<string id="0-5146">State History</string>
		<string id="0-5147">Log of recent status values, with time stamp</string>
		<string id="0-5142">File Indexes</string>
		<string id="0-5143">Indexes of first and last LonMark files where programs may be stored</string>
		<string id="0-5134">Program Name</string>
		<string id="0-5135">Name of currently loaded program</string>
		<string id="0-5136">Program Revision</string>
		<string id="0-5137">Revision number and date of currently loaded program</string>
		<string id="0-5138">Program Select</string>
		<string id="0-5139">Buffer Id where the currently loaded program is stored</string>
		<string id="0-5140">Source Location</string>
		<string id="0-5141">Location from where the current program was downloaded</string>
		<string id="0-3237">Pulse and Transformer Constant</string>
		<string id="0-3238">This configuration property is used to scale the raw pulse value to an energy-meter value</string>
		<string id="0-1352">Pump characteristic</string>
		<string id="0-1353">The basic characteristic data for a pump</string>
		<string id="0-1354">speedmax, pressmax, flowmax</string>
		<string id="0-1355">Maximum speed</string>
		<string id="0-1357">Maximum pressure at zero flow</string>
		<string id="0-1358">maximum flow at zero pressure</string>
		<string id="0-748">Pump down delay</string>
		<string id="0-749">The delay to use before starting the defrost</string>
		<string id="0-1319">Pulse-width modulation period</string>
		<string id="0-1320">The time period to be used in pulse-width modulation control strategy</string>
		<string id="0-3675">Power send on delta.</string>
		<string id="0-3676">The minimum change required to propoagate the output value</string>
		<string id="0-687">Power-up delay</string>
		<string id="0-989">The minimum period of time after power-up or re-establishment of communications before a control action takes place</string>
		<string id="0-688">Chiller enable</string>
		<string id="0-990">The default power-up and restart modes of the device when the default behavior selector is set to zero</string>
		<string id="0-1050">Minimum ramp-down time</string>
		<string id="0-1051">The ramp-down time of the device</string>
		<string id="0-1048">Minimum ramp-up time</string>
		<string id="0-1049">The ramp-up time of the device</string>
		<string id="0-5473">Randomization interval</string>
		<string id="0-5474">
			Specifies an interval around a scheduled time that is used by a scheduler to calculate a random event time.  Used to reduce simultaneous startup and shutdown of many devices by multiple schedulers.
		</string>
		<string id="0-5475">Earliest time offset</string>
		<string id="0-5476">Latest time offset</string>
		<string id="0-708">Reflection factor</string>
		<string id="0-709">The internal gain factor for the measured illumination level</string>
		<string id="0-756">Refrigerant glide</string>
		<string id="0-757">Used to characterize the glide of the refrigerant used</string>
		<string id="0-760">Refrigerant type</string>
		<string id="0-761">Refrigerant name, A, B, C</string>
		<string id="0-762">Refrigerant name</string>
		<string id="0-763">array of 6 characters</string>
		<string id="0-764">Constant A</string>
		<string id="0-765">Constant B</string>
		<string id="0-766">Constant C</string>
		<string id="0-1028">Register name</string>
		<string id="0-1029">The name of a utility data logger register device</string>
		<string id="0-1275">Return fan pressure</string>
		<string id="0-1276">Setpoint for the return fan static pressure</string>
		<string id="0-798">Running hours alarm threshold level</string>
		<string id="0-799">The alarm threshold for the running hours counter</string>
		<string id="0-796">Running hours counter initialization</string>
		<string id="0-797">The initial value of the running hours counter network variable</string>
		<string id="0-3223">Runtime Alarm</string>
		<string id="0-3224">This configuration property can be used to provide the alarm threshold for the run time counter output network variable</string>
		<string id="0-2241">Saturation delay</string>
		<string id="0-3667">Scan Time.</string>
		<string id="0-3668">Duration in which all devices are being queried</string>
		<string id="0-3495">Scene configuration</string>
		<string id="0-3713">
			Scene definition used to create a scene table. This SCPT defines the minimum entries required by the ISI profiles. May be used in combination with SCPTsceneTiming.
		</string>
		<string id="0-3714">Scene number used to uniquely identify a scene. A scene number to be recalled or learned is typically received from a SNVT_switch_2 or SNVT_scene input NV.</string>
		<string id="0-3715">Scene setting level</string>
		<string id="0-3717">Setting value that is applied when the scene specified by scene_number is recalled. Also used to set or specify a factor to be multiplied with the setting.</string>
		<string id="0-3716">% of full level</string>
		<string id="0-3718">Scene rotation angle</string>
		<string id="0-3719">Rotation angle that is applied when the scene specified by scene_number is recalled. Only applies to devices that support a rotation setting such as blinds.</string>
		<string id="0-3720">Unoccupied scene number.</string>
		<string id="0-3721">Scene to be activated when the scene specified by scene_number is active, and an unoccupied input is received.</string>
		<string id="0-4143">Scene color configuration</string>
		<string id="0-4144">
			Scene color definition used to supplement a scene table created with a SCPTscene array. This SCPT defines optional color scene table entries for the ISI profiles. When used, it must be used in combination with a SCPTscene array.
		</string>
		<string id="0-3671">Scene name.</string>
		<string id="0-3672">Name for a scene to be used by optional user interface applications. Used to create an array that supplements a scene table created with a SCPTscene array.</string>
		<string id="0-585">Scene number</string>
		<string id="0-718">The number of the first scene for the panel, other numbers are subsequent</string>
		<string id="0-719">Numeric selector</string>
		<string id="0-961">Scene offset</string>
		<string id="0-962">The offset for the scene number when data is forwarded from primary to secondary</string>
		<string id="0-3497">Scene timing configuration</string>
		<string id="0-3708">
			Scene timing definition used to supplement a scene table created with a SCPTscene array. This SCPT defines the optional scene table entries for the ISI profiles. When used, it must be used in combination with a SCPTscene array.
		</string>
		<string id="0-3709">Scene fade time</string>
		<string id="0-3710">
			Time to ramp to a new setting. Fading starts after any delay specified by the delay_time field, so the total time to move to a new value is delay_time plus fade_time seconds.
		</string>
		<string id="0-3711">Scene delay time</string>
		<string id="0-3712">Delay time from the time a new scene is selected until any change is made to the light intensity or appliance state.</string>
		<string id="0-2500">Schedule</string>
		<string id="0-2501">Describes the attributes of a daily schedule definition</string>
		<string id="0-2490">Temporary flag</string>
		<string id="0-2491">Identifies a temporary schedule. Temporary schedules are deleted at the end of the day that they are active</string>
		<string id="0-2502">Schedule priority</string>
		<string id="0-2503">
			Specifies the priority for this schedule. Low priority values specify high priority, and high priority values specify low priority. Zero (0) is the highest priority and 255 is the lowest
		</string>
		<string id="0-2504">Time-value array index</string>
		<string id="0-2505">
			Identifies the starting entry of a list of time-value events in a SCPTscheduleTimeValue array. The end of the list is identified by the terminator field in the SCPTscheduleTime entry
		</string>
		<string id="0-2482">Schedule dates</string>
		<string id="0-2483">A range of dates with an optional qualifier that specifies when a schedule is active</string>
		<string id="0-2484">Schedule start</string>
		<string id="0-2485">Starting year for schedule</string>
		<string id="0-2486">Starting month for schedule</string>
		<string id="0-2487">Starting day for schedule</string>
		<string id="0-2488">Schedule end</string>
		<string id="0-2489">Ending year for schedule</string>
		<string id="0-2492">Ending month for schedule</string>
		<string id="0-2493">Ending day for schedule</string>
		<string id="0-2494">Month qualifier</string>
		<string id="0-2495">Months within the dates specified by the start and end dates</string>
		<string id="0-2496">Days qualifier</string>
		<string id="0-2497">Days within the dates specified by the start and end dates</string>
		<string id="0-2498">Schedule number</string>
		<string id="0-2499">Index into a schedule or schedule name array</string>
		<string id="0-5469">Exception schedule</string>
		<string id="0-5470">An event that overrides a daily schedule; typically used for special events</string>
		<string id="0-5451">Friday schedule</string>
		<string id="0-5452">
			A structure containing an array of seven time-value pairs that specify the daily schedule for Friday; unused time-value pairs have an invalid value (31) for the hour; if two time-value pairs specify the same time, the first with a valid output value is used
		</string>
		<string id="0-5471">Holiday or vacation schedule</string>
		<string id="0-5472">An event that overrides a daily schedule; typically used for holiday or vacation event</string>
		<string id="0-1338">Internal schedule</string>
		<string id="0-1339">Enable internal scheduling</string>
		<string id="0-5445">Monday schedule</string>
		<string id="0-5446">
			A structure containing an array of seven time-value pairs that specify the daily schedule for Monday; unused time-value pairs have an invalid value (31) for the hour; if two time-value pairs specify the same time, the first with a valid output value is used
		</string>
		<string id="0-2463">Schedule name</string>
		<string id="0-2525">Used to create an array of names for schedules defined by a SCPTschedule array or a SCPTscheduleDates array.</string>
		<string id="0-5453">Saturday schedule</string>
		<string id="0-5454">
			A structure containing an array of seven time-value pairs that specify the daily schedule for Saturday; unused time-value pairs have an invalid value (31) for the hour; if two time-value pairs specify the same time, the first with a valid output value is used
		</string>
		<string id="0-5441">Sunday schedule</string>
		<string id="0-5442">
			A structure containing an array of seven time-value pairs that specify the daily schedule for Sunday; unused time-value pairs have an invalid value (31) for the hour; if two time-value pairs specify the same time, the first with a valid output value is used
		</string>
		<string id="0-5449">Thursday schedule</string>
		<string id="0-5450">
			A structure containing an array of seven time-value pairs that specify the daily schedule for Thursday; unused time-value pairs have an invalid value (31) for the hour; if two time-value pairs specify the same time, the first with a valid output value is used
		</string>
		<string id="0-2506">Schedule time-value pair</string>
		<string id="0-2507">Specifies the time and value for a scheduled event</string>
		<string id="0-2508">Invalid flag</string>
		<string id="0-2509">Identifies an undefined schedule entry</string>
		<string id="0-2510">Terminator flag</string>
		<string id="0-2511">Identifies the last entry in a time-value list</string>
		<string id="0-37">Hour</string>
		<string id="0-2512">Hours since midnight for a scheduled event</string>
		<string id="0-2513">Minute within the hour for a scheduled event</string>
		<string id="0-2465">Scheduler value</string>
		<string id="0-2514">Specifies the value to output when a time-value pair is active. The value must be mapped to a value that matches the type of the output network variable</string>
		<string id="0-5447">Tuesday schedule</string>
		<string id="0-5448">
			A structure containing an array of seven time-value pairs that specify the daily schedule for Tuesday; unused time-value pairs have an invalid value (31) for the hour; if two time-value pairs specify the same time, the first with a valid output value is used
		</string>
		<string id="0-5534">Wednesday schedule</string>
		<string id="0-5535">
			A structure containing an array of seven time-value pairs that specify the daily schedule for Wednesday; unused time-value pairs have an invalid value (31) for the hour; if two time-value pairs specify the same time, the first with a valid output value is used
		</string>
		<string id="0-5481">Alternate time source option flag</string>
		<string id="0-5482">Set to one if the device supports an alternate time source such as an interface to an NTP or SNTP server, GPS clock, or radio atomic-clock source</string>
		<string id="0-5483">General-purpose option flag</string>
		<string id="0-5484">Set to one if the general purpose output is supported; if zero, only the occupancy output is used</string>
		<string id="0-5485">Sunrise and sunset relative scheduling option flag</string>
		<string id="0-5486">Set to one if the scheduler supports sunsrise and sunset relative schedulign; set to zero if sunrise and sunset relative scheduling is not supported</string>
		<string id="0-1343">Scroll speed</string>
		<string id="0-1344">The scroll speed of the display image</string>
		<string id="0-959">Secondary default value</string>
		<string id="0-960">The default output value when the neighboring area is occupied</string>
		<string id="0-683">Temperature sensor constant</string>
		<string id="0-1009">Calibration value for a duct temperature sensor</string>
		<string id="0-1245">Serial number</string>
		<string id="0-1246">Manufacturer-defined serial number string for the device</string>
		<string id="0-680">Occupancy temperature setpoints</string>
		<string id="0-681">The occupancy temperature setpoints for heat and cool mode</string>
		<string id="0-2220">Sluice-lock master/slave control</string>
		<string id="0-2221">
			Role of a device in a sluice-lock connection. A sluice-lock is an interlock mechanism between two entry/exit devices, or a sluice manager and several entry/exit devices, to ensure that only one single entry/exit device is opened at any point in time.
		</string>
		<string id="0-661">Daytime alarm limit</string>
		<string id="0-662">The daytime alarm limit sensitivity value for the fire initiator in percentage obscuration by smoke</string>
		<string id="0-802">Daytime pre-alarm limit</string>
		<string id="0-803">The daytime pre-alarm limit sensitivity value for the fire initiator in percentage obscuration by smoke</string>
		<string id="0-780">Nighttime alarm limit</string>
		<string id="0-781">The nighttime alarm limit sensitivity value for the fire initiator in percentage obscuration by smoke</string>
		<string id="0-806">Nighttime pre-alarm limit</string>
		<string id="0-807">The nighttime pre-alarm limit sensitivity value for the fire initiator in percentage obscuration by smoke</string>
		<string id="0-659">Nominal sensitivity</string>
		<string id="0-660">The nominal sensitivity value for the fire initiator in percentage obscuration by smoke</string>
		<string id="0-4002">Source address.</string>
		<string id="0-4003">Specifies a source address or element of an array of source addresses for and input to a functional block.</string>
		<string id="0-4004">Subnet ID.</string>
		<string id="0-4005">ANSI/CEA-709.1 subnet ID.</string>
		<string id="0-4006">Reserved.</string>
		<string id="0-4007">Set to 0. Applications must ignore this bit.</string>
		<string id="0-4008">Node ID.</string>
		<string id="0-4009">ANSI/CEA-709.1 node ID. The value 0 is invalid.</string>
		<string id="0-1293">Space humidification</string>
		<string id="0-1294">Setpoint for the default space humidification</string>
		<string id="0-1249">Standby rotational speed</string>
		<string id="0-1250">The standby rotational speed in Hz</string>
		<string id="0-698">Maximum step</string>
		<string id="0-699">The maximum step that the associated controller may take to approach the target level</string>
		<string id="0-714">Step value, ramp or master fade</string>
		<string id="0-715">The step value for up/down ramps or fade control</string>
		<string id="0-744">Startup delay</string>
		<string id="0-745">The time to delay after power-up, defrost, or pack fail</string>
		<string id="0-752">Startup valve opening</string>
		<string id="0-753">Maximum valve opening to use after power-up, defrost, or pack fail</string>
		<string id="0-728">Summer time, start date and time</string>
		<string id="0-729">The start of summer time for purposes of daylight-savings time, all zeros disables</string>
		<string id="0-5477">Sunrise time</string>
		<string id="0-5478">
			Time used for sunrise-relative scheduling; must be implemented as a configuration network variable; only the time fields are used for scheduling--the date fields indicate the date used for the configured time
		</string>
		<string id="0-5479">Sunset time</string>
		<string id="0-5480">
			Time used for sunset-relative scheduling; must be implemented as a configuration network variable; only the time fields are used for scheduling--the date fields indicate the date used for the configured time
		</string>
		<string id="0-750">Super heat reference initialization</string>
		<string id="0-751">Default value for the super heat target network variable</string>
		<string id="0-758">Super heat reference maximum</string>
		<string id="0-759">Maximum value for the target super heat network variable</string>
		<string id="0-754">Super heat reference minimum</string>
		<string id="0-755">Minimum value for the target super heat network variable</string>
		<string id="0-1340">Temperature offset for calibration</string>
		<string id="0-1315">Temperature hysteresis</string>
		<string id="0-1316">General-purpose temperature hysteresis differential between on-point and off-point</string>
		<string id="0-746">Defrost termination setting</string>
		<string id="0-747">The defrost termination condition</string>
		<string id="0-811">Thermal rate of change/rise trip value</string>
		<string id="0-812">The thermal alarm trip rate of rise</string>
		<string id="0-602">Thermostat mode</string>
		<string id="0-767">The thermostat control strategy</string>
		<string id="0-832">Thermal alarm trip threshold</string>
		<string id="0-833">Thermal alarm trip threshold for the initiator</string>
		<string id="0-945">Time event entry</string>
		<string id="0-946">Event or mode definitions to be transmitted if the time in the record is reached</string>
		<string id="0-947">record type, hour, minute, event mode</string>
		<string id="0-948">Type of time event record</string>
		<string id="0-949">time event record type names</string>
		<string id="0-39">hours</string>
		<string id="0-41">minutes</string>
		<string id="0-950">Event mode information</string>
		<string id="0-951">event mode number</string>
		<string id="0-3235">Historical Period</string>
		<string id="0-3236">This input configuration network variable defines the period of time between transfer of a values to the historical register</string>
		<string id="0-5467">Time source</string>
		<string id="0-5468">Specifies the source of time</string>
		<string id="0-891">Time zone descriptor</string>
		<string id="0-952">Time zone of node (offset from GMT, start and end of DST)</string>
		<string id="0-1227">Response timeout</string>
		<string id="0-1228">The timeout for a controlling device to respond, during control permission request</string>
		<string id="0-456">Translation table X</string>
		<string id="0-457">Used in conjunction with Translation table Y to scale and linearize a value</string>
		<string id="0-3213">Valve-Plug Characteristic Table X</string>
		<string id="0-3214">
			This configuration property will be used in conjunction with the translation-table Y configuration property to create a translation table that dictates how to scale the flow with respect to the mechanical stroke
		</string>
		<string id="0-3219">Combination-Flow Characteristic Table X</string>
		<string id="0-3220">
			This configuration property will be used in conjunction with the translation-table Y configuration property to create a translation table that dictates how to scale the flow with respect to the valve capacity
		</string>
		<string id="0-458">Translation table Y</string>
		<string id="0-459">Used in conjunction with Translation table X to scale and linearize a value</string>
		<string id="0-3215">Valve-Plug Characteristic Table Y</string>
		<string id="0-3216">
			This configuration property will be used in conjunction with the translation-table X configuration property to create a translation table that dictates how to scale the flow with respect to the mechanical stroke
		</string>
		<string id="0-3221">Combination-Flow Characteristic Table Y</string>
		<string id="0-3222">
			This configuration property will be used in conjunction with the translation-table X configuration property to create a translation table that dictates how to scale the flow with respect to the valve capacity
		</string>
		<string id="0-726">Update rate, time stamp</string>
		<string id="0-727">The update rate of the master clock to the associated network variable</string>
		<string id="0-2517">Value name</string>
		<string id="0-2518">Used to create an array of value names for each of the values defined in a SCPTvalueDefinition array</string>
		<string id="0-2519">Name</string>
		<string id="0-2520">Nul-terminated name string of up to 22 characters. The nul terminator is not required if the string is 22 characters.</string>
		<string id="0-2380">array of 22 characters</string>
		<string id="0-1388">Valve flow characteristic</string>
		<string id="0-1389">Actual flow characteristic of the valve</string>
		<string id="0-3207">Valve Flow</string>
		<string id="0-3208">This configuration property can be used to provide the flow through an open valve at 1 bar differential pressure</string>
		<string id="0-3205">Nominal Valve Size</string>
		<string id="0-3206">This configuration property can be used to provide the nominal size of the valve body</string>
		<string id="0-1390">Valve operating mode</string>
		<string id="0-1391">The normal operating mode of the valve</string>
		<string id="0-3203">Valve Stroke</string>
		<string id="0-3204">This configuration property can be used to provide the stroke to fully open the valve</string>
		<string id="0-3209">Valve Type</string>
		<string id="0-3210">This configuration property can be used to provide the valve type</string>
		<string id="0-813">Visible light output intensity</string>
		<string id="0-814">Visible light output intensity specification of the device at 0 deg viewing angle</string>
		<string id="0-815">candela</string>
		<string id="0-2521">Weekly schedule</string>
		<string id="0-2522">Identifies a schedule to be active for each day of the week</string>
		<string id="0-2523">Time-value index array</string>
		<string id="0-730">Winter time, start date and time</string>
		<string id="0-731">The start of winter time for purposes of daylight-savings time, all zeros disables</string>
		<string id="0-808">Zone number</string>
		<string id="0-809">The zone number for the device</string>
		<string id="0-810">zone number</string>
	</strings>